Rev.00
6
DOP(Communication setting
group)
press
key decide DOP setting group,press
key into ADDR setting
page
6-1
ADDR(Communication –
Address setting page )
Default = 0
1.Decide address with
or
or
key(0~255)
2.Press
key enter data and into BAUD setting page
6-2
BAUD(Communication Baud
Rate setting page)
Default = 19200
1.Decide baud rate with
or
key(38400,19200,9600,4800,2400)
2.Press
key enter data and into PARI setting page
6-3
PARI(Communication Parity
Check setting page)
Default = n82
1.Decide parity check with
or
key(n82,n81,even,odd)
2.Press
key enter data and return DOP setting group
7
AOP(Analog output setting
group)
Press
key decide AOP setting group , press
key into AO.SEL
setting page
7-1
AO.SEL(Analog Output
Select)
Default = DISP3
1.Decide Analog Output Select with
or
key(DISP1,DISP2,DISP3)
2.Press
key enter data and into ANLO setting page
7-2
ANLO(A/O Zero According
to Display setting page)
Default = 0
1.Decide A/O Zero According to Display with
or
or
key
(-19999~99999)
2.Press
key enter data and into ANHI setting page
7-3
ANHI(A/ O Span According
to Display setting page)
Default =10000
1.Decide A/ O Span According to Display with
or
or
key
(-19999~99999)
2.Press
key enter data and return AOP setting group
Step
Parameter mark description
Parameter mark Operation manual
8
Normal display
Press
/ALARM key about 3 sec,into AL1 setting page
8-1
AL1 (Alarm 1)
Default = 0
1.Decide Alarm 1 with
or
or
key(-19999~99999)
2.Press
key enter data and into AL2 setting page
8-2
AL2 (Alarm 2)
Default = 0
1.Decide Alarm 2 with
or
or
key(-19999~99999)
2.Press
key enter data and into AL3 setting page
8-3
AL3(Alarm 3)
Default = 0
1.Decide Alarm 3 with
or
or
key(-19999~99999)
2.Press
key enter data and into AL4 setting page
8-4
AL4(Alarm 4)
Default = 0
1.Decide Alarm 4 with
or
or
key(-19999~99999)
2.Press
key enter data and return normal display
Step
Parameter mark description
Parameter mark Operation manual
9
Normal display
Press
/A-ADJkey about 3 sec,into AZERO adjustment page
9-1
AZERO(Analog Output
Zero Adjustment page)
Default = 0
1.Adjustment analog output zero with
or
or
key(
±
6000)
2.Press
key enter data and into ASPAN adjustment page
9-2
ASPAN(Analog Output
Span Adjustment page)
Default = 0
1.Adjustment analog output span with
or
or
key(
±
6000)
2.Press
key enter data and return normal display
Appendix Error Mark description
Error Mark
Analyze & Description
1
Input over range error detect
Input signal over the maximum input range (0~25KHz)
2
Display over range error detect
Input signal over the maximum display range (99999)
3
Display under range error detect
Input signal under the minimum display range (-19999)
4
EEPROM error detect
1.External interference when EEPROM read/write
2.EEPROM write over 1 million times(guarantee 10 years)
Please power reset,if still display E-00,doing following step:
1.
E-00 & No alternate display for inquire reset EEPROM
2.
Decide Yes with
or
key,press
key return n
ormal display
3.
EEPROM was reset,Please follow step 1~9 set again