AXE MMRD-M Series Скачать руководство пользователя страница 1

 

                                                                                                                                                                                                      Rev.00 

AXE 

 

MICROPROCESS DUAL INPUT(MATH FUNCTION) RPM & LINE-SPEED CONTROLLER METER 

 

MMRD-M Series

 

■ 

Features

 

Dual input measure and display sensor pulse or AC signal   

16BIT DAC analog output can be modified,     

Accuracy 0.03% F.S. 

Four independent alarm with delay and hysteresis function 

Input range(0~25KHz) 

RS485 Communication interface, Protocol MODBUS RTU MODE

 

Readout range D1/D2(0~99999),D3(-19999~99999) 

BAUD RATE:38400/19200/9600/4800/2400

 

RPM or LINE-SPEED can be modified 

0.4" LED highlight display 

Dual input math function(B-A,(B+A)/2,B/A,(B/A)-1,1-(B/A),B/(A+B))

 

Decimal point can be modified

 

Input pulse per revolution can be modified(1~99999) 

Man-machine interface, easy to operate 

Diameter(LINE-SPEED)/Scale(RPM) can be modified(0.0001~9.9999) 

EEPROM Saving, data safekeeping about 10 years 

Display average times can be modified(1~99)

 

Modified inside parameter, must have pass code 

  Name of Parts

 

 

■ 

Connect Diagram

 

Input function jumper table 

  Contact input (PNP) 

  Sensor input (PNP 5V/12V) 

 
 
 
 
 
 

Position 1 ON:IN(A)/IN(B) -> (NPN)

 

  Contact input (NPN) 

  Sensor input (NPN 5V/12V) 

 

Position 1 OFF:IN(A)/IN(B) -> (PNP) 

 

Position 2 ON :IN(A)/IN(B) -> (0~50HZ) 

 

Position 2 OFF:IN(A)/IN(B) -> (0~25KHZ)

 

■ 

Alarm Function description

 

◎ 

When ACT=HI,DEL= 0 :              Display value >    Setting value(AL) + Hysteresis (HYS) 

à

 (Relay on) 

Display value <=    Setting value(AL) - Hysteresis (HYS) 

à

 (Relay off) 

◎ 

When ACT=LO,DEL= 0 :              Display value >= Setting value(AL) + Hysteresis (HYS) 

à

 (Relay off) 

Display value <    Setting value(AL) - Hysteresis (HYS) 

à

 (Relay on) 

◎ 

When ACT=HI,DEL= 1 ~ 99 sec.: Display value >    Setting value(AL) + Hysteresis (HYS) + Delay time(DEL) 

à

 (Relay on) 

Display value <=    Setting value(AL) - Hysteresis (HYS) 

à

 (Relay off) 

◎ 

When ACT=LO,DEL= 1 ~ 99 sec.: Display value >= Setting value(AL) + Hysteresis (HYS) 

à

 (Relay off) 

Display value <    Setting value(AL) - Hysteresis (HYS) + Delay time(DEL) 

à

 (Relay on) 

◎ 

When ACT=HI,DEL= -1 ~ -99 sec.:Display value >    Setting value(AL) + Hysteresis (HYS) 

à

 (Relay one shoot(DEL) and then off) 

Display value <= Setting value(AL) - Hysteresis (HYS) 

à

 (Relay restore normal after the procedure) 

◎ 

When ACT=LO,DEL= -1~ -99 sec.:Display value >= Setting value(AL) + Hysteresis (HYS)

à

(Relay restore normal after the procedure) 

Display value <    Setting value(AL) - Hysteresis (HYS) 

à

 (Relay one shoot(DEL) and then off) 

Key Introduce 

Operation Manual 

Key Function 

1.In normal display,The key function is call out setting group 
2.In parameter setting page,The key function is data Enter , and goto next page 

Key Function 

1.In normal display,The key function is call out alarm value setting page 
2.Into parameter setting page,the parameter mark&data is alternate display,If need modify data can press

key into setting procedure,The display is lock parameter data,this time must let off key about 0.2 

sec,press again,the cursor(twinkle express)is cycle moving left. (Key Response about 0.2 sec) 

COM 

IN 

12V 

Inside jumper 

SW1  SW2 

ON 

ON 

OFF 

OFF 

COM 

IN 

12V 

Sensor 

Inside jumper 

SW1  SW2 

OFF 

OFF 

OFF 

OFF 

4    3    2    1 

SW1 

4    3    2    1 

SW2 

COM 

IN 

12V 

COM 

IN 

12V 

Sensor 

  Inside jumper 

SW1  SW2 

ON 

ON 

ON 

ON 

  Inside jumper 

SW1  SW2 

ON 

ON 

OFF 

OFF 