Cabling requirements APPARTMENT system

Topology: Star network

The maximum length of cabling is limited. The use of other cables then subscribed could influence 

the maximum length of cabling and cause interferences.

Up to 20 monitors in the installation

A

B

C

Twisted pair without shielding (2x 0.75mm²)

60m

60m

30m

Twisted pair without shielding (2x 1mm²)

80m

80m

40m

Upward from 20 monitors in the installation

A

B

C

Twisted pair without shielding (2x 1mm²)

70m

30m

20m

Twisted pair without shielding (2x 1.5mm²)

70m

50m

30m

A

:  Maximum length between PSU and door station

B:

  Maximum length between PSU and the last distributor

C:

  Maximum length 

  between distributor 

  and the last monitor

A

B

C

In a star network all devices communicate through distributors. The advantage of such a star topo-

logy is that ‘local’ problems are contained and do not influence the entire network. Star networks 

are very adequate for renovating projects where an existing intercom has to be exchanged. A star 

network requires more cabling than a serial network.

PSU

Distributor

Distributor

Important!

Switch terminating resistance ON on accessories and monitors with this symbol. 

Содержание entrya Facila

Страница 1: ...Installation Guide 2017 Facila...

Страница 2: ...e 8 Multiple monitors with multiple distributors 8 Camera module 9 Multiple door stations and a lock module with a distributor 9 Cabling requirements APPARTMENT system 10 Topology Star network 10 Topo...

Страница 3: ...ions between devices In a FACILA BUS the data audio power and vide osignals have been integrated on two wires When a connected device on a BUS wants to commu nicate with another device on the same BUS...

Страница 4: ...impedance switch is switched on at the monitor and distributor which are last on the BUS line Double twisted cable Connect half colored wires and full colored wired to twist twisted wires Use the brow...

Страница 5: ...elding 2x 0 75mm 60m 40m Twisted pair without shielding 2x 1mm 80m 60m A Maximum cable length between PSU and door station B Maximum cable lenght between PSU and the last monitor A B Topology Cascade...

Страница 6: ...etween PSU and the last distributor C Maximum cable length between distributor and the last monitor B C In a star network all devices communicate through distributors The advantage of such a star topo...

Страница 7: ...no other device may have this address Example schematics Basic schematic Basic schematic with lock module Multiple door stations with a distributor Multiple monitors with a distributor Multiple monit...

Страница 8: ...uide are protected by copyright and intellectual property of ENTRYA BVBA v1710v31 8 Multiple monitors with distributor in combination with a lock module Multiple monitors with multiple distributors PS...

Страница 9: ...exts and images in this guide are protected by copyright and intellectual property of ENTRYA BVBA 9 Camera module PSU Multiple door stations and a lock module with a distributor PSU Distributor Lock m...

Страница 10: ...Twisted pair without shielding 2x 1mm 70m 30m 20m Twisted pair without shielding 2x 1 5mm 70m 50m 30m A Maximum length between PSU and door station B Maximum length between PSU and the last distribut...

Страница 11: ...werk is dan ook geschikt voor nieuwbouwprojecten Een serienetwerk vereist minder kabels dan een sternetwerk maar bij problemen wordt het volledige netwerk verstoord A Maximum length between PSU and do...

Страница 12: ...has address 15 no other device may have this address Example schematics Basic schematic Basic schematic with lock module Multiple door stations with distributor Multiple monitors with distributor Mul...

Страница 13: ...nd intellectual property of ENTRYA BVBA 13 Multiple monitors with a lock module and a distributor Multiple monitors with multiple distributors PSU PSU Distributor Lock module Important Switch terminat...

Страница 14: ...and images in this guide are protected by copyright and intellectual property of ENTRYA BVBA v1710v31 14 Camera module PSU Multiple door stations with lock module and distributors PSU Distributor Loc...

Страница 15: ...s installed at the end of the BUS line to guarantee that the required tension does not go below 23V DC Before installing a supplementary PSU it is important that one measures the tension on the BUS wh...

Страница 16: ...AL 8019 or NTSC 8020 8018 8020 Unlocking time between 1 9 s 8021 8029 Indicating light will light up in red green blue yellow or purple when calling 8040 8044 Indicating light will blink red green blu...

Отзывы: