Installation 

Avtron Load Bank  •  Part Number K711D36027 

 
 

 

3-3 

The Load Bank must be used in a cool, well ventilated area.  It must be installed where cool air is 
continually available and where hot exhaust air will not be recirculated through the Load Bank. The 
Load Bank must not be operated in a closed space. 
 
The exhaust air may exceed 300

F above ambient under full load conditions.  The unit must not be 

installed near any equipment, wiring, or plumbing which may be damaged by high air temperatures 
or which may constitute a fire hazard.  
 
 
 

AIRFLOW CONSIDERATIONS 
 

Even with an ample supply of cooling air, the Load Bank may overheat if it is not properly installed.  
There are two types of airflow problems that should be avoided: 
 
  1. 

Recirculating Airflow - If the hot, exhausted air is permitted to recirculate through the Load 
Bank, it will reach such a high temperature and low density that it will no longer cool the 
elements.  A Load Bank should not be installed so close to any surface as to reflect the 
exhausted air back to the air intake.   

 
  2. 

Restriction of Cooling Air - Any obstruction located within five (5) feet of the inlet and 
twelve (12) feet of the exhaust hood (duct) will restrict the Load Bank's airflow.  Airflow is 
also restricted when two or more Load Banks have air inlets positioned close to each other.  
This competition for cooling air causes a low pressure area, restricting adequate airflow. 

 
  3. 

The Load Banks are designed to tolerate up to 0.25" water gage additional system airflow 
resistance.  This includes air intake resistance (building make up air pressure) and resistance 
due to exhaust duct/louvers/screen. 

 
  4. 

If exhaust duct exits through motorized louvers, the design must be interlocked to assure full 
open prior to operation.  Consideration must also be given for louver design and actuator to 
prevent heat problems. 

 
Consult the factory if strong prevailing winds exist. 
 
 
 

CONTROL CONNECTIONS 

 
The control panel is supplied mounted in a 19-inch rack-type enclosure.  Connect terminals of the 
control panel to terminals of the Load Bank as shown on the schematic/interconnection diagram 
D36028. 
 
Control power is derived from an externally supplied 480V, 3-phase, 60 Hz power source connected 
to the Load Bank terminal block TB1 terminals 19 and 20 as shown on schematic D36028. 
 
 
 
 
 
 

Содержание K711

Страница 1: ...AVTRON MODEL K711 LOAD BANK Part Number K711D36027 600 kW 480 VAC 3 Phase 60 Hz 50 50 100 100 100 100 and 100 kW CFM REQUIRED 61152 2004 Avtron Manufacturing Inc Cleveland Ohio...

Страница 2: ...TENANCE 5 1 Section VI REPLACEMENT PARTS LIST 6 1 APPENDIX Avtron Load Bank Troubleshooting Guide SUPPLEMENTAL INFORMATION Avtron Bulletin 202 Installation Notes Engine Generator Duct Type Load Banks...

Страница 3: ...because the function of the Load Bank is the dissipation of electrical energy there are inherent dangers to operators and equipment These dangers are outlined in this section Electrical energy is tra...

Страница 4: ...some time after operation These portions of the Load Bank become quite hot and may result in a serious burn should contact be made with them 10 Do not allow objects to enter or block the air intake o...

Страница 5: ...the Load Bank will apply load blocks of 100 150 150 and 200 kW sequentially After an adjustable exercise period the load steps will be removed based upon adjustable timed settings The control panel c...

Страница 6: ...D AVTRON CAN PROVIDE START UP SERVICE AT A NOMINAL CHARGE AVTRON ALSO WILL PROVIDE TELEPHONE ASSISTANCE IF REQUIRED BY CALLING 216 641 8310 1 Verify the Load Bank placement meets the installation requ...

Страница 7: ...hin 10 of the required voltage W A R N I N G Control power is present on terminal block in steps 4 through 6 5 Verify the proper relays energize with each individual load switch A Turn on each load st...

Страница 8: ...triction of Cooling Air Any obstruction located within five 5 feet of the inlet and twelve 12 feet of the exhaust hood duct will restrict the Load Bank s airflow Airflow is also restricted when two or...

Страница 9: ...ies of these load connections are shown on the Load Bank schematic diagram D36028 GROUNDING A permanent ground conductor must be connected to the Load Bank enclosure by an individual ground wire to pr...

Страница 10: ...ntrol panel to the OFF position Place MODE SELECT MANUAL AUTOMATIC operation toggle switch to MANUAL position 2 Verify that all electrical connections Control Load and Grounding to the Load Bank have...

Страница 11: ...TIC OPERATION 1 Place all switches on the control panel to the OFF position Place MODE SELECT MANUAL AUTOMATIC operation toggle switch to the AUTOMATIC position 2 Verify that all electrical connection...

Страница 12: ...programmed exercise cycle controlled by K215 will allow the engine generator to cool down under a no load condition When the proper temperature is sensed K51 will energize K51 will initiate the adjus...

Страница 13: ...sonal injury from electrical shock or from the moving fan blade may result if ALL sources of power are not disconnected Refer to the SAFETY CONSIDERATIONS section of this manual Eye protection should...

Страница 14: ...he hardware where required 5 Inspect all magnetic contactors to make sure that the contacts are not severely pitted or corroded The contacts must move freely and be properly seated 6 Clean all dirt an...

Страница 15: ...s information However changes are sometimes necessary and revisions to the parts list may be made at any time without notice REFERENCE DESIGNATORS Service personnel may use this parts list along with...

Страница 16: ...STRUMENT 370908 2 TRANSFORMERS 7RBT801 CONTROL ENCLOSURE ASSEMBLY D36083 1 SCHEMATIC INTCON DIAGRAM D36028 REF S50 SWITCH TOGGLE CARLINGSWITCH 360591 1 2GL54 73 S1 7 20 21 SWITCH TOGGLE CARLIGSWITCH 3...

Страница 17: ...3SQ XF102 103 FUSE 3A 600V LITTELFUSE 324453 2 KLDR 3 F104 106 FUSE 1A 600V LITTELFUSE 324449 3 KLDR 1 K202 204 206 RELAY TIME DELAY CROUZET 351981 4 208 88 865 215 XK51 201 210 SOCKET RELAY POTTER BR...

Отзывы: