Avtech RMA-FTL1-SEN Скачать руководство пользователя страница 4

  

 

Page 4 

Tank Level Sensors (RMA-FTL1-SEN & RMA-FTL2-SEN, RMA-WTL1-SEN & RMA-WTL2-SEN)

AVT-171211-2.1.0

Sensor Features & Specifications

Environment Condition Monitored

Water Tank Level Sensor

High/low fluid level (water)

Fuel Tank Level Sensor

High/low fluid level (fuel or other harsh liquids)

Type Of Sensor

Switch

Normal State

Float Switch face in downward position

RMA-FTL1-SEN & RMA-WTL1-SEN (NC)

Closed

RMA-FTL2-SEN & RMA-WTL2-SEN (NO)

Open

Alarm State

Float Switch face in upward position

RMA-FTL1-SEN & RMA-WTL1-SEN (NC)

Open

RMA-FTL2-SEN & RMA-WTL2-SEN (NO)

Closed

Sensor Cable Type

Low-voltage two-wire PVC-coated cable

Included

Yes

Length

16'

Extension Cable Type

Low-voltage two-wire speaker cable

Included

Yes

Length

25'

Maximum Extendible Length

900'

Dimensions

Water Tank Level Sensor

Float Switch: 5.0" h x 3.0" w

Control Weight: 4.25" h x 2.13" w

Fuel Tank Level Sensor

Float Switch: 6.1" h x 6.70" w

Control Weight: 4.25" h x 2.13" w

Switch State Differential

Water Tank Level Sensor

Minimum = 10” / Maximum = 40”

Fuel Tank Level Sensor

Minimum = 10” / Maximum = 50”

Maximum Liquid Temperature

140º F (60º C)

Maximum Pressure

28 psi (pounds per square inch)

Minimum Fluid Specific Gravity

Water Tank Level Sensor

0.95

Fuel Tank Level Sensor

0.7

Protection Rating

IP67, NEMA 6

Compatible Products

Any Room Alert model or Wireless Sensor Hub