16
4. Wire the Photocell to the Control unit and cut cable to the required length.
Note:
The AC version of the Control Unit with remote monitoring is shown throughout
this installation procedure. Details regarding the DC installation are shown on page 19.
Wiring instructions-Power and Data Cable:
•
Connect the black positive conductor from the External Photocell to circuit breaker 5
(labelled ‘PC +24VDC’) on terminal block 1 in the Control Unit
•
Connect the white negative conductor from the External Photocell to the ‘PC
-Common’ labelled terminal on terminal block 1 in the Control Unit
•
Connect the green Photocell signal conductor to the ‘PC Signal’ labelled terminal on
terminal block 1 in the Control Unit
Refer to the AV-OL-KT-A1/I2 Installation and Service manual for recommended cable sizes.