page 3
INTRODUCTION / DESCRIPTION
The American AVK Series 67 Post / Flushing Hydrant is designed to be a trouble free, easy to maintain hydrant.
This manual will provide you with the information needed to properly install and maintain the fire hydrant and to ensure a
long service life. Features of the American AVK Series 67 Post / Flushing Hydrant include an EPDM encapsulated one piece
main valve and a stainless steel upper stem. The series 67 is rated for a working pressure of 250 psi, meets or exceeds the
requirements of AWWA C502, Standard for Dry Barrel Fire Hydrants, (where applicable). The AVK Series 67 hydrant and
hydrant tools are designed so that one person can perform all repairs and maintenance outlined in this manu
al.
RECEIVING AND STORAGE
Inspect the hydrants upon receipt for damage in shipment. Note any damage on the bill of lading and have the driver
sign it. Notify American AVK. Unload all of the hydrants carefully to avoid damage. Verify that the hydrants have the correct
direction to open, the correct nozzle configuration and threads, the correct operating nut size and shape, the correct depth
of bury, and the correct inlet connection. Hydrants should remain clean and dry, and the main valve should be closed until
installed to prevent weather related damage. For long term storage the hydrants should be stored indoors.
INSTALLATION AND TESTING
NOTE:
American AVK recommends AWWA Standard C600 and AWWA Manual M17 for further information
regarding hydrant installation and testing.
NOTE:
Consult local codes and standards for proper fire hydrant placement and spacing
WARNING:
All water lines must be isolated or depressurized and drained before installing or maintaining fire
hydrants. Failure to do so may cause pressure to be released resulting in severe injury or death.
INSTALLATION
Correct installation of the Series 67 Post / Flushing Hydrant is important for proper operation. The following steps are
general installation guidelines for a standard AVK Series 67 fire hydrant. Local conditions may require variations.
1.
Before installing a hydrant, check to make sure all bolts are tight and all nozzles are properly installed (See
NOZZLE INSTALLATION). Clean any dirt and debris from inside the hydrant base and from the pipe lead.
2.
Install AVK Series 67 Post hydrants with the valve below the frost line and install adequate drainage, such as gravel.
Support all hydrants in upright positions. All hydrants shall be installed plumb. Include a separate gate valve or curb
valve and restraining joints in supply piping. Refer to Fig.1, Hydrant Installation.