• Concrete Encased Ground. An electrode encased by 

at least 2 in. (5.1 cm) of concrete and located 
within and near the bottom of a concrete foundation 
or footing in direct contact with the earth. The 
electrode must be at least 20 ft. (6.1 m) of one or 
more steel reinforcing bars or rods, 1/2-in. (1.3 cm) 
in diameter, or at least 20 ft. (6.1 m) of bare solid 
copper, 4 AWG (26 mm

2

) wire.

• Ground Ring. A buried ground that encircles a 

building or structure at a depth of at least 2.5 ft 
(0.76 m) below the earth’s surface. The ground ring 
must be at least 20 ft. (6.1 m) of 2 AWG (35 mm

2

), 

bare copper wire.

• Approved Floor Grounds. Floor grounds are those 

grounds on each floor of a high-rise building that 
are suitable for connection to the ground terminal 
in the riser closet and to the cabinet single-point 
ground terminal. Approved floor grounds may 
include the following:

- Building steel.

- The grounding conductor for the secondary side 

of the power transformer feeding the floor.

- Metallic water pipes.

- Power-feed metallic conduit supplying panel 

boards on the floor.

- A grounding point specifically provided in the 

building for that purpose.

WARNING:

 

If the approved ground or approved floor 

ground can only be accessed inside a dedicated power 
equipment room, then connections to this ground must be 
made by a licensed electrician.

Connect the safety ground

Proper grounding of the i120 installation safeguards 
the system, users, and service personnel by providing 
protection from lightning, power surges, AC mains 
faults, power crosses on central office trunks, and 
electrostatic discharge (ESD).

Local electrical installation codes must be followed 
when installing the i120.

DANGER:

 

Connection of both grounds (through the AC 

Power Cord and the Supplementary Ground Conductor) is 
required for safe operation of the i120.

WARNING: 

An improper ground can cause electrical 

shock as well as equipment failures and service outages.

Attaching the ground wires

1. Remove the ground screw on the rear of the i120 

adjacent to the ground symbol. 

2. Place the ring terminal of the 10 AWG (4.0 mm

2

Supplementary Ground Conductor on the screw.

3. Replace the ground screw on the i120 and securely 

tighten the screw such that it cannot be loosened 
without the use of a tool.

If the ground block has been purchased

1. Cut the Supplementary Ground Conductor (which 

has one end attached to the grounding screw on the 
i120) to the length needed to terminate it into one 
of the terminals of the ground block. Do not coil the 
Supplementary Ground Conductor. 

2. Attach one end of the remaining 10 AWG (4 mm2) 

ground wire to one of the terminals in the ground 
block and the other end to an approved ground. 

3. Cut this ground wire to the length needed to reach 

the approved ground. Do not coil this wire.

Note:

 The ground block is provided for use with more 

than one i120 in the rack. It is usually mounted by the 
customer electrician.

If the ground block is not being used

Attach the Supplementary Ground Conductor to an 
approved ground.

Connect

Connect your Avaya Distributed Office to your 
telephone, computers, and network. Refer to the 
enclosed Installation Poster for information.

Connect your computer to the Services port on the 
AM110, using an Ethernet cable.

Содержание i20

Страница 1: ... your Avaya Distributed Office 4 Connect your Avaya Distributed Office to your telephones computers and network See the Installation Poster Connect your computer to the Services port on the AM110 using an Ethernet cable 5 Power up your Avaya Distributed Office The PWR LED and the CPU LED on the front panel illuminate to indicate that the installation is successful 6 Configure Point your Web browse...

Страница 2: ...according to the following table You might also need wire cutters to attach the grounding conductors if your site uses a ground block To configure your i120 you will need a computer with a screen resolution of 1024x768 pixels or higher and either Internet Explorer 6 0 or higher or Mozilla Firefox 1 5 or higher Unpack The Avaya Distributed Office i120 is shipped with the following items If any item...

Страница 3: ...s without cable guides to Each side of the front of the i120 so that the front of the i120 is flush with the rack The middle of each side panel of the i120 so that the i120 projects forward from the rack You can attach a mounting bracket with cutouts that guide cables to the side of the i120 These cutouts provide easier access to the front panel and help you manage the placement of the cables To r...

Страница 4: ...8 3 0 8 thick 415 x 465 mm 20 mm thick to the wall with wood screws and fasten the i120 to the board Ground To assure safe installation and operation carefully read all requirements recommendations and instructions Pay special attention to all WARNING and DANGER statements V6 V2 V1 V7 V5 V4 V3 US B CO NS OL E RS T AS B Inte rfac e USB Inte rfac e Con sole SYSTEM MD M ALM CP U PW R ET H LA N Por t ...

Страница 5: ... and the CE Mark on the product as well as allow a hazard to be present that could result in death or severe personal injury Restricted access location In Finland and Norway the i120 must be installed in a Restricted Access Location due to unreliable earthing concerns A Restricted Access Location is defined as access that can be gained by only Service Personnel or Customers who have been instructe...

Страница 6: ...ts power crosses on central office trunks and electrostatic discharge ESD Local electrical installation codes must be followed when installing the i120 DANGER Connection of both grounds through the AC Power Cord and the Supplementary Ground Conductor is required for safe operation of the i120 WARNING An improper ground can cause electrical shock as well as equipment failures and service outages At...

Страница 7: ...he level of configuration you need to do Distributed Office Local Manager Main screen If your i120 arrives fully configured the Distributed Office Local Manager Main screen is displayed You may now start using your i120 V7 V5 V4 V3 USB CONSOLE RST ASB Interface USB Interface Conso le SYSTEM MDM ALM CPU PW R ETH LAN Port 10 3 CCA Interface FastE thern et 10 2 Contact Closure 10 1 LIN E 3 LIN E 2 TR...

Страница 8: ... the Profile Based Setup Assistant home screen Click Start to run the Profile based Setup Assistant The Profile Based Setup Assistant is displayed the actual screen may differ from this one Initial Setup Assistant Home Screen The Initial Setup Assistant applies to Distributed Office i120 solutions that require complete configuration and should only be reached if the unit was re initialized Check y...

Страница 9: ...9 ...

Страница 10: ...cumentation 03 600758 and Avaya Support Notices for Hardware Documentation 03 600759 These documents can be accessed on the documentation CD and on the Web site http www avaya com support On the Web site search for the document number in the Search box avaya com COMMUNICATIONS AT THE HEART OF BUSINESS 03 602289 ...

Отзывы: