background image

DC power supply installation navigation

Determining the minimum number of DC power supplies

 on page 27

Preparing cables for installation

 on page 27

Removing the power filler panel

 on page 28

Installing the DC power supply

 on page 29

DC power supply installation

26     Installation — DC Power Supply

May 2011

Содержание Ethernet Routing Switch 8300 Series

Страница 1: ...Installation DC Power Supply Avaya Ethernet Routing Switch 8300 4 2 NN46200 310 02 03 May 2011...

Страница 2: ...TO DO SO YOU ON BEHALF OF YOURSELF AND THE ENTITY FOR WHOM YOU ARE INSTALLING DOWNLOADING OR USING THE SOFTWARE HEREINAFTER REFERRED TO INTERCHANGEABLYAS YOU AND END USER AGREE TO THESE TERMS AND COND...

Страница 3: ...c of Korea only 8 National Safety Statements of Compliance 8 CE Marking Statement Europe only 8 NOM Statement 8310 and 8306 Chassis Mexico only 9 Informaci n NOM nicamente para M xico 9 Denan Statemen...

Страница 4: ...ibutor or reseller 37 Getting technical support from the Avaya Web site 38 Chapter 7 Translations of safety messages 39 Notices 39 Chapter 8 Technical specifications 45 Technical specifications naviga...

Страница 5: ...national standards as detailed below National Electromagnetic Compliance EMC Statements of Compliance FCC Statement USA only This equipment has been tested and found to comply with the limits for a Cl...

Страница 6: ...glement sur le brouillage radio lectrique du minist re des Communications du Canada CE Marking Statement Europe only EN 55 022 Statements This is to certify that the Avaya 8300 Series chassis and com...

Страница 7: ...nd European Free Trade Association EFTA Notice All products labeled with the CE marking comply with R TTE Directive 1999 5 EEC which includes the Electromagnetic Compliance EMC Directive 2004 108 EC a...

Страница 8: ...mmunications MIC This device may not be sold for use in a non business application National Safety Statements of Compliance CE Marking Statement Europe only EN 60 950 Statement This is to certify that...

Страница 9: ...VAC 12 A 47 to 60 Hz per power supply 8302AC 200 to 240 VAC 10 A 47 to 60 Hz per power supply single supply single supply one redundant supply two supplies or two supplies one redundant supply config...

Страница 10: ...una fuente redundante 8005DC 48 to 60 VDC 42 to 34 A una fuente una fuente configuraciones de una fuente redundante dos fuentes o dos configuraciones de una fuente redundante Denan Statement Japan Nip...

Страница 11: ...SD ESD Hinweise bieten Information dazu wie man die Entladung von statischer Elektrizit t und Folgesch den an Avaya Produkten verhindert Electrostatic alert PRECAUCI N ESD Descarga electrost tica El a...

Страница 12: ...ion PRECAUCI N Los avisos de Precauci n brindan informaci n acerca de c mo evitar posibles interrupciones del servicio o el da o a los productos Avaya Caution CUIDADO Os avisos de cuidado oferecem inf...

Страница 13: ...rimentos ao trabalhar com os produtos da Avaya Warning AVVISO Le indicazioni di avviso forniscono informazioni per evitare danni alle persone durante l utilizzo dei prodotti Avaya Danger High Voltage...

Страница 14: ...mazioni per evitare situazioni o condizioni che potrebbero causare gravi danni alle persone o il decesso a causa dell alta tensione o di scosse elettriche Danger Notice Danger Danger notices provide i...

Страница 15: ...o ou condi o que possa causar graves ferimentos ou morte Danger PERICOLO Le indicazioni di pericolo forniscono informazioni per evitare situazioni o condizioni che potrebbero causare gravi danni alle...

Страница 16: ...Regulatory Information and Safety Precautions 16 Installation DC Power Supply May 2011...

Страница 17: ...ge 17 DC power supply Added Attention to the section Ethernet Routing Switch 8300 series chassis in the DC power supply fundamentals chapter Customer Service Customer service chapter is added to this...

Страница 18: ...see NOM Statement 8310 and 8306 Chassis Mexico only on page 9 and Informaci n NOM nicamente para M xico on page 9 New in this Release 18 Installation DC Power Supply May 2011...

Страница 19: ...s are required to take appropriate measures necessary to correct the interference at their own expense For the minimum Ethernet Routing Switch 8300 software version required to support the hardware se...

Страница 20: ...nutes for each power supply Replacing the DC power supply cover 1 minute for each power supply Navigation DC power supply fundamentals on page 21 DC power supply installation on page 25 Technical spec...

Страница 21: ...the power supply Light Emitting Diode LED on the DC power supply Table 2 Power supply LED State Description Off No output is present On green Power supply output is normal DC power supply accessories...

Страница 22: ...hassis DC power supplies The 8306 and 8310 chassis each have three power supply bays in which you can install either the 8005DC or the 8005DI DC power supply If the total power provided by the power s...

Страница 23: ...rays must not exceed the 8005DI DC power supply rating To determine the minimum number of power supplies to install for the Ethernet Routing Switch 8300 system see Determining the minimum number of DC...

Страница 24: ...ant power configuration and one power supply fails the chassis continues to operate with no interruption of service The chassis continues to supply the same module output power with the remaining powe...

Страница 25: ...circuits Prerequisites Verify that you have the following tools and materials cable crimping tool for crimping the lugs onto the cable heat gun to shrink the tubing around the cable optional 7 16 inc...

Страница 26: ...the minimum number of DC power supplies on page 27 Preparing cables for installation on page 27 Removing the power filler panel on page 28 Installing the DC power supply on page 29 DC power supply in...

Страница 27: ...ndant power supply needs If one power supply satisfies your system power consumption needs a second power supply provides redundancy If two power supplies satisfy your system power consumption needs a...

Страница 28: ...the Ethernet Routing Switch 8300 chassis You must remove the power filler panel from the power bay when you install a power supply in a bay for the first time Caution To maintain proper cooling never...

Страница 29: ...power source of the Ethernet Routing Switch 8300 Caution Risk of equipment damage To prevent damage from electrostatic discharge always wear an antistatic wrist strap connected to an ESD jack Danger...

Страница 30: ...eplacing a failed power supply remove the failed DC power supply 4 Grasp the handle of the new power supply 5 Push the new power supply partway into the bay leaving the terminal block at the side of t...

Страница 31: ...e terminal Danger Risk of injury by electric shock Before you continue with this procedure ensure that the DC power source is switched off 9 Attach the earth ground lead to the ground stud on the powe...

Страница 32: ...ips screwdriver to replace the plastic safety cover on the power supply 15 Firmly slide the power supply all the way into the bay See Job aid Tightening the retaining screws on the DC power supply on...

Страница 33: ...urn on the power supplies simultaneously If you wait longer to turn on the supplies the power supplies shut off within 7 seconds To correct this condition turn off the power supplies for 2 minutes and...

Страница 34: ...Job aid DC power supply input and ground stud location Job aid Attaching the earth ground lead to the ground stud DC power supply installation 34 Installation DC Power Supply May 2011...

Страница 35: ...ghtening the retaining screws on the DC power supply Figure 2 Tightening the retaining screws on the DC power supply 8306 and 8310 chassis Installing the DC power supply Installation DC Power Supply M...

Страница 36: ...DC power supply installation 36 Installation DC Power Supply May 2011...

Страница 37: ...To download and print selected technical publications and release notes directly from the Internet go to www avaya com support Getting product training Ongoing product training is available For more i...

Страница 38: ...om the Avaya Web site The easiest and most effective way to get technical support for Avaya products is from the Avaya Technical Support Web site at www avaya com support Customer Service 38 Installat...

Страница 39: ...Dies ist ein Ger t der Klasse A Bei Einsatz des Ger ts in Wohngebieten kann es St rungen des Radio und Fernsehempfangs verursachen In diesem Fall muss der Benutzer alle notwendigen Ma nahmen ergreife...

Страница 40: ...nu est adapt une utilisation avec la source d alimentation laquelle il est raccord Plusieurs crit res tels que le calibre l inflammabilit et l aptitude l usage m canique doivent tre pris en compte lor...

Страница 41: ...quipment damage To prevent damage from electrostatic discharge always wear an antistatic wrist strap connected to an ESD jack Caution ATTENTION Risque d endommagement de l quipement Pour pr venir tout...

Страница 42: ...c bles Voltage Pour votre s curit v rifiez que les cosses sont correctement serties sur les c bles Verletzungsrisiko durch Stromschlag Es besteht ein Sicherheitsrisiko wenn die Anschlussst cke nicht o...

Страница 43: ...frigeraci n adecuada no opere Ethernet Routing Switch 8300 con el compartimiento de la fuente de alimentaci n vac o Si necesita reemplazar una fuente de alimentaci n defectuosa y no cuenta con un pane...

Страница 44: ...erve el panel de relleno de energ a para utilizarlo en caso de ser necesario operar Ethernet Routing Switch 8300 sin una fuente de alimentaci n Caution CUIDADO Guarde o painel de preenchimento de ener...

Страница 45: ...ings for the 8005DI DC input power supply and output power supply DC input power specifications The following table describes the technical specifications for DC input power for Model 8005DI DC power...

Страница 46: ...r Bellcore TR 332 standard Model 8005DC power supply This section provides power ratings for the 8005DC input power supply and output power supply DC input power specifications The following table des...

Страница 47: ...5DC power supply Table 7 DC output power specifications for Model 8005DC power supply Parameter Specifications Output power maximum 1462 W 1372 W 90 W fans Modules 3 3 V 150 A 12 V 72 A Fans 12 VDC 7...

Страница 48: ...Technical specifications 48 Installation DC Power Supply May 2011...

Страница 49: ...ing 29 status LEDs 21 distributor 37 documentation 37 E estimated installation time 19 H hardware shipped with the DC power supply 21 I installation DC power supply 29 L LEDs power supply 21 R reselle...

Страница 50: ......

Отзывы: