15
Setting the set point (desired temperature)
1.
press
SET
for 1 second, the set value will start flashing after a few moments;
2.
increase or decrease the value using
UP
or
DOWN
;
3.
press
SET
to confirm the new value.
Switching the device ON/OFF
Press
UP
for more than 3 seconds. The control and defrost algorithms are now disabled
and the Instrument displays the message “OFF” alternating with the temperature read by
the set probe.
Manual defrost
Press for
DOWN
more than 3 seconds (the defrost starts only if the temperature conditions
are valid).
Continuous cycle
Press
UP
and
DOWN
together for more than 3 seconds.
Access and setting type F (frequent) and type C (configuration) parameters
1. Press
SET
for 3 seconds (the display will show ”PS”);
2.To access the type F and C parameter menu, press
SET
, enter the password “22”
using
UP/DOWN
, press
SET
to confirm;
To access the F parameter menu only, press
SET
(without entering the password);
3. Scroll inside the parameter menu using
UP/DOWN
;
4. To display/set the values of the parameter displayed, press
SET
, then
UP/DOWN
and
finally
SET
to confirm the changes (returning to the parameter menu).
To save all the new values and exit the parameter menu, press
SET
for 3 seconds;
To exit the menu without saving the changed values (exit by timeout) do not press any
button for at least 60 seconds.