              UNINTERUPTIBLE POWER SUPPLY 

 

Pag. 7 

TEHNICAL PARAMETERS 

Maximum capacity 

500VA    800VA    1000VA    1500VA 

Maximum rated power 

300W    500W    700W    1050W 

Main input power supply  

150 – 270 VCA 

Input freqvency  

45 – 65 Hz 

Output power 

207 – 241  VCA 

Input freqvency 

50 – 60 Hz 

Output waveform 

Pure Sine Wave 

Switching time 

< 4ms 

Battery capacity  

12V DC / 24V DC (for 1050W) 

Overload protection 

110% ~ 130% (30 seconds) 

 

 

POSIBILE PROBLEMS 

PROBLEM 

POSIBILE CAUSE 

WHAT TO DO 

UPS doesn’t 
start, LCD 

not working 

ON button not pushed enough  
Battery not connected 

Burned fuse 
UPS damaged 

Push ON button over 4 seconds 
Connect the battery 

Replace fuse 
Repair or replace 

UPS works 
only on 

battery  

Main power cable brocken 
Burned fuse 

Main power is under 160V or 
over 260V 

UPS damaged 

Replace cable 
Replace fuse 

Contact power supply company 
 

Repair or replace 

Fast beep 

signal 

Overload 

Battery exhausted 

Unplug unneccesary consumers  

Replace or charge battery 

UPS works 
only short 

time on 
battery  

Battery exhausted because of 
intenssive work or not fully 

charged all the time  
Old or damaged battery 

Let the UPS charge the battery 
for 24 hours 

 
Replace battery 

 

Содержание PREMIUM 300W/500VA-12VDC

Страница 1: ...LE POWER SUPPLY Pag 1 AVANSA PREMIUM UNINTERRUPTIBLE POWER SUPPLY FOR ELECTRIC AND ELECTRONIC DEVICES Pure Sine Wave 300W 500VA 12VDC 500W 800VA 12VDC 700W 1000VA 12VDC 1050W 1500VA 24VDC User Manual Warranty Certificate ...

Страница 2: ...feature of this device is the output power waveform when operating on battery which is pure sine wave identical to the main electricity power network of your house When the main power of your house is ON the UPS will charge your battery ensuring a long lasting battery life The UPS is only working with an external 12V battery or 24V for the 1050W model UPS It should be used only lead acid battery t...

Страница 3: ...y connect the main power supply and then connect the consumer to the UPS To start press and hold the power button ON OFF for 4 seconds The operation of the system begins with the automatic detection of the state of the battery and mains voltage If the voltage of the battery is under 10 8V the UPS will consider that the battery is damaged and it will not start If the battery is good and the voltage...

Страница 4: ...he UPS is heating up the cooling fan is automatically controlled according to UPS needs you don t need to worry if you hear the fan working even if the battery is fully charged or there is no power consumption the fan is automatically switched on and off depending on the UPS needs Ground The UPS stops if there is leakage current Battery alarm and protection if the battery is discharged to a value ...

Страница 5: ...values 50Ah 150Ah Do not use less than 50Ah batteries because the high initial charging current of the UPS up to 10A will reduce the battery life The UPS of 1050W 1500VA will need the use a 24V battery or two 12V batteries connected in serial connection If you use two 12V batteries they should be similar batteries having the same age and the same capacity Below you can find some teoretical values ...

Страница 6: ...AVANSA UNINTERUPTIBLE POWER SUPPLY Pag 6 ...

Страница 7: ... LCD not working ON button not pushed enough Battery not connected Burned fuse UPS damaged Push ON button over 4 seconds Connect the battery Replace fuse Repair or replace UPS works only on battery Main power cable brocken Burned fuse Main power is under 160V or over 260V UPS damaged Replace cable Replace fuse Contact power supply company Repair or replace Fast beep signal Overload Battery exhaust...

Отзывы: