17
5.2 Installation requirements
The alarm central unit room, in which VASCU is located, must satisfy the following conditions:
» Fire protection device operation room (FPDOR) should be located on the floor of the structure, close to entrance/exit
designed and marked as the entrance for rescue teams.
» The room must be located and marked in a way that allows rescuers to notice it at the entrance. It is advisable to make sure
FPDOR access doors are not located farther than 10m from rescue team exit.
» The width of passage leading to the room should be at least 1,5 m.
» The room should be properly marked.
» If FPDOR is located at a distance greater than 10 m from the rescue team exit, additional signs must be used in order to point
location and direction to FPDOR.
» The Fire Safety Instructions in graphics and site evacuation procedures should include signs and location of FPDOR.
» Install the Manual Call Point in FPDOR or in its immediate vicinity. FPDOR should be monitored by automatic sensors being
part of fire alarm system on the site.
» Access to FPDOR should be given solely to authorized persons and rescue team. It is acceptable to lock the door as long as
one key is located in a suitably marked box with breakable glass attached to the wall in immediate vicinity to room doors.
» FPDOR should be a closed room whose walls and ceilings have REI 60 fire resistance rating. The door of FPDOR should have
EI30 fire resistance rating.
» The control desk with a fireman microphone should be connected to VASCU via wires assuring circuit continuity in case of fire.
» Natural and artificial lighting should be provided. Lighting intensity in the room must be min. 500 lx.
» The room must be equipped with emergency lighting of an average lighting intensity – min. 10 lx.
» Weather conditions must satisfy the following requirements: temperature from 0°C to +40°C, relative humidity from
25% to 80%, air pressure from 860 hPa to 1060 hPa.
» A suitable amount of space around front VASCU board must be provided in order to allow required manipulations.
» The height of control and indication devices assembly should allow their suitable operation.
» Background noisevalues in the room, in which the console with the fireman microphone is located, should not exceed 40 dB.
» A table with dimensions big enough to unfold site and system documentations must be located in the room.
5.3 Environmental conditions
Do not place the product in the environment which may affect its performance or shorten its life. Environments which have
a negative influence frequently have high temperatures, are dusty, humid and have high level of vibrations. The equipment must
be placed in cold and dry area far away from direct sunlight and inflammable and explosive materials.
The AutroVoice miniVES system is designed to either be mounted in a 19” RACK cabinet or to be mounted on a wall as a standalone
device. Even without the additional casing it is rated at IP30 and thus compliant with the EN54-16 norm.
Содержание AutroVoice miniVES 2001
Страница 2: ...2 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 6: ...6 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 146: ...146 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL 14 Annexes List of certified switches to connect devices in CHAIN topology...
Страница 147: ...147 15 Certificates...
Страница 152: ...152 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL Notes...
Страница 153: ...153...
Страница 154: ...154 COMPACT VOICE ALARM SYSTEM SERVICE MANUAL...
Страница 155: ...155...