background image

In the Event of Faults

 

 

A fault is indicated by one of the 

components

 

(fire detectors, external equipment or other 
faults).

 

 

 

FAULT WARNINGS

        

19:23

Total:  2

Total:  1

Total:  1

    DZ FAULTS
       1 OFFICES
    OTHER FAULTS
       1 LOOP (2)

 

(Display Picture - Example) 

 
 

 

Actions to be taken - Operation Mode 

Notify service/technical personnel.

 

To silence the internal buzzer, press the 
black Mute Panel button

 

 

Press 

 

 

 

Observe the Fault Warnings.

 

If you need to find out more detailed information before 
investigating the scene(s), follow the 

General 

Procedure, Step 4,

 a) to e) on the last page of this 

folder, 

How to View Detailed Information. 

 

If 

not

, go directly to step 5.

 

Investigate the scene(s) and carry out the 
necessary actions, i.e. repair the fault(s).

 

 

After the scene(s) are investigated and the necessary 
actions are taken, you can accept the fault warning(s).

 

If there are several fault warnings, select 
the one you want to accept by scrolling 
with the arrow buttons, then press

   

 

 

In this 

example

 a detection zone includes several points 

in fault warning state. Note that other types of faults are 
operated differently than what is described in this 

example

. A FAD in fault warning state, for example, can 

be accepted at this stage by pressing Action Digit 3 
(ACCEPT FAULT WARNING).

 

To view all points in fault warning state 
within the selected zone, press Action 
Digit 1 (SHOW POINTS). 

Select the point, then press

  

 

 

To accept the selected point, press digit 3 
(ACCEPT FAULT WARNING).

 

 

If there are several fault warnings, each one can be 
accepted in turn. When the first fault has been accepted 
and the message «Successfully Completed» is shown, 
the Close button can be pressed to return quickly to the 
previous menu where the next fault warning can be 
accepted. 

Fault warnings that are accepted, will no longer blink in 
the display. This allows you to see on the screen 
whether a fault warning is accepted or not.

 

How to Toggle Between Menu 
Mode and Operation Mode

 

 

You can easily toggle between Menu Mode and 
Operation Mode by pressing the Menu Button.

 

 
 

 

If an alarm condition occurs when you are using 

Menu Mode

you have to press the Menu Button to enter 

Operation Mode

 

in order to operate the control panel.  

 

If no buttons are pressed when the system is in Menu Mode, 
the system will return automatically to Operation Mode after a 
short period. 

 

 
 

How to View Detailed Info

 

 

The SHOW STATUS gives detailed information on 
the current status of all conditions

, i.e. Alarms, 

Faults

Disablements

 and 

Detection Zones in Test.

 

 

The Show Status menu is the first menu selection in 

Menu Mode. 

 

SHOW STATUS

    

  

      1 FIRE ALARMS 
      2 PRELARMS
      3 FAULTS
      4 DISABLEMENTS
      5 DETECTION ZONES IN TEST

        

19:23

 

 

Detailed 

zonal information

 and a list of the 

points in alarm

 for the 

selected zone can also be accessed directly from 

Operation Mode

Follow the general procedure below. 

 

 

General Procedure - Operation Mode 

 

An event has occured, for 

example

, a Fire Alarm 

Condition, and you want to view detailed zonal 
information for the selected detection zone(s). 

 

Press

 

 

 

 

Observe the zone(s). 
Here you can find out detailed zonal / point information 
before investigating the scene(s).

 

a)  To select a zone (if several zones), scroll with the 

arrow buttons 

6

PQR

 (up) or 

9

YZ

 (down) 

b)  To view detailed zonal information for the selected 

zone, press 

 , then  to go one step backwards, 

press 

  

c)  To view points in alarm for the selected zone, press 

digit 1 (SHOW POINTS). 

d)  To go one step backwards, press 

 

e) 

To select another zone, follow b) to d), if 

not

 go to  

step 5.

 

 
 

Step

 

Step

 

!

"

 

Отзывы: