Facade protection kit

Complete bracket w/mounting arm, coupled with AutroFlame IR flame detector BG-201.

116-BG-201F

Assembly instructions

Attach the bracket to the mounting arm with the supplied screws, washers and nuts. Attach 
the detector base to the bracket before attaching the detector head to the detector base.

116-P-MOUNTFACADEKIT/WGB, Rev. B, 2021-01-11

NOTE! 

The ONLY way to properly mount 
the detector head to the detector 
base is to make sure that points A 
and B fit together.

 

Detector head

 

Detector Base

NOTE! 

There is a mark in 

the plastic that indicates 
the detector's 30° field of 
view. This must point in 
the direction from the wall 
towards the inside of the 
bracket.

Содержание AutroFlame BG-201

Страница 1: ...P MOUNTFACADEKIT WGB Rev B 2021 01 11 The flame detector is mounted on a discreet bracket protecting the detector from weather and nusiance alarm sources The bracket also limits the detector s field of view The mounting arm is adjustable In this way the detector s field of view can be adapted to individual needs both horizontally and vertically In this way the flame detector can point to the facad...

Страница 2: ... Class and coverage data Table 1 specifies maximum heights for detector mounting We recommend that the detector is mounted at a height of between 4 and 6 meters for practical and coverage reasons Following Autronica s recommendations table 1 gives a minimum of 2 meters coverage from the bottom of the wall and upwards If the distance between the detector and a potential fire is doubled the signal m...

Страница 3: ...ll A 45 angle ensures that the outer line of view runs along the wall This ensures a protected area from behind the vertical axis and all along the detector s field of view See illustration below perspective view Facade protection kit Complete bracket w mounting arm coupled with AutroFlame IR flame detector BG 201 116 BG 201F Recommended mounting Horizontal ...

Страница 4: ...tor BG 201 116 BG 201F 116 P MOUNTFACADEKIT WGB Rev B 2021 01 11 A facade protection kit covers up to 20 meters of a wall The ground coverage depends on the mounting of the detectors as shown in Table 1 See examples below top view of buildings Example 1 Example 2 Example 3 Example 4 Example 5 ...

Страница 5: ...each side of the center line will then be equal to the mounting height The formula is as follows Ground coverage area m mounting height x 2 4 For example a 6 meter mounting height will give 12 meters of ground coverage along the facade To meet our safety criteria 2 meters on each side must be subtracted providing a total coverage of 8 meters in this example Alternative mounting Vertical 116 P MOUN...

Страница 6: ...or base to the bracket before attaching the detector head to the detector base 116 P MOUNTFACADEKIT WGB Rev B 2021 01 11 NOTE The ONLY way to properly mount the detector head to the detector base is to make sure that points A and B fit together Detector head Detector Base NOTE There is a mark in the plastic that indicates the detector s 30 field of view This must point in the direction from the wa...

Страница 7: ... 201F Right hand mounting 116 P MOUNTFACADEKIT WGB Rev B 2021 01 11 No Amount Name 1 1 Mounting arm 2 1 Screws M8 x 1 x 50 3 1 Lock Washer 4 1 Washer ST8 5 2 Nut M6 6 2 Washer ST6 7 1 Nut M8 8 1 Bracket 9 2 Screw M6 lowered 10 1 Detector base 11 2 Screw M4 x 16 x 4 8 12 1 Detector head 13 3 Screw M4 x 10 x 4 8 ...

Страница 8: ...T6 7 1 Nut M8 8 1 Bracket 9 2 Screw M6 lowered 10 1 Detector base 11 2 Screw M4 x 16 x 4 8 12 1 Detector head 13 3 Screw M4 x 10 x 4 8 Facade protection kit Complete bracket w mounting arm coupled with AutroFlame IR flame detector BG 201 116 BG 201F 116 P MOUNTFACADEKIT WGB Rev B 2021 01 11 Left hand mounting ...

Отзывы: