2
Specifications
© Copyright Reserved Autonics Co., Ltd.
25
2
Specifications
2.1
Ratings
Category
TM2 Series
TM4 Series
Number of Channels
2 channels
4 channels
Each channel insulated – Dielectric strength 1,000VAC
Power Supply
24VDC
Allowable voltage range
90% ~ 110% of rated voltage
Power Consumption
5W max. (At maximum load)
Indicating type
Non indicating type - Parameter setting and monitoring with externally
device (PC or PLC).
Input
type
RTD
DPt100
Ω, JPt100 Ω 3 wire (allowable
line resistance: Max.
5Ω)
Thermocouples
K, J, E, T, L, N, U, R, S, B, C, G, and PLII (13types)
Indicating
accuracy
RTD
(Bigger one either PV
±
0.5% or
±
1
℃
)
±
1 Digit Max.
Thermocouple
※
1
C·T Input
(
±
5% F.S.)
±
1 Digit Max
-
Current output
(
±
1.5% F.S.)
±
1 Digit Max
-
Influence
of
Temperatu
re
※
2
RTD
(Bigger one either PV
±
0.5% or
±
2
℃
)
±
1 Digit Max.(In case of
thermocouple input, it is
±
5
℃
at -100
℃
below)
Themocouples L ,U, C, G, R, S, B: (Bigger one either PV
±
0.5% or
±
5
℃
)
±
1
Digit Max.
Thermocouples
Control
Output
Relay
250VAC 3 A 1a
SSR
12VDC ±3V 30mA Max.
22VDC ±3V 30mA Max.
Current
DC4-20mA or DC0-20mA
(Load 500
Ω
Max.)
-
Sub
Output
Relay
250VAC 3A 1a
Communications output
RS485 communications output (Modbus RTU method)
Event
Input
Leakage current
Approx. Max. 4mA
-
Contact
ON: Max. 1K
Ω, OFF: Min. 100KΩ.
-
Non-contact
ON: Max. 1.5V residual voltage
OFF: Max. 0.1mA leakage current
-
C·T
0.0-50.0A (Primary current
measurement range)
※
C·T ratio (1000:1)
-
Control
type
Heating, Cooling
ON/OFF control, P, PI, PD, PID control
Heating &
Cooling
Hysteresis
RTD/ Thermocouples: 1~100
℃
/
℉
(0.1~100.0
℃
/
℉
) variable
Proportional Band (P)
0.1 ~ 999.9
℃
Содержание TM Series
Страница 1: ...User Manual ...
Страница 2: ......
Страница 10: ...Handling Precautions x Copyright Reserved Autonics Co Ltd ...
Страница 14: ...Table of Contents xiv Copyright Reserved Autonics Co Ltd ...
Страница 23: ...1 Product Introduction Copyright Reserved Autonics Co Ltd 23 1 4 2 Other Parts ...
Страница 24: ...1 Product Introduction 24 Copyright Reserved Autonics Co Ltd ...
Страница 34: ...4 Connections and block diagram 34 Copyright Reserved Autonics Co Ltd 3 Example of connection 4 1 TM4 Series ...
Страница 40: ...4 Connections and block diagram 40 Copyright Reserved Autonics Co Ltd ...
Страница 44: ...5 Preparation and Startup 44 Copyright Reserved Autonics Co Ltd 5 3 2 Multiple Modules ...
Страница 52: ...6 Parameter Settings and Functions 52 Copyright Reserved Autonics Co Ltd 6 2 1 3 1 1 Using a Deadband ...
Страница 53: ...6 Parameter Settings and Functions Copyright Reserved Autonics Co Ltd 53 6 2 1 3 1 2 Using an Overlap Band ...
Страница 57: ...6 Parameter Settings and Functions Copyright Reserved Autonics Co Ltd 57 Example Ramp Graph ...
Страница 90: ...6 Parameter Settings and Functions 90 Copyright Reserved Autonics Co Ltd ...
Страница 96: ......
Страница 97: ......