1 Modbus RTU Protocol
© Copyright Reserved Autonics Co., Ltd.
11
1
Modbus RTU Protocol
1.1
Read coil status (Func 01–01H)
Read output (0X reference, Coil) ON/OFF status in the slave device.
(1)
Query (Master)
Slave address Function Starting address
No. of points
Error check (CRC16)
High
Low
High
Low
Low
High
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
(2)
Response (Slave)
Slave address Function Byte count Data
Data
Data
Error check (CRC16)
Low
High
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
If read the 10 output status (ON: 1, OFF: 0) within coil 000001 (0000 H) to 000010 (0009 H) on
Slave (Address 17) from Master.
Query (Master)
Slave address Function Starting address
No. of points
Error check (CRC16)
High
Low
High
Low
Low
High
11 H
01 H
00 H
00 H
00 H
0A H
## H
## H
If the values range from coil 000008 (0007 H) to 000001 (0000 H) on the Slave are “ON-ON-
OFF-OFF-ON-ON-OFF-ON”, and the values from 000010 (0009 H) to 000009 (0008 H) are
respectively “OFF-ON”.
Response (Slave)
Slave address Function Byte count
Data
(000008 to
000001)
Data
(000010 to
000009)
Error check (CRC16)
Low
High
11 H
01 H
02 H
CD H
01 H
## H
## H
CRC16
CRC16
Содержание SPR1 Series
Страница 1: ... Copyright Reserved Autonics Co Ltd i ...
Страница 2: ...ii Copyright Reserved Autonics Co Ltd ...
Страница 8: ...Safety Considerations viii Copyright Reserved Autonics Co Ltd ...
Страница 10: ...Table of Contents x Copyright Reserved Autonics Co Ltd ...
Страница 22: ...2 Modbus Mapping Table 22 Copyright Reserved Autonics Co Ltd MCY SPRC1 V1 2 1807US ...