2 Modbus Mapping Table
© Copyright Reserved Autonics Co., Ltd.
23
No(Address)
Func R/W Parameter
Description
Setting Range
Unit Factory
Default Note
301011 (03F2)
04
R
FRQ
Power supply frequency
0.0
to
99.9
Hz
-
301012 (03F3)
※
1
04
R
RUN LAMP
Operation indicator
0: OFF 1 : ON
-
-
Bit 0
MAN LAMP
Manual control indicator
0: OFF 1 : ON
-
-
Bit 1
ALM LAMP
Alarm output indicator
0: OFF 1 : ON
-
-
Bit 2
OUT LAMP
Control output indicator
0: OFF 1 : ON
-
-
Bit 3
V LAMP
Unit indicator
0: OFF 1 : ON
-
-
Bit 4
A LAMP
Unit indicator
0: OFF 1 : ON
-
-
Bit 5
RUN D/I
RUN contact input status
0: OFF 1 : ON
-
-
Bit 6
AUTO D/I
AUTO contact input status
0: OFF 1 : ON
-
-
Bit 7
RESET D/I
RESET contact input status
0: OFF 1 : ON
-
-
Bit 8
301013 (03F4)
※
2
04
R
Fuse Alarm
Fuse break alarm
0: OFF 1 : ON
-
-
Bit 0
Over Curr
Alarm
Overcurrent alarm
0: OFF 1 : ON
-
-
Bit 1
Over Volt
Alarm
Overvoltage alarm
0: OFF 1 : ON
-
-
Bit 2
Heat Sink
Alarm
Heatsink overheat alarm
0: OFF 1 : ON
-
-
Bit 3
SCR Alarm
SCR error alarm
0: OFF 1 : ON
-
-
Bit 4
Heater Break
Alarm
Heater break alarm
0: OFF 1 : ON
-
-
Bit 5
※
1.
301012 (03F3) address data organization
Bit F Bit E Bit D Bit C Bit B Bit A Bit 9 Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
-
-
-
-
-
-
-
RESET
intput
AUTO
intput
RUN
intput
A
indicator
V
indicator
OUT
indicator
ALM
indicator
MAN
indicator
RUN
indicator
0
0
0
0
0
0
0
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
1Byte
1Byte
※
2.
301013 (03F4) address data organization
Bit F Bit E Bit D Bit C Bit B Bit A Bit 9 Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
-
-
-
-
-
-
-
-
-
-
Heater
break
SCR
error
Heatsink
overheat
Over-
voltage
Over-
current
Fuse
break
0
0
0
0
0
0
0
0
0
0
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
0 / 1
1Byte
1Byte