Autonics MT4N Series Скачать руководство пользователя страница 4

-|Transparent Guide|-

  

■ Parameter 2 group

Parameter

Mark

Defaults

Setting range

Display 

condition

2-1

OUT1 

operation 

mode

OU!T

OFF

[OUT1 output model]

OFF, HI, LO, HL, HL-G

• 

Refer to Output Operation Mode

-

2-2

OUT2 

operation 

mode

OU@T

OFF

[OUT2 output model]

OFF, HI, LO, HL, HL-G

• 

Refer to Output Operation Mode

-

2-3

OUT1 

hysteresis

HYs1

0)01

[Except indicator model]

Within 10 % of max. display range, digit

2-1 OUT1

operation 

mode:

except 

OFF

2-4

OUT2

hysteresis

HYs2

0)01

[Except indicator model]

Within 10 % of max. display range, digit

2-2 OUT2 

operation 

mode:

except 

OFF

2-5

Startup 

compensation 

time 

STaT

0)0

[Except indicator model]

0.0 to 99.9 sec

-

2-6

Peak 

monitoring 

delay time

PEkT

00 S

00 to 30 sec

-

2-7

Display cycle

DIsT

)2 S

0.1 to 5.0 sec

-

2-8

Current value 

display part 

color

COLR

RED

RED: red / red, GRN: green / green, 

YEL: yellow / yellow, R-G: red / green, 

G-R: green / red

• Display: normal / error occurs

-

2-9

Keys for zero 

adjustment 

ZERO

NO

NO, YES

•  YES: Press the [◀] + [▲] keys for 3 

sec to adjust zero. 

-

2-10

External 

input 

terminal

EVLN

HOLD

[Except indicator model]

HOLD,

 

ZERO

•  If the external input terminal is 

short-circuited for 50 ms or more, it 

operates with the set function.

-

2-11

High-limit 

value of 

transmission 

output

FS-H

5)00

[DC voltage & Transmission (DC 4 - 20 

mA) output model]

Max. value of display range

-

50)0

[DC current & 

Transmission (DC 4 - 20 

mA) output model]

Max. value of display range

25)0

[AC voltage & Transmission (DC 4 - 20 

mA) output model]

Max. value of display range

%000

[AC current & 

Transmission (DC 4 - 20 

mA) output model]

Max. value of display range

2-12

Low-limit 

value of 

transmission 

output

FS-L

0)00

[DC voltage & Transmission (DC 4 - 20 

mA) output model]

Min. value of display range

-

00)0

[DC current & 

Transmission (DC 4 - 20 

mA) output model]

Min. value of display range

)0

[AC voltage & Transmission (DC 4 - 20 

mA) output model]

Min. value of display range

)000

[AC current & 

Transmission (DC 4 - 20 

mA) output model]

Min. value of display range

2-13

Comm.

 

Address 

ADRS

01

[RS485 communication output model]

01 to 99

-

2-14

Comm. 

speed

BPS

9600

[RS485 communication output model]

38.4k, 19.2k, 9600, 4800, 2400, 1200 bps

-

2-15 Parity bit

PRTY

NONE

[RS485 communication output model]

NONE, EVEN, ODD

-

2-16 Stop bit

STP

2

[RS485 communication output model]

2,

 

1 bit

-

2-17 Response 

waiting time

RSwT

5

[RS485 communication output model]

5 to 99 sec

-

2-18 Lock

LOC

OFF

OFF: unlock, 

LOC1: lock parameter 1, 

LOC2: lock parameter 1, 2, 

LOC3: lock parameter 0, 1 and 2

-

  

■ Parameter 0 group

Parameter

Mark

Defaults

Setting range

Display 

condition

0-1

OUT1 high-

limit output 

setting value

OU!H

5)00

[DC voltage model], [DC current model]

-5 to 110 % of display range

2-1 OUT1 

operation

mode:

except 

OFF

25)0

[AC voltage model]

0 to 110 % of display range

%000

[AC current model]

0 to 110 % of display range

0-2

OUT1 low-

limit output 

setting value

OU!L

0)00

[DC voltage model]

-5 to 110 % of display range

00)0

[DC current model]

-5 to 110 % of display range

[AC voltage model]

0 to 110 % of display range

)000

[AC current model]

0 to 110 % of display range

0-3

OUT2 high-

limit output 

setting value

OU@H

5)00

•  Same as setting range of OUT1 high-

limit output setting value

2-2 OUT2 

operation

mode:

except 

OFF

25)0

%000

0-4

OUT2 low-

limit output 

setting value

OU@L

0)00

•  Same as setting range of OUT1 low-

limit output setting value

00)0

)000

0-5

Display max. 

peak value

 01)

hPEK

)00

[DC voltage model]

Max. peak value in run mode

2-1 OUT1 

operation

mode:

except OFF

or

2-2 OUT2 

operation

mode:

except OFF

&

2-6 Peak 

monitoring 

delay time:

except 00

)0

[DC current model], [AC voltage model]

Max. peak value in run mode

)000

[AC current model]

Max. peak value in run mode

0-6

Display min. 

peak value 

01)

lPEK

)00

[DC voltage model]

Min. peak value in run mode

)0

[DC current model], [AC voltage model]

Min. peak value in run mode

)000

[AC current model]

Min. peak value in run mode

 01)  Reset: Press any one of [◀], [▼], [▲] keys.

Input range

Display range

Input 

impedance

Diaplay method: STND (fixed) Diaplay method

: SCAL 

 01)

0 - 5 A 

0.000 to 5.000

5

Decimals

Display range

0

-1999 to 9999

)0

-199.9 to 999.9

)00

-19.99 to 99.99

)000

-1.999 to 9.999

0.01 Ω

0 - 2.5 A 

0.000 to 2.500

@5

0.01 Ω

0 - 500 mA 

0.0 to 500.0 

500

0.19 Ω

0 - 250 mA 

0.0 to 250.0

250

0.19 Ω

0 - 100 mA 

0.0 to 100.0

100

1.01 Ω

0 - 50 mA 

0.00 to 50.00

50

1.01 Ω

 01)  Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input 

range to measure. 

 

When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.

Input range

Display range

Input 

impedance

Diaplay method: STND (fixed) Diaplay method

: SCAL 

 01)

0 - 250 VACᜠ 

0.0 to 250.0 

250

Decimals

Display range

0

-1999 to 9999

)0

-199.9 to 999.9

)00

-19.99 to 99.99

)000

-1.999 to 9.999

1.086 MΩ

0 - 125 VACᜠ 

0.0 to 125.0

125

1.086 MΩ

0 - 50 VACᜠ 

0.00 to 50.00

50

199.12 kΩ

0 - 25 VACᜠ 

0.00 to 25.00

25

199.12 kΩ

0 - 5 VACᜠ 

0.000 to 5.000

5

19.12 kΩ

0 - 2.5 VACᜠ 

0.000 to 2.500

@5

19.12 kΩ

 01)  Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input 

range to measure. 

 

When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.

Input Range and Display Range

When the max. input value is over the 100 %, it may result in input terminal damage.

  

■ DC voltage model

Input range

Display range

Input 

impedance

Diaplay method: STND (fixed) Diaplay method

: SCAL 

 01)

0 - 50 VDCᜡ

0.00 to 50.00

50

Decimals

Display range

0

-1999 to 9999

)0

-199.9 to 999.9

)00

-19.99 to 99.99

)000

-1.999 to 9.999

433.48 kΩ

0 - 10 VDCᜡ 

0.00 to 10.00

10

433.48 kΩ

0 - 5 VDCᜡ 

0.000 to 5.000

5

43.48 kΩ

0 - 1 VDCᜡ 

0.000 to 1.000

1

43.48 kΩ

0 - 250 mVDCᜡ  0.0 to 250.0

250

2.28 kΩ

0 - 50 mVDCᜡ 

0.00 to 50.00

50

2.28 kΩ

 01)  Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input 

range to measure. 

 

When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.

  

DC current model

  

■ AC voltage model

  

AC current model

Input range

Display range

Input 

impedance

Diaplay method: STND (fixed) Diaplay method

: SCAL 

 01)

0 - 500 mA

0.0 to 500.0

500

Decimals

Display range

0

-1999 to 9999

)0

-199.9 to 999.9

)00

-19.99 to 99.99

)000

-1.999 to 9.999

0.22 Ω

0 - 200 mA 

0.0 to 200.0

200

0.22 Ω

0 - 50 mA 

0.00 to 50.00

50

2.22 Ω

4 - 20 mA

4.00 to 20.00

4-20

2.22 Ω

0 - 5 mA

0.000 to 5.000

5

22.22 Ω

0 - 2 mA 

0.000 to 2.000

2

22.22 Ω

 01)  Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input 

range to measure. 

 

When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.