Autonics KT-502H Скачать руководство пользователя страница 2

Temperature Transmitter

G-3

A. Recorder

B. Indicator

C. Converter

D. Controller

E. Thyristor 

     unit

F. Pressure 

    transmitter

G. Temp. 

     transmitter

H. Accessories

KT-502H

(unit: mm)

● Mounting bracket

Ø83

142

2-(1/2 14NPT)

Input type

Input range(

) Input range(

)

RTD

DPt100Ω

200   to   850

328   to   1562

DPt500Ω

200   to   250

328   to   482

DPt1000Ω

200   to   250

328   to   482

Cu50Ω

50   to   150

58   to   302

Cu100Ω

50   to   150

58   to   302

Ni100Ω

60   to   180

76   to   356

Ni500Ω

60   to   180

76   to   356

Ni1000Ω

60   to   150

76   to   302

Resistance

transmitter

Resistance (Ω)

0  to 

400Ω

-

0  to 

2000Ω

Thermocouple

(PtRh30-PtRh6)

0   to   1820

32   to   3308

E(NiCr-CuNi)

270   to   1000

454   to   1832

J(Fe-CuNi)

210   to   1200

346   to   2192

K(NiCr-Ni)

270   to   1372

454   to   2501.6

N(NiCrSi-NiSi)

270   to   1300

454   to   2372

R(PtRh13-Pt)

50   to   1768

58   to   3214.4

S(PtRh10-Pt)

50   to   1768

58   to   3214.4

T(Cu-CuNi)

270   to   400

454   to   752

Analog

Voltage

10 - 75mV

-

100 - 100mV
100 - 500mV
100 - 2000mV

● Opening cover

Dimensions

Connections

Input Type And Range

To open the cover, 

unscrew the M3×6L 

headless bolt using a 1.5 

hexagon wrench and rotate 

the cover. 

Mounting bracket

83

55

96

96

200

94

DN50

(2B Pipe)

HART Communicator

Power

Supply

Indicator

Recorder

DCS

Controller

1

2

3

4

5

6

Power supply

10.5-45VDC

+

-

A

B

b

RTD

mV

+

+

-

-

TC

Min. 250

Содержание KT-502H

Страница 1: ...100 100mV 100 500mV 100 2000mV Output DC4 20mA 2 wire Accuracy 0 3 Alarm Below 3 8mA Over 20 5mA Sensor break 3 6mA Load Max V power supply 7 5V 0 22A Galvanic insulation 2kVAC input output Environ ment Ambient temperature 20 to 70 storage 20 to 80 Ambient humidity 0 to 85 RH storage 0 to 85 RH Explosion class Ex d IIC T6 Protection structure IP67 IEC standard Material Body Aluminum AlDc 8S Cover ...

Страница 2: ... Ω 0 to400Ω 0 to2000Ω Thermocouple B PtRh30 PtRh6 0 to 1820 32 to 3308 E NiCr CuNi 270 to 1000 454 to 1832 J Fe CuNi 210 to 1200 346 to 2192 K NiCr Ni 270 to 1372 454 to 2501 6 N NiCrSi NiSi 270 to 1300 454 to 2372 R PtRh13 Pt 50 to 1768 58 to 3214 4 S PtRh10 Pt 50 to 1768 58 to 3214 4 T Cu CuNi 270 to 400 454 to 752 Analog Voltage 10 75mV 100 100mV 100 500mV 100 2000mV Opening cover Dimensions Co...

Страница 3: ...o 4 PV LRV 5 URV 1 Process Variables 2 Diag Service 3 Basic Setup 4 Detailed Setup 5 Review 1 Test device 2 Loop test 3 Calibration 4 D A trim Connect reference meter ABORT O K Fid dev output 4 000 mA equal to reference meter 1 Yes 2 No ABORT ENTER Enter meter Value 4 000 HELP DEL ABORT ENTER Setting fid dev output to 4mA ABORT O K WARN Loop should be removed from automatic control ABORT O K Selec...

Страница 4: ...supply or cut off the power Switch or circuit breaker should be installed nearby users for convenient control Do not use this unit near the high frequency instruments high frequency welding machine sewing machine large capacity SCR controller Installation environment Indoor Outdoor Altitude max 2 000m Pollution degree 2 Installation category Ⅱ Use the verified explosion proof electric connection c...