Modbus address map
(1) Alarm output setup group [ Alarm Setup ]
Parameter
Addr
Description
Setting range
Unit Default
CH1 AL1 Type
40101
CH1 alarm output1
operation
0: Off, 1: PV.Hi 2: PV.Lo,
3: SBA 4: P.End
- PV.Hi
CH1 AL1 Opt
40102
CH1 alarm output1 option
0: None, 1: Latch,
2: StBy, 3: La+St
- None
CH1 AL1 Low
※
1
40103
CH1 alarm output1
low-limit SV
Display range by input
type
Digit
-200
CH1 AL1 High
※
1
40104
CH1 alarm output1
high-limit SV
1350
CH1 AL2 Type
40105
CH1 alarm output2
operation
0: Off, 1: PV.Hi, 2: PV.Lo,
3: SBA, 4: P.End
- PV.Lo
CH1 AL2 Opt
40106
CH1 alarm output2 option
0: None, 1: Latch, 2: StBy,
3: La+St
- None
CH1 AL2 Low
※
1
40107
CH1 alarm output2
low-limit SV
Display range by input
type
Digit
-200
CH1 AL2 High
※
1
40108
CH1 alarm output2
high-limit SV
1350
CH1 Alarm Hys
40109
CH1 alarm output hysteresis 001 to 999
Digit 001
CH2 AL1 Type
※
2
40110
CH2 alarm output1
operation
0: Off, 1: PV.Hi, 2: PV.Lo,
3: SBA, 4: P.End
- PV.Hi
CH2 AL1 Opt
※
2
40111
CH2 alarm output1 option
0: None 1: Latch 2: StBy
3: La+St
- None
CH2 AL1 Low
※
1
※
2
40112
CH2 alarm output1
low-limit SV
Display range by input
type
Digit
-200
CH2 AL1 High
※
1
※
2
40113
CH2 alarm output1
high-limit SV
1350
CH2 AL2 Type
※
2
40114
CH2 alarm output2
operation
0: Off, 1: PV.Hi, 2: PV.Lo,
3: SBA4: P.End
- PV.Lo
CH2 AL2 Opt
※
2
40115
CH2 alarm output2 option
0: None, 1: Latch, 2: StBy,
3: La+St
- None
CH2 AL2 Low
※
1
※
2
40116
CH2 alarm output2
low-limit SV
Display range by input
type
Digit
-200
CH2 AL2 High
※
1
※
2
40117
CH2 alarm output2
high-limit SV
1350
CH2 Alarm Hys
※
2
40118
CH2 alarm output
hysteresis
001 to 999
Digit 001
※
It displays only for alarm output models.
※
1. It is related with alarm output operation(AL Type) parameter setting.
CH AL
Type(Off, SBA or P.End): CH
AL Low, CH AL
High parameters are not displayed.
CH AL
Type(PV.Hi): CH
AL High parameter is not displayed.
CH AL
Type(PV.Lo): CH
AL Low parameter is not displayed.
※
2. It displays only for 2 channels alarm output model.
Содержание KRN50 SERIES
Страница 2: ... ii Copyright Reserved Autonics Co Ltd ...
Страница 20: ...2 Specifications 20 Copyright Reserved Autonics Co Ltd ...
Страница 22: ...3 Dimensions 22 Copyright Reserved Autonics Co Ltd ...
Страница 24: ...4 Connections 24 Copyright Reserved Autonics Co Ltd ...
Страница 28: ...6 Functions 28 Copyright Reserved Autonics Co Ltd ...
Страница 34: ...7 General operation and parameter setting menu 34 Copyright Reserved Autonics Co Ltd ...
Страница 66: ...8 Recording 66 Copyright Reserved Autonics Co Ltd ...
Страница 71: ...8 Recording 71 Copyright Reserved Autonics Co Ltd ...
Страница 75: ...8 Recording 75 Copyright Reserved Autonics Co Ltd ...
Страница 77: ...8 Recording 77 Copyright Reserved Autonics Co Ltd ...