background image

U-15

LCD Touchscreen Paperless Recorder

-|Transparent setting guide|-

 Error

Displays error messages on screen and print data when error occurs.

Message

Description

HHHH

When input type is temperature sensor (Thermocouple, RTD) and the measurement value is higher 

than high-limit value of input range, it flashes HHHH. It is cleared when the measurement value is within 

the high-limit range.
When input type is analog (voltage, current (shunt)) and the measurement value is over 10% of high-

limit input range, it flashes HHHH. It is cleared when the measurement value is within 10% of high-limit 

input range.

LLLL

When input type is temperature sensor (Thermocouple, RTD) and the measurement value is lower than 

low-limit value of input range, it flashes LLLL. It is cleared when the measurement value is within the 

 

low-limit range.
When input type is analog (voltage, current (shunt)) and the measurement value is over 10% of low-limit 

input range, it flashes LLLL. It is cleared when the measurement value is within 10% of low-limit input 

range.

BURN

When input type is temperature sensor (Thermocouple, RTD) and input is break, it flashes BURN. It is 

cleared when input is connected. 

ASKey

When forgetting and entering invalid password 3 times, “ASKey” appears with error message. Contact our 

service center with ASKey.

 Functions

 Factory Default

 Display

Menu

Default

History Mode Graph

H Trend

Memory

Internal Memory

File Name

-

Parameter

Default

Parameter

Default

CH Rotation 

Time

5s

Display CH 

Color

Auto set

Name

GROUP1

Line Thickness 2Pt

No. of CHs

Auto set

Min. Value

-200.0

Background

21 (White)

Max. Value

1350.0

Display CH

Auto set

Parameter

Default

Parameter

Default

Special Func. None

Record Method Instant

Ref. CH

-

Digital Filter

None

Two Unit

-

No. of 

Digital Filters

1

Input Bias

0.0

Burn-out Mark None

Span

1.000

 Input CH Info.

Parameter

Default

Parameter

Default

Copy

None

High-Limit Input

Auto set

Tag Name

CH-1

Point

0.0

Input Type

TC-K

Low-Limit Scale -

Low-Limit 

Graph Scale

-200.0

Low-Limit Scale -

High-Limit

Graph Scale

1350.0

Display Unit

Low-Limit Input

Auto set

Parameter

Default

Parameter

Default

Type

PV.Hi

ON Delay

0s

Ref. CH

-

OFF Delay

0s

Option

Normal

Alarm No.

None

Setting Value

1350.0

Save Event

ON

Hys

0.0

 

File History

 

Input/Display

 

Input Option

 

Alarm

 

Group Setting

Содержание KRN1000 Series

Страница 1: ...unication Visit our website www autonics com to download the manuals The user manual includes product specifications functions and operations The user manual for communication includes information about Modbus RTU protocol Modbus TCP protocol and Modbus mapping table LCD Touchscreen Paperless Recorder Features Manuals Comprehensive Device Management Program DAQMaster DAQMaster is comprehensive dev...

Страница 2: ...mpling period 1 to 4 CH 25ms 125ms 250ms 5 to 16 CH 125ms 250ms internal sampling period is average movement filter and alarm output operation unit time Recording period 1 to 3600 sec Internal memory Approx 200MB External memory 2 SD USB memory max 32GB Dielectric strength 2300VAC 50 60Hz for 1 min between power terminals and case Except Ethernet and USB device Vibration Mechanical 10 to 60Hz 4 9m...

Страница 3: ...ed at the same time If sensor input line is longer it is recommended to use shield cable to reduce noise Type Input Output type Description Universal input Input type RTD JPt100Ω DPt100Ω DPt50Ω Cu100Ω Cu50Ω supplied current approx 190µA Thermocouple B C W5 E G J K L L Russia N P R S T U Analog Voltage 60mV 200mV 2V 1 5V 5V 1V 10V Current 0 20mA 4 20mA measurable when using 250Ω shunt resistance 1 ...

Страница 4: ...0 0 32 0 to 1112 0 273 2 to 873 2 U CC TC U 200 0 to 400 0 328 0 to 752 0 73 2 to 673 2 Platinel Ⅱ TC P 0 0 to 1350 0 32 0 to 2462 0 273 2 to 1623 2 RTD Cu50Ω CU50 200 0 to 200 0 328 0 to 392 0 73 2 to 473 2 Cu100Ω CU100 200 0 to 200 0 328 0 to 392 0 73 2 to 473 2 JPt100Ω JPT100 200 0 to 600 0 328 0 to 1112 0 73 2 to 873 2 DPt50Ω DPT50 200 0 to 600 0 328 0 to 1112 0 73 2 to 873 2 DPt100Ω DPT100 20...

Страница 5: ...nput output Power input Power connection 100 240VAC 50 60Hz Universal input Communication output Option input output 1 Option input output 2 Alarm output 8 channels Alarm output 6 channels Digital input 2 channels Option input output 3 Option input output 4 Alarm output 6 channels Power for transmitter output Alarm output 4 channels Digital input 2 channels Power for transmitter output In case of ...

Страница 6: ...digital figures Front cover Open the front cover There are power switch and USB Host Device SD card slot Power switch Turn ON OFF the power of KRN1000 USB host port Connect the USB memory It recognizes up to 32GB When using extension cable cable length should be up to 1 5m Connect only USB device USB device port Used for connecting PC via Modbus RTU communication SD card slot SD card memory slot I...

Страница 7: ...t value display part Displays the measured value of each channel as graph Set one graph among 9 graphs bar graph Vertical Horizontal Trend graph Vertical Horizontal Mixed graph Divided Vertical Horizontal Trend Graph Group All Digital Bar graph Vertical Horizontal Trend graph Divided Vertical Horizontal Trend Graph Vertical Horizontal Mixed graph Group All Digital Screen Description ...

Страница 8: ...U 11 LCD Touchscreen Paperless Recorder Transparent setting guide Touch the status display part at the upper screen and menu appears as right screen Menu is as below Menu ...

Страница 9: ... limit scale 1000 high limit scale 1000 if input value is 2V display value is 400 In case voltage current shunt input type this mode is used when input value is calculated by Root for the desired display value Differential pressure signal of differential pressure flow meter is calculated Root for the to be measured flux This function is used to measure flux by input value E g In case low limit inp...

Страница 10: ...Set the summer time duration Set enable to summer time and designate start date and end date of summer time at Menu System Info Date Time High Low Limit Graph Scale Value In case of temperature sensor input thermocouple RTD set the graph scale value to set the desired record range Therefore it helps to record as curve at the desired range Display Scale For analog input this function is to set 9999...

Страница 11: ...network hub HUB and gateway etc there is no distance limit but it is recommended to use min network Please use communication cables which is satisfied the below conditions RS422 485 communication Shield Twist Pair over AWG24 characteristic impedance 100Ω capacity component 50 pF m cable length max 1km Ethernet communication Over CAT5E cable max length 100m USB communication Single cable built in f...

Страница 12: ... When input type is temperature sensor Thermocouple RTD and input is break it flashes BURN It is cleared when input is connected ASKey When forgetting and entering invalid password 3 times ASKey appears with error message Contact our service center with ASKey Functions Factory Default Display Menu Default History Mode Graph H Trend Memory Internal Memory File Name Parameter Default Parameter Defau...

Страница 13: ...0 Internal Memory Storage Options Overwrite System Info Parameter Default Parameter Default Date Setting Auto set Summer Time Disable Time Setting Summer Time Duration 1month 1day to 1month 1day Date Type yyyy mm dd Time 1 hour Parameter Default Parameter Default Reservation Recording Date Reservation Type Disable Reservation Recording Time Parameter Default Parameter Default Device Name KRN1000 R...

Страница 14: ...same thickness and length For thermocouple CT temperature sensor use the designated compensation wire for extending wire Keep away from high voltage lines or power lines to prevent inductive noise In case installing power line and input signal line closely use line filter or varistor at power line and shielded wire at input signal line Do not use near the equipment which generates strong magnetic ...

Отзывы: