J-42

 Features

 Ordering information

DIN W48×H48mm, Preset counter/timer

 Upgraded counting speed : 1cps/30cps/2kcps/5kcps

 Selectable voltage input(PNP) or No-voltage input(NPN)

 Addition of Up/Down input mode

 Available to set a decimal point(Fixed decimal point of display)

 Wide range of input power supply :

   100-240VAC 50/60Hz, 12-24VAC/DC(Option)

 Selectable Counter/Timer by internal DIP switch

 Various time rangelBuilt-in microprocessor

 Speci

fi

 cations

Model

Single preset

FX4S

-

Indicator

-

FX5S-I

Digit

4digit 5digit 

Digit size

W3.8×H7.6

mm 

W4×H8

mm

Power supply

100-240VAC 50/60Hz, 12-24VAC/DC(Option)

Allowable voltage range

90 to 110% of rated voltage

Power consumption

• Indication type : Approx. 4.7VA (240VAC 60Hz), Approx. 5.6VA (24VAC 60Hz), Approx. 2.8W(24VDC)
• Single preset : Approx. 5.7VA(240VAC 60Hz), Approx. 4.5VA(24VAC 60Hz), Approx. 3W(24VDC)

Max. counting speed for CP1, CP2 Selectable 1cps/30cps/2kcps/5kcps by internal DIP switch
Min. input
signal width

INHIBIT input

Approx. 20ms

RESET input

Input

CP1, CP2  input
(INHIBIT)

Input logic is selectable

[Voltage input] Input impedance : 5.4k

Ω

 "H" level : 5-30VDC, "L" level : 0-2VDC

[No-voltage input] Impedance at short-circuit : Max. 1k

Ω

, Residual voltage at short-circuit : Max. 2VDC,          

                              Impedance at open-circuit : Min. 100k

Ω

RESET input

One-shot output time

0.05 to 5sec 

-

Control
output

Contact

Type

SPDT(1c) 

-

Capacity 250VAC 3A at resistive load

-

Solid-
state

Type

NPN open collector

-

Capacity 30VDC Max. 100mA Max.

-

Memory protection

10 years(When using non-volatile semiconductor memory)

External power

12VDC±10% 50mA Max.

Insulation resistance

Min. 100M

Ω

(at 500VDC megger)

Dielectric strength

2000VAC 50/60Hz for 1 minute

Noise
 strength

AC power

±2kV the square wave noise(pulse width : 1

) by the noise simulator

DC power

±500V the square wave noise(pulse width : 1

) by the noise simulator

Vibration

Mechanical

0.75mm amplitude at frequency of 10 to 55Hz(for 1 min.) in each of X, Y, Z directions for 1 hour

Malfunction

0.5mm amplitude at frequency of 10 to 55Hz(for 1 min.) in each of X, Y, Z directions for 10 minutes

Shock

Mechanical

300m/s²(Approx. 30G) in each of X, Y, Z directions for 3 times

Malfunction

100m/s²(Approx. 10G) in each of X, Y, Z directions for 3 times

Relay
life cycle

Mechanical

Min. 10,000,000 operations

Electrical

Min. 100,000 operations(250VAC 3A at resistive load)

Environ
-ment

Ambient temperature 10 to 55

, storage: -25 to 65

Ambient humidity 35 to 85%RH, storage: 35 to 85%RH

Approval
Unit weight

AC type : Approx. 147g, DC type : Approx. 153g

AC type : Approx. 137g, DC type : Approx. 143g

FXS Series

Item

Digit

Size

Output

FX

FX

4

S

I

No mark Single preset
I

Indicator

4

9999(4digit)

5

99999(5digit)

S

DIN W48×H48

mm

FX

Counter/Timer

Please read “Caution for your safety” in operation

manual before using.

Environment resistance is rated at no freezing or condensation.   

Содержание FX4S

Страница 1: ...Control output Contact Type SPDT 1c Capacity 250VAC 3A at resistive load Solid state Type NPN open collector Capacity 30VDC Max 100mA Max Memory protection 10 years When using non volatile semiconductor memory External power 12VDC 10 50mA Max Insulation resistance Min 100MΩ at 500VDC megger Dielectric strength 2000VAC 50 60Hz for 1 minute Noise strength AC power 2kV the square wave noise pulse wid...

Страница 2: ...when using for timer Operated by a power ON start when it is used as a timer Sensor Sensor Sensor Sensor FXS Sereis FXS Sereis FXS Sereis FXS Sereis FXS Sereis FXS Sereis NPN output PNP output NPN open collector output PNP open collector output CP1 CP2 INHIBIT RESET input CP1 CP2 INHIBIT RESET input Please select the counting speed as 30cps when it is used for counter Please select the counting sp...

Страница 3: ... logic Select PNP Voltage input In case of operating the load by power supply of the sensor Using 2 counters with one sensor It is available to use 2 counters with one sensor Please connect as the power of sensor is supplied from only one of countes and design input logic with same way Please select proper capacity of load because total current consumption should not be exceed current capacity Max...

Страница 4: ...t operation mode in indication type FX5S I and SW2 selection switch SW1 CP1 CP2 1cps 30cps 2kcps 5kcps SW1 Function 4 Down mode Up mode SW1 Function 5 Counter Timer SW1 Function 8 Disable the memory protection Enable the memory protection ON OFF ON OFF ON OFF ON OFF 6 7 ON OFF 6 7 ON OFF 6 7 ON OFF 6 7 ON OFF ON OFF ON OFF Max counting speed ON ON OFF 3 2 1 8 7 6 5 4 3 2 1 SW2 SW1 Setting function...

Страница 5: ...0 0 n 1 n 1 n 1 n 1 n 1 n 1 n 1 n 1 n 1 n n n n n n 2 n 2 n 2 n 2 n 2 n 2 n 2 n 2 n 2 n 2 n 2 n 3 n 3 n 3 n 3 n 3 n 4 n 4 n 5 n 5 n 3 n 3 n 3 0 0 0 0 0 1 1 1 1 1 1 1 2 2 2 2 3 3 No counting No counting No counting No counting 4 4 5 5 2 2 2 2 3 3 3 3 Ⓐ Ⓐ Ⓐ Ⓐ Ⓐ Ⓐ Ⓐ Ⓐ Ⓐ Ⓐ ⒷⒷⒷⒷ ⒷⒷⒷⒷ L L L L L L L L L L L L L L L L L L Count value Count value Count value Count value Count value Count value Count value ...

Страница 6: ... 99min 59 9sec 999 9min 9999 9min 99hour 59min 9hour 59min 59sec 999 9hour 999hour 59min 9999hour 9999 9hour RESET RESET INHIBIT INHIBIT RESET RESET RESET RESET Max display value Max time range Max time range Max time range Max display value Max display value Max display value Max display value Max display value Max display value 0 0 ON 1 2 3 OFF ON 1 2 3 OFF ON 1 2 3 OFF ON 1 2 3 OFF ON 1 2 3 OFF...

Страница 7: ...E F F The display value continuesuntil reset signal is appliedthen output is held Retained output will be maintained until reset signal is applied N Display value and retained output are maintained until Reset signal is applied C The display value returns to reset start status as soon as display value is reached to preset value R The display value is held until output is OFF then returns to reset ...

Страница 8: ...ted spec when duty ratio is 1 3 It can not respond if it is smaller than min singal width Ta Error signal Error description Returning method Zero setting status Change the setting value to non zero status Reset function Reset In case of changing the input mode after supplying the power please take external reset or manual reset If reset is not executed the counter will be working as previous mode ...