6.Parametersettingandfunctions
27
©CopyrightReservedAutonicsCo.,Ltd.
6.Parametersettingandfunctions
6.1
Controlinput
(1)Inputtype
Type
Parameter
AUTO
input
Analog input
Current
4-20mA
Input
impedance
100Ω
4-20
0-20mA
0-20
Voltage
1-5VDC
Input
impedance
25Ω
1-5
0-5VDC
0-5
0-10VDC
0-10
ON/OFF
input
Voltage pulse
0/12VDC
SSR
No-voltage pulse ON/OFF
-
Com. input
RS485
-
-
COM
MANUAL input
Internal VR
10kΩ
-
-
External VR
3 to 10kΩ
-
-
(2)Inputselection
In AUTO input, select it at control input type [
IN-P
] at setting mode1.
In MANUAL input, set output slope manual adjustment [
A-GA
] in operating mode as OFF and
select the input by the inner 3-level slide switch.
• Output slope manual adjustment [
A-GA
] setting as OFF: Select the input by the inner 3-level
slide switch.
Type
Description
MAN
INT
Adjust output slope with the internal VR
MAN
EXT
Adjust output slope with the external VR
AUTO
No function
AUTO/MANUAL selection is available by no.7 and 11 terminals. ON setting is for AUTO input drive
and OFF setting is for MANUAL input drive. When AUTO/MANUAL terminal input is OFF, internal
AUTO/MANUAL selection switch is available only for setting MAN INT, and MAN EXT.
Содержание Digipower 2000
Страница 2: ... ii Copyright Reserved Autonics Co Ltd ...
Страница 8: ...Safety Precautions viii Copyright Reserved Autonics Co Ltd ...
Страница 14: ...1 Product introduction 14 Copyright Reserved Autonics Co Ltd ...
Страница 26: ...5 Installation and initial operation 26 Copyright Reserved Autonics Co Ltd ...
Страница 46: ...7 Factory default 46 Copyright Reserved Autonics Co Ltd ...
Страница 54: ...9 Modbus Mapping Table 54 Copyright Reserved Autonics Co Ltd ...