1.3
Read Holding Registers(Func 03–03H)
Reads the Binary data of Holding Registers(4X reference) in Slave device.
(1)
Query (Master)
Slave Address Function
Starting Address
No. of Points
Error Check(CRC16)
Hi(Upper)
Lo(Lower)
Hi(Upper)
Lo(Lower)
Lo(Lower)
Hi(Upper)
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
(2)
Response (Slave)
Slave Address Function Byte Count
Data(Data)
Data(Data)
Data(Data)
Error Check(CRC16)
Hi(Upper) Lo(Lower) Hi(Upper) Lo(Lower) Hi(Upper) Lo(Lower) Lo(Lower) Hi(Upper)
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
If reading the values of 2, from Holding Register 400001(0000 H) to 400002(0001 H), in
Slave(Address 17) from the Master.
Query (Master)
Slave Address Function
Starting Address
No. of Points
Error Check(CRC16)
Hi(Upper)
Lo(Lower)
Hi(Upper)
Lo(Lower)
Lo(Lower)
Hi(Upper)
11 H
03 H
00 H
00 H
00 H
02 H
## H
## H
If the value of 400001(0000 H) on Slave is “555(22B H)” and the value of 400002(0001 H) is
“100(64 H)”.
Response (Slave)
Slave Address Function
Byte Count
Data(Data)
Data(Data)
Error Check(CRC16)
Hi(Upper) Lo(Lower) Hi(Upper) Lo(Lower) Lo(Lower) Hi(Upper)
11 H
03 H
04 H
02 H
2B H
00 H
64 H
## H
## H
CRC16
CRC16
Содержание BFC Series
Страница 1: ... Copyright Reserved Autonics Co Ltd i USER MANUAL For COMMUNICATION ...
Страница 2: ...ii Copyright Reserved Autonics Co Ltd ...
Страница 8: ...Table of Contents viii Copyright Reserved Autonics Co Ltd ...
Страница 45: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 45 ...
Страница 46: ...2 Modbus Mapping Table 46 Copyright Reserved Autonics Co Ltd MSB BFCC1 V1 3 1701US ...