![Autometers Systems IC 995 Скачать руководство пользователя страница 2](http://html1.mh-extra.com/html/autometers-systems/ic-995/ic-995_installation-and-operating-manual_3022058002.webp)
EN61010:2001
LVD approval
8
2
3
96
96
96
70
90
76
45
90
90
85
Neutral
L1
L2
L3
Direc tion of Current
L
O
A
D
M
A
I
N
S
P1
P1
P1
S1 S2
S1 S2
S1
S2
230 volt
Auxiliary
Supply
Kwh
Pulse
Output
RS 485
Tx+
Tx-
Shield
Terminals 34-36
Digital I nputs
The meter
must
have Auxiliar y Power
Supply connected
Terminals 24-28
Digital Outputs
2. Functionality
1. Multi-function
: accurately measures phase voltages, line voltages, line currents,
active, reactive and apparent power, phase and total power factors, frequency and
maximum demand.
2. Harmonics
: the IC995 measures component harmonics up to the 31st inst and THD
for both current and voltage.
3. Network analysis
: displays 4-quadrant energies, including active capacitive energy,
active inductive energy, reactive capacitive energy and reactive inductive energy. Also
measures current “K” factor, voltage crest factor, waveform factor and degree of voltage
and current imbalance.
4. Inputs/Outputs
: the IC995 is provided with 4 digital inputs, 2 digital relay outputs,
1 volt-free pulse output (set at 10kWh/pulse) and 1 RS485 (Modbus protocol) output
in order to satisfy remote meter reading and system control monitoring.
3. Technical features
FEATURE
VALUES
Network
1PH2W, 3P3W, 3P4W
Frequency
45~65Hz
Voltage
Normal: AC 100V, 400V
INPUT
Overloading: 600V (continuous); 1000V / 30s
Consumption: < 0.2VA
Current
Normal: AC 1A, 5A
Overloading: 6A(continuous); 50A /1s
Consumption: < 0.2VA
Pulse output
Mode: Optocoupler pulse output, volt free
Communication
RS485 (Modbus-RTU)
Digital input (DI)
4 drying contact inputs, with +5V power
Digital output (DO)
Mode: 2 NO contacts (AC 250V/3A, DC 30V/3A)
Accuracy
Frequency 0.01Hz, reactive energy 1 class, others 0.5 class
Display
LCD with backlight
Power supply
AC/DC 85~270V; consumation:
≤4VA
Isolation
Power / current input / voltage input: AC2kV/1min;
Power / Digital inputs / RS485: AC1.5kV/1min;
Inputs / outputs / housing >5M_
Environment
Working T: -10C~+45C; Storing T: -20C~+70C
Relative humidity: 5%~95% Non-Condensing; Altitude: ≤2500m
Material used
Polycarbonate v.0 rated
The IC 995 meter is manufactured in compliance to:
EN 62052-11: 2004
(AC) General requirements
EN 62053-21: 2003
(Particular requirements part 21 static meters)
Dimensions
Connection Diagram
3 phase 4 wire, 230/400v 50Hz
* it is important P2 faces the Load side