background image

3505 HUTCHINSON ROAD 

CUMMING, GA 30040-5860, USA

®

S

tride

®

 F

ield

 i/O M

Odules

POWER SUPPLY

Power Supply Voltage

 

To maintain a UL 508 panel listing use a 

Class 2 power supply.

Reverse Polarity Protection

60VDC max

Current Consumption

ISOLATION

Power Supply / Ethernet

1500VAC, 50Hz, 1 min

Inputs / Power Supply

1500VAC, 50Hz, 1 min

Inputs / Ethernet

1500VAC, 50Hz, 1 min

Input / Input

1500VAC, 50Hz, 1 min

ENVIRONMENTAL CONDITIONS

Operating Temperature

-10°C to +60°C [+14°F to +140°F]

UL Operating Temperature

-10°C to +40°C [+14°F to +104°F]

Storage Temperature

-40°C to +85°C [-40°F to +185°F]

Humidity (non-condensing)

0 to 90%

Maximum Altitude

2000m [6500ft]

Installation

Indoor

Pollution Degree

2

CONNECTIONS

Ethernet

RJ-45

Inputs / Power Supply

Removable screw terminals

MECHANICAL SPECIFICATIONS

Material

Self-extinguishing plastic

IP Code

IP20

Wire diameter

0.8 to 2.1 mm

2

 / AWG 14–18

Tightening Torque

0.5 N·m [4.4 in·lb]

Mounting

In compliance with DIN rail standard EN-50022

Weight

EMC (for industrial environments)

Immunity

EN 61000-6-2

Emission

EN 61000-6-4

UL

US Standard

UL 61010-1

Canadian Standard

CSA C22.2 No 61010-1

CCN

NRAQ/NRAQ7

UL Type Designation

Open Type device

Classification

Industrial Control Equipment

File Number

E157382

TECHNICAL SPECIFICATIONS (typical @ 25°C, nominal conditions)

FEATURES

•  Interface Ethernet 10/100 Base-T, Modbus TCP Server

•  4 isolated input channels

• 

Each input configurable for RTD, Resistance or Potentiometer

• 

Integrated web server to acquire the status of the analog inputs via browser

• 

Remotely configurable

• 

Connection by removable screw terminals

• 

LED signaling for Link/Act Ethernet, power supply

•  Galvanic isolation

• 

UL listed / CE mark

• 

In compliance with EN-50022 DIN rail mounting

T

eMperaTure

 i

npuT

 M

Odule

: rTd, 4-

channel

 (pn# siO-MB04rTds)

GENERAL DESCRIPTION

The SIO-MB04RTDS device is a Modbus TCP server that can convert up to 4 analog signals applied to the inputs into engineering units in digital format.

The inputs can be connected to two-wire or three-wire RTD or resistance sensors.

The input channels are electrically isolated from each other. 

The device guarantees high accuracy and a stable measurement versus time and temperature. The device is equipped with a selectable Watchdog Timer 

system. The Ethernet interface allows reading and writing the values of the internal registers of the device in real time. 

Signal LEDs for Ethernet activity and power supply allow direct monitoring of the system. 

The built-in Web Server allows remote visualization, acquisition of the analog inputs and access to the configuration parameters.

Connections are made by removable screw terminals (inputs and power supply) and RJ45 plug (Ethernet).

The SIO-MB04RTDS is in compliance with Directive UL 61010-1 for the US market and with Directive CSA C22.2 No 61010-1 for the Canadian market.

The device has full electrical isolation between the lines, providing protection against the effects of ground loops existing in industrial applications.

It is housed in a tough self-extinguishing plastic enclosure which, thanks to its thin 22.5 mm profile, allows high-density mounting on EN-50022 standard DIN rail.

USER INSTRUCTIONS

Before installing the device, please read the “Installation Instructions” section.

To configure the device in INIT mode, refer to the User Guide. Connect power supply, Ethernet and analog inputs as shown in the “Wiring” section. The LED 

states indicate the working condition of the device; see the “Front Panel LEDs” table to verify the device working state. 

Instructions for configuration and calibration operations are contained in the User Guide.

To simplify handling or replacing of the device, it is possible to remove the wired terminals even with the device powered.

 

14–30VDC 

 

150mA max (2)

About 160g [5.6 oz]

I/O SPECIFICATIONS

Input Accuracy (1) RTD

±0.05% full scale

Resistance

±0.05% full scale

Potentiometer

±0.05% full scale

Linearity (1)

RTD

±0.1% full scale

Lead Wire Resistance Influence(1)

RTD/res. 3 wires (50

Ω

 max balanced) 

±0.05% full scale/

Ω

RTD Excitation Current

0.370 mA typical

Thermal Drift (1) Full Scale

±0.01%/°C

Sampling Time

150ms (4 channels)

Warm-up Time

3 min.

(1)   Referred to input Span (difference between maximum and minimum values).

NETWORK CONNECTIVITY

Standard

In compliance with IEEE 802.3

Network Interface

Ethernet 10/100Base-T

Protocol

Modbus TCP

Max. Cable Length

100m [328ft]

Number of Sockets

16 simultaneous Modbus TCP connections

INPUTS

Input Type

Min

Max

RTD 2 or 3 wire 

Pt100 

Pt1000 

Ni100 

Ni1000

 

-200°C 

-200°C 

-60°C 

-60°C

 

850°C 

200°C 

180°C 

150°C

Resistance 2 or 3 wire 

Low 

High

 

0

Ω

 

0

Ω

 

500

Ω

 

2000

Ω

Pot. (nominal value)

20

Ω

50k

Ω

Please refer to the User Guide for more information, including the 

compete Modbus address list. Access the user guide by visiting

https://www.automationdirect.com/pn/doc/manual/SIO-MB04RTDS

or scan the QR code below.