3505 HUTCHINSON ROAD
CUMMING, GA 30040-5860, USA
®
S
tride
®
F
ield
i/O M
Odules
POWER SUPPLY
Power Supply Voltage
To maintain a UL 508 panel listing use a
Class 2 power supply.
Reverse Polarity Protection
60VDC max
Current Consumption
ISOLATION
Power Supply / Ethernet
1500VAC, 50Hz, 1 min
Inputs / Power Supply
1500VAC, 50Hz, 1 min
Inputs / Ethernet
1500VAC, 50Hz, 1 min
Input / Input
1500VAC, 50Hz, 1 min
ENVIRONMENTAL CONDITIONS
Operating Temperature
-10°C to +60°C [+14°F to +140°F]
UL Operating Temperature
-10°C to +40°C [+14°F to +104°F]
Storage Temperature
-40°C to +85°C [-40°F to +185°F]
Humidity (non-condensing)
0 to 90%
Maximum Altitude
2000m [6500ft]
Installation
Indoor
Pollution Degree
2
CONNECTIONS
Ethernet
RJ-45
Inputs / Power Supply
Removable screw terminals
MECHANICAL SPECIFICATIONS
Material
Self-extinguishing plastic
IP Code
IP20
Wire diameter
0.8 to 2.1 mm
2
/ AWG 14–18
Tightening Torque
0.5 N·m [4.4 in·lb]
Mounting
In compliance with DIN rail standard EN-50022
Weight
EMC (for industrial environments)
Immunity
EN 61000-6-2
Emission
EN 61000-6-4
UL
US Standard
UL 61010-1
Canadian Standard
CSA C22.2 No 61010-1
CCN
NRAQ/NRAQ7
UL Type Designation
Open Type device
Classification
Industrial Control Equipment
File Number
E157382
TECHNICAL SPECIFICATIONS (typical @ 25°C, nominal conditions)
FEATURES
• Interface Ethernet 10/100 Base-T, Modbus TCP Server
• 4 isolated input channels
•
Each input configurable for RTD, Resistance or Potentiometer
•
Integrated web server to acquire the status of the analog inputs via browser
•
Remotely configurable
•
Connection by removable screw terminals
•
LED signaling for Link/Act Ethernet, power supply
• Galvanic isolation
•
UL listed / CE mark
•
In compliance with EN-50022 DIN rail mounting
T
eMperaTure
i
npuT
M
Odule
: rTd, 4-
channel
(pn# siO-MB04rTds)
GENERAL DESCRIPTION
The SIO-MB04RTDS device is a Modbus TCP server that can convert up to 4 analog signals applied to the inputs into engineering units in digital format.
The inputs can be connected to two-wire or three-wire RTD or resistance sensors.
The input channels are electrically isolated from each other.
The device guarantees high accuracy and a stable measurement versus time and temperature. The device is equipped with a selectable Watchdog Timer
system. The Ethernet interface allows reading and writing the values of the internal registers of the device in real time.
Signal LEDs for Ethernet activity and power supply allow direct monitoring of the system.
The built-in Web Server allows remote visualization, acquisition of the analog inputs and access to the configuration parameters.
Connections are made by removable screw terminals (inputs and power supply) and RJ45 plug (Ethernet).
The SIO-MB04RTDS is in compliance with Directive UL 61010-1 for the US market and with Directive CSA C22.2 No 61010-1 for the Canadian market.
The device has full electrical isolation between the lines, providing protection against the effects of ground loops existing in industrial applications.
It is housed in a tough self-extinguishing plastic enclosure which, thanks to its thin 22.5 mm profile, allows high-density mounting on EN-50022 standard DIN rail.
USER INSTRUCTIONS
Before installing the device, please read the “Installation Instructions” section.
To configure the device in INIT mode, refer to the User Guide. Connect power supply, Ethernet and analog inputs as shown in the “Wiring” section. The LED
states indicate the working condition of the device; see the “Front Panel LEDs” table to verify the device working state.
Instructions for configuration and calibration operations are contained in the User Guide.
To simplify handling or replacing of the device, it is possible to remove the wired terminals even with the device powered.
14–30VDC
150mA max (2)
About 160g [5.6 oz]
I/O SPECIFICATIONS
Input Accuracy (1) RTD
±0.05% full scale
Resistance
±0.05% full scale
Potentiometer
±0.05% full scale
Linearity (1)
RTD
±0.1% full scale
Lead Wire Resistance Influence(1)
RTD/res. 3 wires (50
Ω
max balanced)
±0.05% full scale/
Ω
RTD Excitation Current
0.370 mA typical
Thermal Drift (1) Full Scale
±0.01%/°C
Sampling Time
150ms (4 channels)
Warm-up Time
3 min.
(1) Referred to input Span (difference between maximum and minimum values).
NETWORK CONNECTIVITY
Standard
In compliance with IEEE 802.3
Network Interface
Ethernet 10/100Base-T
Protocol
Modbus TCP
Max. Cable Length
100m [328ft]
Number of Sockets
16 simultaneous Modbus TCP connections
INPUTS
Input Type
Min
Max
RTD 2 or 3 wire
Pt100
Pt1000
Ni100
Ni1000
-200°C
-200°C
-60°C
-60°C
850°C
200°C
180°C
150°C
Resistance 2 or 3 wire
Low
High
0
Ω
0
Ω
500
Ω
2000
Ω
Pot. (nominal value)
20
Ω
50k
Ω
Please refer to the User Guide for more information, including the
compete Modbus address list. Access the user guide by visiting
https://www.automationdirect.com/pn/doc/manual/SIO-MB04RTDS
or scan the QR code below.