The P2-8AD4DA-2 Voltage Analog Input/Output
Module provides eight channels of 0-10 VDC
inputs and four channels of 0-10 VDC outputs
for use with the Productivity2000 System.
General Specifications . . . . . . . . . . . . . . . . . . . . . . 1
Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 2
Output Specifications . . . . . . . . . . . . . . . . . . . . . . . 2
Wiring Diagram and Schematic . . . . . . . . . . . . . . . . 3
Module Installation Procedure . . . . . . . . . . . . . . . . . 4
QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Hot Swap Information . . . . . . . . . . . . . . . . . . . . . . . 4
Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Module Configuration . . . . . . . . . . . . . . . . . . . . . . . 5
Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Non-Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . 6
OLED Panel Display Menus . . . . . . . . . . . . . . . . . . 7
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Removable Terminal Block Specifications. . . . . . . . 8
General Specifications
Operating Temperature
0º to 60ºC (32º to 140ºF)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
IEC60068-2-6 (Test Fc)
Shock
IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation
1800VAC applied for 1 second
Insulation Resistance
> 10MΩ @ 500VDC
Heat Dissipation
1.95 W
Enclosure Type
Open Equipment
Agency Approvals
UL 61010-1 and UL 61010-2-201 File E139594, Canada & USA
CE (EN 61131-2 EMC, EN 61010-1 and EN 61010-2-201 Safety)*
Module Keying to Backplane Electronic
Module Location
Any I/O slot in a Productivity2000 System
Field Wiring
Use ZIPLink Wiring System or removable terminal block (not
included). See “Wiring Options” on page 5.
EU Directive
See the “EU Directive” topic in the Productivity2000 Help File.
Information can also be obtained at:
www.productivity2000.com
Connector Type (not included) 18-Position Removable Terminal Block
Weight
90g (3.2 oz)
*Meets EMC and Safety requirements. See the D.O.C. for details.