background image

1

Sales 800-633-0405

www.productivity2000.com

®

1

I

00.00V

2

I

00.00V

3

I

00.00V

4

I

00.00V

5

I

00.00V

6

I

00.00V

7

I

00.00V

8

I

 SPARE

Terminal Block sold separately, (see wiring options on page 5).

Warranty: Thirty-day money-back guarantee. Two-year limited replacement. 

(See www.productivity2000.com for details).

P2-8AD4DA-2 

Analog Input/Output

The P2-8AD4DA-2 Voltage Analog Input/Output 

Module provides eight channels of 0-10 VDC 

inputs and four channels of 0-10 VDC outputs 

for use with the Productivity2000 System.

General Specifications   . . . . . . . . . . . . . . . . . . . . . . 1

Input Specifications  . . . . . . . . . . . . . . . . . . . . . . . . . 2

Output Specifications   . . . . . . . . . . . . . . . . . . . . . . . 2

Wiring Diagram and Schematic . . . . . . . . . . . . . . . . 3

Module Installation Procedure . . . . . . . . . . . . . . . . . 4

QR Code  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Hot Swap Information  . . . . . . . . . . . . . . . . . . . . . . . 4

Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Module Configuration   . . . . . . . . . . . . . . . . . . . . . . . 5

Linear Scaling  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Non-Linear Scaling  . . . . . . . . . . . . . . . . . . . . . . . . . 6

OLED Panel Display Menus  . . . . . . . . . . . . . . . . . . 7

Warning  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Removable Terminal Block Specifications. . . . . . . .  8

General Specifications

Operating Temperature

0º to 60ºC (32º to 140ºF)

Storage Temperature

-20º to 70ºC (-4º to 158ºF)

Humidity

5 to 95% (non-condensing)

Environmental Air

No corrosive gases permitted

Vibration

IEC60068-2-6 (Test Fc)

Shock

IEC60068-2-27 (Test Ea)

Field to Logic Side Isolation

1800VAC applied for 1 second

Insulation Resistance

> 10MΩ @ 500VDC

Heat Dissipation

1.95 W

Enclosure Type

Open Equipment

Agency Approvals

UL 61010-1 and UL 61010-2-201 File E139594, Canada & USA 

CE (EN 61131-2 EMC, EN 61010-1 and EN 61010-2-201 Safety)*

Module Keying to Backplane Electronic
Module Location

Any I/O slot in a Productivity2000 System

Field Wiring

Use ZIPLink Wiring System or removable terminal block (not 

included). See “Wiring Options” on page 5.

EU Directive

See the “EU Directive” topic in the Productivity2000 Help File. 

Information can also be obtained at: 

www.productivity2000.com

Connector Type (not included) 18-Position Removable Terminal Block
Weight

90g (3.2 oz)

*Meets EMC and Safety requirements. See the D.O.C. for details.

Содержание Productivity2000 P2-8AD4DA-2

Страница 1: ...ations 8 General Specifications Operating Temperature 0 to 60 C 32 to 140 F Storage Temperature 20 to 70 C 4 to 158 F Humidity 5 to 95 non condensing Environmental Air No corrosive gases permitted Vib...

Страница 2: ...Output Specifications Output Channels 4 1 common Module Signal Output Range 0 10 VDC 0 5 VDC Output Signal Resolution 16 bit Resolution Value of LSB least significant bit 0 5 V 76 V count 0 10 V 152 V...

Страница 3: ...or DC Voltage Output Circuits V COM 0 5 VDC Load V COM 0 10 VDC Load 24 VDC User Supplied Power 3 Wire Voltage Transmitter V COM 3 Wire Transmitter V1 V2 V3 V4 V5 V6 V8 V7 COM COM 0V CH1 ADC CH2 ADC...

Страница 4: ...your installation for use of this powerful feature 1 Align with slot 2 rotate to seated position Module Installation WARNING Do not apply field power until the following steps are completed See hot s...

Страница 5: ...d output point channel selected and to each Status Bit Item Module Configuration Wiring Options 1 ZIPLink Feed Through Modules and Cables 0 5 m 1 6 ft cable 1 0 m 3 3 ft cable 2 0 m 6 6 ft cable ZL RT...

Страница 6: ...nk Level 7 0 0 0 0 0 0 0 Select the minimum and maximum values of the raw input signal These values will relate to the minimum and maximum scaled values 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 The Scale Linear...

Страница 7: ...NFO DISPLAY UNITS DECIMAL COUNTS DISPLAY UNITS HEX COUNTS DISPLAY UNITS VOLTS End of Status Menu List MISSING EXTERNAL 24VDC SELFTEST FAIL REPLACE MODULE End of Status Menu List MISSING CONFIG DATA 1I...

Страница 8: ...If you have any questions concerning the installation or operation of this equip ment or if you need additional information please call Technical Support at 770 844 4200 This publication is based on i...