Dimensions and Installation
8.75”
inches
[mm]
4.75
[120.7]
8.50
[215.9]
8.75
[222.3]
9.88
[251.0]
19.56
[496.8]
14.50
[368.3]
15.44
[392.2]
10.31
[261.9]
6.00
[152.4]
6.00
[152.4]
6.00
[152.4]
6.00
[152.4]
7.56
[192.0]
11.25
[285.6]
5.59
[142.1]
5.59
[142.1]
5.59
[142.1]
5.59
[142.1]
Base Dimensions
Mounting Clearances
Provide a minimum clearance of 2 inches
(50mm) between the bases and all sides
of the enclosure. Allow extra door clear-
ance for operator panels and other
door mounted items. There should be a
minimum of 3 inches (76mm) clearance
between the base and any wire duct, and
a minimum of 7.2 inches (183mm) from
base to base in a multiple base installation.
Grounding
A good common ground reference (earth
ground) is essential for proper operation of
the Productivity3000
®
system. One side of
all control circuits, power circuits and the
ground lead must be properly connected to
earth ground by either installing a ground
rod in close proximity to the enclosure
or by connecting to the incoming power
system ground. There must be a single-
point ground (i.e. copper bus bar) for all
devices in the enclosure that require an
earth ground.
Temperature
Considerations
The Productivity3000 system should be
installed within the operating temperature
specifications as listed in this document. If
the temperature deviates above or below
the specification, measures such as cooling
or heating the enclosure should be taken to
maintain the specification.
Power Considerations
The Productivity3000 system is designed
to be powered by 110/220 VAC or 24/48
VDC via one of the Productivity3000
power supplies. The Productivity3000 has
achieved CE certification without requiring
EMF/RFI line noise filters on the AC power
supply. Please review the “EU Directives”
document, located in the User Manual
or at www.automationdirect.com/produc-
tivity/p3000, for applications which require
CE Compliance.