P3 and P6 Terminal Block Hook-Up Diagram
NOTE: THE GSDA-AI-A8 DOES NOT SUPPLY LOOP “EXCITATION VOLTAGE”. If the flowmeter, SCADA
system, etc. does not have a Loop Excitation supply, an ex9 to +36 VDC power source must be
provided, capable of at least 50mA for each of the two 4-20 mA Current Loops (Input and Output), as
shown in the diagram below. Additionally, if the Input and Output must be isolated from each other,
two excitation supplies may be needed.
}
Form C
Relay Output
(Programmable)
GSDA-AI-A8 RELAY Output - Normally Open
GSDA-AI-A8 RELAY Output - Common
GSDA-AI-A8 RELAY Output - Normally Closed
Auto / Manual
Switch
(Open = Manual)
4-20 mA OUT
(White)
- 4-20 mA OUT
(Black)
4-20 mA IN
(White)
- 4-20 mA IN
(Black)
P3
P6
+
-
9-36 VDC
EXCITATION
SUPPLY
+
-
+
-
1
2
3
CUSTOMER
SUPPLIED
IF NEEDED
+
-
+
-
+
-
9-36 VDC
EXCITATION
SUPPLY
CUSTOMER
SUPPLIED
IF NEEDED
+
+