CLK-1
1-800-633-0405
CLICK Module Insert
www.automationdirect.com/click-plc
3505 HUTCHINSON ROAD
CUMMING, GA 30040-5860
C0-04TRS-10 CLICK Expansion I/O Module
Copyright© 2020,
Automationdirect.com
Incorporated/All Rights Reserved Worldwide
C0-04TRS-10
Please read and understand the information in this
insert prior to installation, operation, or servicing
this equipment. Please refer to the CLICK User
Manual (C0-USER-M) for more information
(https://
cdn.automationdirect.com/static/manuals/
).
General Specifi
Operating Temperature
32° to 131°F (0° to 55°C)
Storage Temperature
-4° to 158°F (-20° to 70°C)
Relative Humidity
30% to 95% (non-condensing)
Environmental Air
No corrosive gases permitted (Level 2 environmental pollution)*
Altitude
Up to 2000m
Agency Approvals
UL61010-2-201
CE (EN61131-2):2007*
RoHS (2011/65/EU) and amendment (EU) 2015/863
Output Specifications
Outputs per Module
4
Peak Voltage
24VDC; 264VAC
Operating Voltage Range
6–24 VDC; 6–240 VAC
Output type
4 Relays, FORM A (SPST)
AC Frequency
47–63 Hz
Maximum Output Current
10A / point
10A / common
Minimum Load Current
100mA @ 5VDC
Maximum Inrush Current
16A for 10ms
OFF to ON Response
< 15ms
ON to OFF Response
< 15ms
Status Indicators
Logic Side (4 points, red LED)
Power Indicator (green LED)
Commons
4 (1 point / common)
Bus Power Required (24V)
Max. 120mA (all points ON)
+ Keep out iron powder, moisture, oil or chemicals. Isolate from shock or vibration, direct sunlight, and from electric or ferromagnetic field.
* Meets EMC and Safety requirements. See the Declaration of Compliance for details.
WARNING
• Don’t use this equipment in a flammable or explosive environment in order to avoid accidental injury or fire.
• You should use external electromechanical devices that are independent of the PLC (Programmable Logic
Controller) system to provide protection for any part of the system; otherwise malfunction or output failures
may result in a hazardous accident.
• When using this product, connect it to the Click CPU unit.
• Please ensure to earth the Ground terminal of the Power Units for CLICK CPU (C0-00AC/01AC) to avoid
electric shock or equipment damage during a short circuit.
• Don’t operate the equipment with a nonconforming external power supply to avoid electric shock,
equipment damage or fire.
• Don’t intentionally fault wiring; this may cause equipment damage or fire.
• To avoid electric shock or malfunctions which might result in an accident, don’t touch any terminal while
the PLC power is on.
• Don’t put metals (e.g. Screwdriver) into radiator holes, drop trash, or foreign objects (e.g. wire cut-offs) into
the device, in order to avoid electric shock or equipment damage.
• If the equipment is used in a manner not specified by the manufacturer, the protection provided by the
equipment may be invalidated.
CAUTION
• Use and store the equipment in an environment described in the specifications (regarding temperature,
humidity, vibrations, shock, etc.) in order to avoid equipment damage or fire.
• Ensure all wiring has strain reliefs in order to avoid damage to insulation that might result in electric shock
or fire.
• Ensure secondary external power circuits are only live after PLC control program is started; otherwise a
malfunction or output failure may result in a hazardous accident.
• Don’t block the radiator holes. This may cause an increase of internal temperature resulting in equipment
damage or fire.
• Don’t disassemble or modify equipment so as to avoid electric shock, equipment damage, or fire.
• Cut off all phases of the external power source before maintenance work, thus avoiding electric shock or
equipment damage.
General Safety
Please follow the instructions below for personal and operational safety.
In this Insert Sheet, the safety instruction levels are classified into
“WARNING”
and
“CAUTION”
Assumes that incorrect handling may cause hazardous conditions, resulting in
severe injury or death.
Assumes that incorrect handling may cause hazardous conditions, resulting in
medium or slight injury, or may cause equipment damage.
WARNING