Automationdirect.com Productivity2000 P2-08TRS Скачать руководство пользователя страница 4

 

www.productivity2000.com  

Tech Support 770-844-4200

4

WARNING:

 

To minimize the risk of potential safety problems, you should follow all appli-

cable local and national codes that regulate the installation and operation of your equip-

ment. These codes vary from area to area and it is your responsibility to determine which 

codes should be followed, and to verify that the equipment, installation, and operation are 

in compliance with the latest revision of these codes.

Equipment damage or serious injury to personnel can result from the failure 

to follow all applicable codes and standards. We do not guarantee the products 

described in this publication are suitable for your particular application, nor do we 

assume any responsibility for your product design, installation, or operation.

If you have any questions concerning the installation or operation of this equipment, 

or if you need additional information, please call Technical Support at 770-844-4200.

This publication is based on information that was available at the time it was print-

ed. At AutomationDirect.com® we constantly strive to improve our products and services, 

so we reserve the right to make changes to the products and/or publications at any time 

without notice and without any obligation. This publication may also discuss features that 

may not be available in certain revisions of the product.

Typical Relay Life

Voltage & Type of Load

Operations at 4A Load Current

30VDC Resistive
30VDC Solenoid
120VAC Resistive
120VAC Solenoid

100,000
100,000
100,000
100,000

General Specifications

Operating Temperature

0° to 60°C (32° to 140°F),

Storage Temperature

-20° to 70°C (-4° to 158°F)

Humidity

5 to 95% (non-condensing)

Environmental Air

No corrosive gases permitted 

Vibration

IEC60068-2-6 (Test Fc)

Shock

IEC60068-2-27 (Test Ea)

Field to Logic Side Isolation

1800VAC applied for 1 second

Insulation Resistance

>10M

Ω

 @ 500VDC

Heat Dissipation 

3W

Enclosure Type

Open Equipment

Module Keying to Backplane

Electronic

Module Location

Any I/O slot in a Productivity2000 System.

Field Wiring

Use

 ZIP

Link Wiring System or removable terminal 

block (not included). See “Wiring Options” on 

page 3.

EU Directive

See the “EU Directive” topic in the Productivity 

Suite Help File. Information can also be obtained 

at: www.productivity2000.com

Connector Type (not included) 18 position removable terminal block

Agency Approvals

UL 61010-1 and UL 61010-2-201 File E139594, 

Canada and USA

CE (EN 61131-2 EMC, EN 61010-1 and EN 61010-

2-201 Safety)*

*Meets EMC and Safety requirements.  See the D.O.C. for details.

Removable Terminal Block Specifications

Part Number

P2-RTB

P2-RTB-1

Number of 

Positions 

18 Screw Terminals

18 Spring Clamp Terminals

Wire Range 

30–16 AWG (0.051–1.31  mm²) 

Solid / Stranded Conductor  

3/64 in. (1.2 mm) Insulation Maximum

1/4 in. (6–7 mm) Strip Length

28–16 AWG (0.081–1.31 mm²) 

Solid / Stranded Conductor  

3/64 in. (1.2 mm) Insulation Maximum

19/64 in. (7–8 mm) Strip Length

Conductors

“USE COPPER CONDUCTORS, 75°C” or Equivalent.

Screw Driver 

Width 

0.1 inch (2.5 mm) Maximum*

Screw Size 

M2

N/A

Screw Torque 

2.5 lb∙in (0.28 N∙m)

N/A

*Recommend Screw Driver TW-SD-MSL-1