Automationdirect.com Productivity 2000 P2-08DA-2 Скачать руководство пользователя страница 2

2

Tech Support 770-844-4200

www.productivity2000.com

General Specifications

Operating Temperature

0º to 60ºC (32º to 140ºF)

Storage Temperature

-20º to 70ºC (-4º to 158ºF)

Humidity

5 to 95% (non-condensing)

Environmental Air

No corrosive gases permitted

Vibration

IEC60068-2-6 (Test Fc)

Shock

IEC60068-2-27 (Test Ea)

Field to Logic Side Isolation

1800VAC applied for 1 second

Insulation Resistance

> 10MΩ @ 500VDC

Heat Dissipation

150mW

Enclosure Type

Open Equipment

Module Keying to Backplane Electronic
Module Location

Any I/O slot in a Productivity2000 System

Field Wiring

Use 

ZIP

Link Wiring System or removable terminal block 

(not included). See “Wiring Options” on page 5.

EU Directive

See the “EU Directive” topic in the Productivity Suite 

Help File. Information can also be obtained at: 

www.productivity2000.com

Connector Type (not included) 18-position removable terminal block
Weight

90g (3.2 oz)

Agency Approvals

UL508 File E139594, Canada & USA
CE (EN61131-2*)

Output Specifications

Output Channels

8

Output Ranges

±10VDC

Signal Resolution

16-bit

Resolution Value of LSB 

(least significant bit)

±10V = 305μV/count

 

1 LSB = 1 count

Data Range

-32768 to +32767 counts

Output Type

Voltage: 10mA max

Output Value in Fault Mode

0V

Load Impedance

≥1000Ω

Maximum Capacitive Load (voltage output)

0.01 μF

Maximum Inductive Load (Current Output) 1mH
Allowed Load Type

Grounded

Maximum Inaccuracy

0.1% of range 

(including temperature drift)

Maximum Full Scale Calibration Error

±0.025% of range maximum

Maximum Offset Calibration Error

±0.025% of range maximum

Accuracy vs. Temperature

±25ppm/°C max full scale calibration change 

(±0.0025% of range/°C)

Maximum Crosstalk at DC, 50Hz and 60Hz -96dB, 1 LSB
Linearity Error

±16 LSB maximum (±0.025% of full scale) 

Monotonic with no missing codes

Output Stability and Repeatability

±10 LSB after 10 minute warm-up (typical)

Output Ripple

0.05% of full scale

Output Setting Time

300μs max, 5μs min (full scale change)

All Channel Update Rate

1ms

Maximum Continuous Overload

Outputs current limited to 40mA typical 

Continous overloads on multiple outputs can damage 

the module.

Type of Output Protection

0.1 μF Transient Suppressor

Output Signal (power-up,-down) or at 

Power Up and Power Down

0V

External Power Supply Required

24VDC (-20% / +25%), 150mA

*Meets EMC and Safety requirements. See the D.O.C. for details.

Содержание Productivity 2000 P2-08DA-2

Страница 1: ...844 4200 This publication is based on information that was available at the time it was printed At AutomationDirect com we constantly strive to improve our products and services so we reserve the righ...

Страница 2: ...alue of LSB least significant bit 10V 305 V count 1 LSB 1 count Data Range 32768 to 32767 counts Output Type Voltage 10mA max Output Value in Fault Mode 0V Load Impedance 1000 Maximum Capacitive Load...

Страница 3: ...C User Supplied Power CH1 DAC CH2 DAC CH3 DAC CH4 DAC CH5 DAC CH6 DAC CH7 DAC CH8 DAC ISOLATED ANALOG CIRCUIT POWER ISOLATED ANALOG CIRCUIT COMMON INTERNAL MODULE CIRCUITRY COM COM COM COM COM COM vol...

Страница 4: ...n your installation for use of this powerful feature 1 Align with slot 2 rotate to seated position Module Installation WARNING Do not apply field power until the following steps are completed See hot...

Страница 5: ...tput point channel selected and to each Status Bit Item Wiring Options 1 ZIPLink Connection System Cable ZIPLink Module Complete System ZIPLink pre wired terminal block cables 0 5 m 1 6 ft cable 1 0 m...

Страница 6: ...0 0 0 0 0 1 2 3 4 5 6 6 5 7 0 0 0 0 0 0 0 Level Transmitter Tank Level 7 0 0 0 0 0 0 0 Select the minimum and maximum values of the raw input signal These values will relate to the minimum and maximu...

Страница 7: ...4 0000H 1 0 00V 2 0 00V 3 0 00V 4 0 00V 5 0 6 0 7 0 8 0 5 0000H 6 0000H 7 0000H 8 0000H 5 0 00V 6 0 00V 7 0 00V 8 0 00V MISSING EXTERNAL 24VDC MISSING CONFIG DATA End of Status Menu List SELFTEST FAI...

Страница 8: ...Tech Support 770 844 4200 www productivity2000 com Document Name Edition Revision Date P2 08DA 2 DS 1st Ed Rev B 2 7 2017 Copyright 2016 AutomationDirect com Incorporated All Rights Reserved Worldwid...

Отзывы: