2
Tech Support 770-844-4200
www.productivity2000.com
General Specifications
Operating Temperature
0º to 60ºC (32º to 140ºF)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
IEC60068-2-6 (Test Fc)
Shock
IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation
1800VAC applied for 1 second
Insulation Resistance
> 10MΩ @ 500VDC
Heat Dissipation
150mW
Enclosure Type
Open Equipment
Module Keying to Backplane Electronic
Module Location
Any I/O slot in a Productivity2000 System
Field Wiring
Use
ZIP
Link Wiring System or removable terminal block
(not included). See “Wiring Options” on page 5.
EU Directive
See the “EU Directive” topic in the Productivity Suite
Help File. Information can also be obtained at:
www.productivity2000.com
Connector Type (not included) 18-position removable terminal block
Weight
90g (3.2 oz)
Agency Approvals
UL508 File E139594, Canada & USA
CE (EN61131-2*)
Output Specifications
Output Channels
8
Output Ranges
±10VDC
Signal Resolution
16-bit
Resolution Value of LSB
(least significant bit)
±10V = 305μV/count
1 LSB = 1 count
Data Range
-32768 to +32767 counts
Output Type
Voltage: 10mA max
Output Value in Fault Mode
0V
Load Impedance
≥1000Ω
Maximum Capacitive Load (voltage output)
0.01 μF
Maximum Inductive Load (Current Output) 1mH
Allowed Load Type
Grounded
Maximum Inaccuracy
0.1% of range
(including temperature drift)
Maximum Full Scale Calibration Error
±0.025% of range maximum
Maximum Offset Calibration Error
±0.025% of range maximum
Accuracy vs. Temperature
±25ppm/°C max full scale calibration change
(±0.0025% of range/°C)
Maximum Crosstalk at DC, 50Hz and 60Hz -96dB, 1 LSB
Linearity Error
±16 LSB maximum (±0.025% of full scale)
Monotonic with no missing codes
Output Stability and Repeatability
±10 LSB after 10 minute warm-up (typical)
Output Ripple
0.05% of full scale
Output Setting Time
300μs max, 5μs min (full scale change)
All Channel Update Rate
1ms
Maximum Continuous Overload
Outputs current limited to 40mA typical
Continous overloads on multiple outputs can damage
the module.
Type of Output Protection
0.1 μF Transient Suppressor
Output Signal (power-up,-down) or at
Power Up and Power Down
0V
External Power Supply Required
24VDC (-20% / +25%), 150mA
*Meets EMC and Safety requirements. See the D.O.C. for details.