Automationdirect.com Productivity 2000 P2-08DA-1 Скачать руководство пользователя страница 2

2

Tech Support 770-844-4200

www.productivity2000.com

General Specifications

Operating Temperature

0º to 60ºC (32º to 140ºF)

Storage Temperature

-20º to 70ºC (-4º to 158ºF)

Humidity

5 to 95% (non-condensing)

Environmental Air

No corrosive gases permitted

Vibration

IEC60068-2-6 (Test Fc)

Shock

IEC60068-2-27 (Test Ea)

Field to Logic Side Isolation

1800VAC applied for 1 second

Insulation Resistance

> 10MΩ @ 500VDC

Heat Dissipation

700mW

Enclosure Type

Open Equipment

Agency Approvals

UL508 File E139594, Canada & USA
CE (EN61131-2*)

Module Keying to Backplane Electronic
Module Location

Any I/O slot in a Productivity2000 System

Field Wiring

Use ZIPLink Wiring System or removable terminal block 

(not included). See “Wiring Options” on page 5.

EU Directive

See the “EU Directive” topic in the Productivity2000 

Help File. Information can also be obtained at: 

www.productivity2000.com

Connector Type (not included) 18-position removable terminal block
Weight

90g (3.2 oz)

Output Specifications

Output Channels (Commons)

8

Module Signal Output Range

4-20 mA

Output Signal Resolution

16-bit

Resolution Value of LSB 

(least significant bit)

4-20 mA = 0.244 μA/count

 

1 LSB = 1 count

Data Range

0 to 65535 counts

Output Type (sourcing)

Current: 20mA max

Output Value in Fault Mode

Near 0mA

Load Impedance 

(Minimum External Power Supply)

0 - 570Ω (19.2 VDC)

 

0 - 690Ω (21.6 VDC)

 

0 - 810Ω (24VDC)

 

0 - 930Ω (26.4 VDC)

 

0 - 1100Ω (30VDC)

 

Minimum Load 0 - 125Ω @ 0 - 45°C

 

                      250 - 715Ω @ 0 - 60°C

Maximum Inductive Load

1mH

Allowed Load Type

Grounded

Maximum Inaccuracy

0.1% of range (Counts TBD) 

(including temperature drift)

Maximum Full Scale Calibration 

Error (not including offset error)

±0.025% of range maximum

Maximum Offset Calibration Error

±0.025% of range maximum

Accuracy vs. Temperature

±25ppm/°C max full scale calibration change

 

(±0.0025% of range/°C)

Max Crosstalk

-96dB, 1 LSB

Linearity Error (End to End)

±16 LSB maximum (±0.025% of full scale) 

Monotonic with no missing codes

Output Stability and Repeatability

±10 count after 10 minute warm-up (typical)

Output Ripple

0.05% of full scale

Output Setting Time

300μs max, 5μs min (full scale change)

All Channel Update Rate

600μs

Maximum Continuous Overload

Outputs open circuit protected

Type of Output Protection

Electronically current limited to 20mA or less

Output Signal (power-up,-down)

4mA

External DC Power Required

24VDC @ 220mA (Loop Power Included)

*Meets EMC and Safety requirements. See the D.O.C. for details.

Содержание Productivity 2000 P2-08DA-1

Страница 1: ...00 This publication is based on information that was available at the time it was printed At AutomationDirect com we constantly strive to improve our products and services so we reserve the right to make changes to the products and or publications at any time without notice and without any obligation This publication may also discuss features that may not be available in certain revisions of the p...

Страница 2: ...least significant bit 4 20 mA 0 244 μA count 1 LSB 1 count Data Range 0 to 65535 counts Output Type sourcing Current 20mA max Output Value in Fault Mode Near 0mA Load Impedance Minimum External Power Supply 0 570Ω 19 2 VDC 0 690Ω 21 6 VDC 0 810Ω 24VDC 0 930Ω 26 4 VDC 0 1100Ω 30VDC Minimum Load 0 125Ω 0 45 C 250 715Ω 0 60 C Maximum Inductive Load 1mH Allowed Load Type Grounded Maximum Inaccuracy 0 ...

Страница 3: ...0H 3 0000H 4 0000H 1 0 00 2 0 00 3 0 00 4 0 00 5 0 6 0 7 0 8 0 5 0000H 6 0000H 7 0000H 8 0000H 5 0 00 6 0 00 7 0 00 8 0 00 MISSING EXTERNAL 24VDC MISSING CONFIG DATA End of Status Menu List SELFTEST FAIL REPLACE MODULE End of Status Menu List DISPLAY UNITS DECIMAL COUNTS DISPLAY UNITS HEX COUNTS DISPLAY STATUS INFO DISPLAY SETUP INFO DISPLAY UNITS MILLIAMP 4 20mA PASSED SELF TEST P2 08DA1 Fw Rev 1...

Страница 4: ... 5 6 6 5 7 0 0 0 0 0 0 0 Level Transmitter Tank Level 7 0 0 0 0 0 0 0 Select the minimum and maximum values of the raw input signal These values will relate to the minimum and maximum scaled values 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 The Scale Linear function can be used to Convert analog field input signals from the range which is native to the analog input module to an application specific range Make ...

Страница 5: ...CH3 ADC CH4 ADC CH5 ADC CH6 ADC CH7 ADC CH8 ADC ISOLATED ANALOG CIRCUIT POWER ISOLATED ANALOG CIRCUIT COMMON INTERNAL MODULE CIRCUITRY COM COM COM COM COM COM 4 20 mA current sourcing 4 20 mA current sourcing 4 20 mA current sourcing 4 20 mA current sourcing 4 20 mA current sourcing 4 20 mA current sourcing 4 20 mA current sourcing 4 20 mA current sourcing 1 2 3 4 5 6 7 8 9 10 11 12 18 13 14 15 16...

Страница 6: ...n your installation for use of this powerful feature 1 Align with slot 2 rotate to seated position Module Installation WARNING Do not apply field power until the following steps are completed See hot swapping procedure for exceptions WIRESTRIP LENGTH WIRESTRIP LENGTH Step One Align module catch with base slot and rotate module into connector Locked Unlocked Step Two Pull top locking tab toward mod...

Страница 7: ...nd to each Status Bit Item A Stop Mode Value may also be assigned Wiring Options 1 ZIPLink Connection System Cable ZIPLink Module Complete System ZIPLink pre wired terminal block cables 0 5 m 1 6 ft cable 1 0 m 3 3 ft cable 2 0 m 6 6 ft cable ZIPLink Modules Feed through ZL P2 CBL18 ZL P2 CBL18 1 ZL P2 CBL18 2 ZL RTB20 2Terminal Block with pigtail cable 1 0 m 3 3 ft cable 2 0 m 6 6 ft cable ZL P2 ...

Страница 8: ...8 Tech Support 770 844 4200 www productivity2000 com Document Name Edition Revision Date P2 08DA 1 DS 1st Ed 3 9 2015 Copyright 2015 AutomationDirect com Incorporated All Rights Reserved Worldwide ...

Отзывы: