![Automationdirect.com Productivity 2000 P2-04AD Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/automationdirect-com/productivity-2000-p2-04ad/productivity-2000-p2-04ad_manual_3021967005.webp)
3
Sales 800-633-0405
www.productivity2000.com
Voltage Input Circuits
Current Sinking Input Circuits
An Edison S500-32-R 0.032A fast-acting
fuse is recommended for all current loops.
COM
V+
4-Wire Voltage
Transmitter
4-Wire Transmitter
Optional Transmitter
Power Supply
AC or DC
- +
24 VDC User
Supplied Power
+
3-Wire Voltage
Transmitter
V+
COM
3-Wire Transmitter
.032A
2-Wire 4-20 mA
Transmitter
fuse
fuse
.032A
fuse
+
.032A
- +
- +
V+
I
+
COM
V+
I
+
3-Wire Current
Transmitter
4-Wire 4-20 mA
Transmitter
2-Wire Transmitter
3-Wire Transmitter
4-Wire Transmitter
Power
Supply
24VDC User
Supplied Power
+
–
+
–
+
–
User Supplied
Transmitter Power
AC or DC
V+
I
+
COM
COM
V1+
I1+
V2+
I2+
V3+
I3+
I4+
V4+
COM
COM
24VDC-
24VDC+
- +
24 VDC User
Supplied Power
CH1 ADC
CH2 ADC
CH3 ADC
CH4 ADC
ISOLATED
ANALOG
CIRCUIT
POWER
ISOLATED ANALOG
CIRCUIT COMMON
INTERNAL
MODULE CIRCUITRY
COM
COM
123456789
10
11
12
18
13
14
15
16
17
Wiring Diagram
Schematic
Notes
:
1. Shield connected to signal source
common.
2. If current is chosen, I+ must be
jumped to V+. For example when
using 4-20 mA source for Input 3,
I3+ must be jumped to V3+.