Output Specifications

Outputs per Module

2

Output Range

0–10 VDC

Signal Resolution

12-bit

Resolution Value of LSB

(least significant bit)

0–10 VDC = 2.44 mV / count

1 LSB = 1 count

Data Range

0–4095 counts

Output Type

Voltage @ 10mA

Output Value in Fault Mode

0V

Load Impedance

1000

Maximum Capacitive Load

0.01 µF

Allowed Load Type

Grounded

Maximum Inaccuracy

0.5% of range

Full Scale Calibration Error

±0.2% of range

Offset Calibration Error

±0.2% of range

Accuracy vs. Temperature

±75 PPM / °C maximum full-scale 

calibration change (±0.0025% of range / °C)

Max Crosstalk at DC, 50/60Hz

-72dB, 1 LSB

Linearity Error (End to End)

±4 LSB max., (±0.1% of full scale)

Monotonic with no missing codes

Output Stability and 

Repeatability

±2% LSB after 10 min. warm up (typical)

Output Ripple

±0.2% of full scale

Output Settling Time

0.3 ms max., 5µs min. (full scale range)

All Channel Update Rate

4ms

Maximum Continuous Overload

Outputs current limited to 40mA typical

Continuous overloads on multiple outputs 

can damage the module.

Type of Output Protection

0.1 µs Transient Suppressor

Output Signal at Power Up and 

Power Down

0V

Input Specifications

Inputs per Module

4

Input Range

0–10 VDC

Signal Resolution

13-bit

Resolution Value of LSB

(least significant bit)

0–10 VDC = 1.22 mV per count

(1LSB = 1 count)

Data Range

0–8191 counts

Input Type

Single-ended (1 common)

Maximum Continuous Overload

±100VDC

Input Impedance

200k

 

Hardware Filter Characteristics

Low Pass, -3dB @ 100Hz

Sample Duration Time

4ms per channel
(does not include ladder scan time)

All Channel Update Rate

20ms

Open Circuit Detection Time

Zero reading within 100ms

Conversion Method

Successive approximation

Accuracy vs. Temperature

±75PPM / ºC maximum

Maximum Inaccuracy

0.5% of range

(including temperature drift)

Linearity Error

±0.036% of range

Monotonic with no missing codes

Input Stability and Repeatability

±0.024% of range

Full Scale Calibration Error

(including offset)

±0.097% of range

Offset Calibration Error

±0.097% of range

Max Crosstalk at DC, 50Hz and 

60Hz

±0.049% of range

External Power Supply Required

24VDC (-20% / + 25%), 100mA

Содержание Productivity 1000 P1-4ADL2DAL-2

Страница 1: ...page 5 General Specifications Operating Temperature 0º to 60ºC 32º to 140ºF Storage Temperature 20º to 70ºC 4º to 158ºF Humidity 5 to 95 non condensing Environmental Air No corrosive gases permitted Vibration IEC60068 2 6 Test Fc Shock IEC60068 2 27 Test Ea Field to Logic Side Isolation 1800VAC applied for 1 second Insulation Resistance 10M 500VDC Heat Dissipation 1950mW Enclosure Type Open Equipm...

Страница 2: ...urrent limited to 40mA typical Continuous overloads on multiple outputs can damage the module Type of Output Protection 0 1 µs Transient Suppressor Output Signal at Power Up and Power Down 0V Input Specifications Inputs per Module 4 Input Range 0 10 VDC Signal Resolution 13 bit Resolution Value of LSB least significant bit 0 10 VDC 1 22 mV per count 1LSB 1 count Data Range 0 8191 counts Input Type...

Страница 3: ... COM Voltage Source Voltage Source 24VDC User Supplied Power ISOLATED ANALOG CIRCUIT POWER P1 04ADL2DAL 2 Wiring Diagram V COM 4 Wire Voltage Transmitter 4 Wire Transmitter Voltage Input Circuits Transmitter Power Supply AC or DC 24 VDC User Supplied Power 3 Wire Voltage Transmitter V COM 3 Wire Transmitter Load Power Supply 0 10 VDC Load V COM Voltage Output Circuits Notes for maximum accuracy 1 ...

Страница 4: ...cked position and then pull modules apart Step Two Attach field wiring using the removable terminal block or ZIPLink wiring system LOCK UNLOCK WIRE STRIP LENGTH MIN MAX P1 08TD1 Check all latches are secure after modules are connected QR Code Use any QR Code reader application to display the module s product insert P1 08TD1 P1 08TD1 1 2 3 4 5 6 7 8 9 10 L L L L L L L L 24V 1 2 3 4 0V 5 6 7 8 12 24...

Страница 5: ...inal Block only P1 10RTB Quantity 1 4 Spring Clamp Terminal Block only P1 10RTB 1 Quantity 1 5 Accessories ZL RTB COM TW SD SL 1 TW SD MSL 1 ZL RTB20 ZL RTB20 1 2 1 Cable ZIPLink Module Complete System 2 ZL RTB COM provides a common connection point for power or ground Module Configuration Using the Hardware Configuration tool in the Productivity Suite programming software drag and drop the P1 4AD...

Страница 6: ... raw input signals to engineering units for use in the program or convert engineering units to output signals for control purposes max min min max 1045 0 8191 220 Level Transmitter Tank Level Non Linear Scaling Non Linear Scalin 0 5 1 1 55 2 25 3 4 55 6 75 7 0 0 0 0 0 0 0 0 1 2 3 4 5 6 6 5 7 0 0 0 0 0 0 0 Level Transmitter Tank Level 7 0 0 0 0 0 0 0 Select the minimum and maximum values of the raw...

Страница 7: ...7 Sales 800 633 0405 www productivity1000 com ...

Страница 8: ... determine which codes should be followed and to verify that the equipment installation and operation are in compliance with the latest revision of these codes Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and standards We do not guarantee the products described in this publication are suitable for your particular application nor do we a...

Отзывы: