Automationdirect.com Productivity 1000 P1-4ADL2DAL-2 Скачать руководство пользователя страница 1

1

Sales 800-633-0405

www.productivity1000.com

24V

V2+
V3+
V4+

0V

V1+
V2+

COM
COM

V1+

P1-4ADL2DAL-2

0-10VDC IN

0-10VDC OUT

INPUTS

OUT

1000

P1-4ADL2DAL-2 Analog Input/

Output

The P1-4ADL2DAL-2 Voltage Analog Input/Output 

Module provides four 13 bit input channels at 0-10 

VDC and two 12 bit output channels at 0-10VDC for 

use with the Productivity1000 system.

General Specifications  . . . . . . . . . . . . . . . . . . . . . .  1

Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . .  2

Output Specifications  . . . . . . . . . . . . . . . . . . . . . . .  2

Wiring Diagram and Schematic . . . . . . . . . . . . . . . .  3

Module Installation Procedure . . . . . . . . . . . . . . . . .  4

QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4

Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5

Module Configuration  . . . . . . . . . . . . . . . . . . . . . . .  5

Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  6

Non-Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . .  6

Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

Terminal Block Specifications . . . . . . . . . . . . . . . . .  8

Warranty: Thirty-day money-back guarantee. Two-year limited 

replacement. (See www.productivity1000.com for details).

Terminal Block sold separately, (see wiring options on page 5).

General Specifications

Operating Temperature

0º to 60ºC (32º to 140ºF)

Storage Temperature

-20º to 70ºC (-4º to 158ºF)

Humidity

5 to 95% (non-condensing)

Environmental Air

No corrosive gases permitted

Vibration

IEC60068-2-6 (Test Fc)

Shock

IEC60068-2-27 (Test Ea)

Field to Logic Side 

Isolation

1800VAC applied for 1 second

Insulation Resistance

> 10M

 @ 500VDC

Heat Dissipation

1950mW

Enclosure Type

Open Equipment

Module Location

Any I/O position in a Productivity1000 System

Field Wiring

Removable terminal block (sold separately). Use 

ZIP

Link Wiring System optional See “Wiring 

Options” on page 5.

EU Directive

See the “EU Directive” topic in the Productivity 

Suite Help File. Information can also be obtained at:

www.productivity1000.com

Terminal Type 

(sold separately) 

10-position Removable Terminal Block

Weight

60g (2.1 oz)

Agency Approvals

UL 61010-1 and UL 61010-2-201 File E139594, 

Canada and USA
CE (EN 61131-2 EMC, EN 61010-1 and EN 61010-

2-201 Safety)*

*See CE Declaration of Conformance for details.

Содержание Productivity 1000 P1-4ADL2DAL-2

Страница 1: ...page 5 General Specifications Operating Temperature 0º to 60ºC 32º to 140ºF Storage Temperature 20º to 70ºC 4º to 158ºF Humidity 5 to 95 non condensing Environmental Air No corrosive gases permitted Vibration IEC60068 2 6 Test Fc Shock IEC60068 2 27 Test Ea Field to Logic Side Isolation 1800VAC applied for 1 second Insulation Resistance 10M 500VDC Heat Dissipation 1950mW Enclosure Type Open Equipm...

Страница 2: ...urrent limited to 40mA typical Continuous overloads on multiple outputs can damage the module Type of Output Protection 0 1 µs Transient Suppressor Output Signal at Power Up and Power Down 0V Input Specifications Inputs per Module 4 Input Range 0 10 VDC Signal Resolution 13 bit Resolution Value of LSB least significant bit 0 10 VDC 1 22 mV per count 1LSB 1 count Data Range 0 8191 counts Input Type...

Страница 3: ... COM Voltage Source Voltage Source 24VDC User Supplied Power ISOLATED ANALOG CIRCUIT POWER P1 04ADL2DAL 2 Wiring Diagram V COM 4 Wire Voltage Transmitter 4 Wire Transmitter Voltage Input Circuits Transmitter Power Supply AC or DC 24 VDC User Supplied Power 3 Wire Voltage Transmitter V COM 3 Wire Transmitter Load Power Supply 0 10 VDC Load V COM Voltage Output Circuits Notes for maximum accuracy 1 ...

Страница 4: ...cked position and then pull modules apart Step Two Attach field wiring using the removable terminal block or ZIPLink wiring system LOCK UNLOCK WIRE STRIP LENGTH MIN MAX P1 08TD1 Check all latches are secure after modules are connected QR Code Use any QR Code reader application to display the module s product insert P1 08TD1 P1 08TD1 1 2 3 4 5 6 7 8 9 10 L L L L L L L L 24V 1 2 3 4 0V 5 6 7 8 12 24...

Страница 5: ...inal Block only P1 10RTB Quantity 1 4 Spring Clamp Terminal Block only P1 10RTB 1 Quantity 1 5 Accessories ZL RTB COM TW SD SL 1 TW SD MSL 1 ZL RTB20 ZL RTB20 1 2 1 Cable ZIPLink Module Complete System 2 ZL RTB COM provides a common connection point for power or ground Module Configuration Using the Hardware Configuration tool in the Productivity Suite programming software drag and drop the P1 4AD...

Страница 6: ... raw input signals to engineering units for use in the program or convert engineering units to output signals for control purposes max min min max 1045 0 8191 220 Level Transmitter Tank Level Non Linear Scaling Non Linear Scalin 0 5 1 1 55 2 25 3 4 55 6 75 7 0 0 0 0 0 0 0 0 1 2 3 4 5 6 6 5 7 0 0 0 0 0 0 0 Level Transmitter Tank Level 7 0 0 0 0 0 0 0 Select the minimum and maximum values of the raw...

Страница 7: ...7 Sales 800 633 0405 www productivity1000 com ...

Страница 8: ... determine which codes should be followed and to verify that the equipment installation and operation are in compliance with the latest revision of these codes Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and standards We do not guarantee the products described in this publication are suitable for your particular application nor do we a...

Отзывы: