background image

2

Tech Support 770-844-4200

www.productivity1000.com

Output Specifications

Outputs per Module

2

Output Range

4–20 mA

Signal Resolution

12-bit

Resolution Value of LSB

(least significant bit)

4–20 mA = 3.9 µA / count

1 LSB = 1 count

Data Range

0–4095 counts

Output Type

Current sourcing at 20mA max

Output Value in Fault Mode

Less than 4mA

Load Impedance

0–570 

 (19.2 VDC), 0–690 

 (21.6 VDC), 

0–810 

 (24.0 VDC), 0–930 

 (26.4 VDC),

0–1100 

 (30.0 VDC)

Minimum Load: 0

 @ 0–45 °C

125

 @ 45–60 °C ambient temperature

Maximum Inductive Load

1mH

Allowed Load Type

Grounded

Maximum Inaccuracy

1% of range

Full Scale Calibration Error

±0.2% of range minimum

Offset Calibration Error

±0.2% of range maximum

Accuracy vs. Temperature

±75 PPM / °C maximum full-scale 

calibration change (±0.005% of range / °C)

Max Crosstalk at DC, 50Hz and 

60Hz

-72dB, 1 LSB

Linearity Error (End to End)

±4 counts max., (±0.1% of full scale)

Output Stability and 

Repeatability

±2% counts after 10 min. warm up (typical)

Output Ripple

±0.2% of full scale

Output Settling Time

0.3 ms max., 5µs min. (full scale range)

All Channel Update Rate

4ms (max)

Maximum Continuous Overload

Outputs open circuit protected

Type of Output Protection

Electronically current limited to 20mA or less

Output Signal at Power Up and 

Power Down

4mA

Input Specifications

Inputs per Module

4

Module Signal Input Range

0–20 mA

Signal Resolution

13-bit

Resolution Value of LSB

(least significant bit)

0–20 mA = 2.44 µA per count

(1LSB = 1 count)

Data Range

0–8191 counts

Input Type

Sinking, Single-ended (1 common)

Maximum Continuous Overload

±31mA

Input Impedance

247

, ±0.5%, 1/4W Current Input

Filter Characteristics

Low Pass, -3dB @ 120Hz

Sample Duration Time

4ms per channel
(does not include ladder scan time)

All Channel Update Rate

20ms

Open Circuit Detection Time

Zero reading within 100ms

Conversion Method

Successive approximation

Accuracy vs. Temperature

±75PPM / ºC maximum

Maximum Inaccuracy

0.5% of range

(including temperature drift)

Linearity Error (end to end)

±0.037% of range

Monotonic with no missing codes

Input Stability and Repeatability

±0.024% of range (after 10 minute warm-up)

Maximum Full Scale Calibration 

Error

±0.098% of range

Offset Calibration Error

±0.098% of range

Maximum Crosstalk at DC, 

50Hz and 60Hz

±0.049% of range

Recommended Fuse (external)

Edison S500-32-R, 0.032 A fuse

External Power Supply Required

24VDC (-20% / + 25%), 140mA (Loop Power 

Included)

Содержание Productivity 1000 P1-4ADL2DAL-1

Страница 1: ...wiring options on page 5 General Specifications Operating Temperature 0º to 60ºC 32º to 140ºF Storage Temperature 20º to 70ºC 4º to 158ºF Humidity 5 to 95 non condensing Environmental Air No corrosive gases permitted Vibration IEC60068 2 6 Test Fc Shock IEC60068 2 27 Test Ea Field to Logic Side Isolation 1800VAC applied for 1 second Insulation Resistance 10M 500VDC Heat Dissipation 2470mW Enclosur...

Страница 2: ...ontinuous Overload Outputs open circuit protected Type of Output Protection Electronically current limited to 20mA or less Output Signal at Power Up and Power Down 4mA Input Specifications Inputs per Module 4 Module Signal Input Range 0 20 mA Signal Resolution 13 bit Resolution Value of LSB least significant bit 0 20 mA 2 44 µA per count 1LSB 1 count Data Range 0 8191 counts Input Type Sinking Sin...

Страница 3: ...CUIT POWER P1 4ADL2DAL 1 Wiring Diagram Current Input Circuits Current Output Circuits COM 3 Wire Current Transmitter 032A 2 Wire 4 20 mA Transmitter fuse 2 Wire Transmitter 3 Wire Transmitter 24VDC User Supplied Power 032A fuse Note Do not connect both ends of shield 4 Wire 4 20 mA Transmitter 4 Wire Transmitter User Supplied Transmitter Power AC or DC 4 20mA Load Note Shield is connected to comm...

Страница 4: ...cked position and then pull modules apart Step Two Attach field wiring using the removable terminal block or ZIPLink wiring system LOCK UNLOCK WIRE STRIP LENGTH MIN MAX P1 08TD1 Check all latches are secure after modules are connected QR Code Use any QR Code reader application to display the module s product insert P1 08TD1 P1 08TD1 1 2 3 4 5 6 7 8 9 10 L L L L L L L L 24V 1 2 3 4 0V 5 6 7 8 12 24...

Страница 5: ...nly P1 10RTB Quantity 1 4 Spring Clamp Terminal Block only P1 10RTB 1 Quantity 1 5 Accessories ZL RTB COM TW SD SL 1 TW SD MSL 2 ZL RTB20 ZL RTB20 1 2 1 Cable ZIPLink Module Complete System 2 ZL RTB COM provides a common connection point for power or ground Complete System ti i t f Module Configuration Using the Hardware Configuration tool in the Productivity Suite programming software drag and dr...

Страница 6: ... raw input signals to engineering units for use in the program or convert engineering units to output signals for control purposes max min min max 1045 0 8191 220 Level Transmitter Tank Level Non Linear Scaling Non Linear Scalin 0 5 1 1 55 2 25 3 4 55 6 75 7 0 0 0 0 0 0 0 0 1 2 3 4 5 6 6 5 7 0 0 0 0 0 0 0 Level Transmitter Tank Level 7 0 0 0 0 0 0 0 Select the minimum and maximum values of the raw...

Страница 7: ...7 Sales 800 633 0405 www productivity1000 com ...

Страница 8: ... determine which codes should be followed and to verify that the equipment installation and operation are in compliance with the latest revision of these codes Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and standards We do not guarantee the products described in this publication are suitable for your particular application nor do we a...

Отзывы: