background image

1

Sales 800-633-0405

www.productivity1000.com

24V

V2+
V3+
V4+

0V

COM
COM
COM
COM

V1+

P1-04DAL-2

0-10VDC OUT

ANALOG

1000

P1-04DAL-2 Analog Output

The P1-04DAL-2 Low Resolution Voltage Analog 

Output Module provides four outputs for converting 

digital values from 0–4095 (12-bit) to 0–10 VDC 

analog signals for use with the Productivity1000 

system.

Output Specifications  . . . . . . . . . . . . . . . . . . . . . . .  1

General Specifications  . . . . . . . . . . . . . . . . . . . . . .  2

Removable Terminal Block Specifications. . . . . . . .  2

Wiring Diagram and Schematic . . . . . . . . . . . . . . . .  3

Module Installation Procedure . . . . . . . . . . . . . . . . .  4

QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4

Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5

Module Configuration  . . . . . . . . . . . . . . . . . . . . . . .  5

Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  6

Non-Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . .  6

Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

Warranty: Thirty-day money-back guarantee. Two-year limited 

replacement (See www.productivity1000.com for details).

Terminal Block sold separately, (see wiring options on page 5).

Output Specifications

Output Channels

4

Module Signal Output Range

0–10 V

Signal Resolution

12-bit

Resolution Value of LSB

(least significant bit)

0–10 V = 2.44 mV / count

1 LSB = 1 count

Data Range

0–4095 counts

Output Type

Voltage sourcing at 10mA

Output Value in Fault Mode

0V

Load Impedance

1000

Maximum Capacitive Load

0.01 µF

Allowed Load Type

Grounded

Maximum Inaccuracy

0.5% of range

Full Scale Calibration Error

±0.2% of range

Offset Calibration Error

±0.2% of range

Accuracy vs. Temperature

±75 PPM / °C maximum full-scale 

calibration change (±0.0025% of range / °C)

Max Crosstalk at DC, 50/60Hz

-72dB, 1 LSB

Linearity Error (End to End)

±4 LSB max., (±0.1% of full scale)

Monotonic with no missing codes

Output Stability and 

Repeatability

±2% LSB after 10 min. warm up (typical)

Output Ripple

±0.2% of full scale

Output Settling Time

0.3 ms max., 5µs min. (full scale range)

All Channel Update Rate

2ms

Maximum Continuous Overload

Outputs current limited to 40mA typical

Continuous overloads on multiple outputs 

can damage the module.

Type of Output Protection

0.1 µ Transient Suppressor

Output Signal at Power Up and 

Power Down

0V

External Power Supply Required

24VDC (-20% / +25%), 100mA

Содержание Productivity 1000 P1-04DAL-2

Страница 1: ...ion 12 bit Resolution Value of LSB least significant bit 0 10 V 2 44 mV count 1 LSB 1 count Data Range 0 4095 counts Output Type Voltage sourcing at 10mA Output Value in Fault Mode 0V Load Impedance 1...

Страница 2: ...rature 20 to 70 C 4 to 158 F Humidity 5 to 95 non condensing Environmental Air No corrosive gases permitted Vibration IEC60068 2 6 Test Fc Shock IEC60068 2 27 Test Ea Field to Logic Side Isolation 180...

Страница 3: ...CH1 DAC CH2 DAC CH3 DAC CH4 DAC CIRCUIT POWER INTERNAL MODULE CIRCUITRY 24V 10 1 2 3 4 5 6 7 8 9 ISOLATED ANALOG ISOLATED ANALOG CIRCUIT COMMON voltage source voltage source voltage source voltage sou...

Страница 4: ...ked position and then pull modules apart Step Two Attach field wiring using the removable terminal block or ZIPLink wiring system WIRE STRIP LENGTH MIN MAX P1 08TD1 UNLOCK LOCK Check all latches are s...

Страница 5: ...ZL RTB20 1 2Terminal Block with pigtail cable 1 0 m 3 3 ft cable 2 0 m 6 6 ft cable ZL P1 CBL10 1P ZL P1 CBL10 2P 3 Screw Terminal Block only P1 10RTB Quantity 1 4Spring Clamp Terminal Block only P1 1...

Страница 6: ...max The Scale Linear function can be used to Convert an application specific range to range which is native to the analog output module Make other linear conversions in ranges appropriate to the appl...

Страница 7: ...7 Sales 800 633 0405 www productivity1000 com...

Страница 8: ...e failure to follow all applicable codes and standards We do not guarantee the products described in this publication are suitable for your particular application nor do we assume any responsibility f...

Отзывы: