9.2 Configuration of the basic settings
9.2.1 Selection of the display unit
Set [Uni] before the values for the parameters [SPx], [nSPx], [FSPx],
[ASP], [AEP] are defined�
In case of subsequent changes of the display unit rounding errors during
internal conversion to other units may falsify the set values�
►
Change to [EF]�
►
Select [Uni] and set the unit of measurement�
Selection of the unit of measurement: [mm], [m], [inch]
►
Confirm with [MODE/ENTER]�
> The selected unit is indicated by a green LED on the display�
9.2.2 Setting the display
►
Change to [EF]�
►
Select [diS] and make settings�
7 settings can be selected:
•
[d1] = update of the measured values every 50 ms�
•
[d2] = update of the measured values every 200 ms�
•
[d3] = update of the measured values every 600 ms�
•
[rd1], [rd2], [rd3] = display like [d1], [d2], [d3] but rotated by 180°�
The update of the measured value only refers to the display� It has no
effect on the outputs�
•
[OFF] = the measured value display is deactivated in the Run mode�
When one button is pressed the current measured value is displayed
for 15 s�
►
Confirm with [MODE/ENTER]�
The LEDs remain active even if the display is deactivated�
9.2.3 Configure OUT1
►
Select [OU1] and set the switching functions�
Switching functions:
•
[Hno] = hysteresis function / normally open
•
[Hnc] = hysteresis function / normally closed
•
[Fno] = window function / normally open
•
[Fnc] = window function / normally closed
►
Confirm with [MODE/ENTER]�