background image

ADC MDM-TEL

 

Modem

Document

MDM-TEL Application Note.doc

Page 13 of 16

Return to top

13

Last reviewed: 03/07/2002

Local

Modem

IBM Compatible

Remote
Modem

PLC

Troubleshooting a Modem Connection

:

1.  Remote modem is not answering:

Try to isolate the problem to the remote side or local.  If you have a known good working
PLC/Modem setup, try dialing into it.  If you are successful at this, then you know the problem
is on the local side.

Make sure that the remote modem configuration has auto answer turned on.  You also need
to have a number of rings selected.

Try removing the cable between the remote modem and PLC.  If it answers, you know the
problem is in the remote cable connection.  Consult the diagrams towards the beginning of
this document for the correct pinout.  If possible, try using the programming cables we
provide as well as the null modem adapter that comes with the modem.

Try a different cable on the local modem.

Verify settings for the modem driver on the PC.  Consult the appropriate section of this
document for setting up this driver in Windows.

2.  Remote modem answers but the PLC doesn’t connect:

If possible, try to connect to the PLC directly from the serial port of a PC.

Verify that the PLC port is Ok.

Phone line problem.  Repeat connection attempt on another phone line if possible.

The PLC port has not been configured or improperly configured.  Consult the section in this
document that describes the port configuration.

Verify the remote modem configuration.  Follow the steps in this document again and re-
download the configuration to verify the correct setup.

The modem driver is not configured properly.  Consult the steps in this document to verify
modem driver setup.

The wrong modem may be answering.  This can happen on a phone network in some
facilities.  Have someone power off the remote modem and attempt to connect again.  If there
is an answer, there is a problem with the phone network, which needs to be corrected.

The remote modem is not on a dedicated line.  PBX (Private Branch Exchange) lines will
cause problems with many different software packages.

3.  The PLC connects but the connection is lost intermittently when program status is turned on

or during a program transfer.

Poor phone line quality.  Sometimes there is no way to resolve this.  Be sure that the phone
line on the remote end is not run around devices that cause high RF signals, such as
frequency drives.  You can often tell the quality of a phone line by actually calling someone
and talking on this line.  If it is very noisy, then it is most likely that you will have problems
using it for PLC connectivity.

Poor cable quality between PLC and modem or PC and modem if using external modem.  If
the cable between the modem and PLC is routed around devices that generate high RF
signals, you will most likely have problems with your connection.  They will need to be
isolated.  Distance between the PLC and the modem could also be a factor.  50 ft. is the
maximum length for RS232.  You may achieve this distance depending upon your
environment (high RF signal environment).

Raise the timeout and retries in the link editor in DirectSOFT32:

If you are still experiencing problems after following these steps, contact AutomationDirect
tech support at (770) 844-4200.

Содержание MDM-TEL

Страница 1: ...bleshooting a Modem Connection 3 Connecting two Direct Logic PLCs together through the MDM TEL modem 4 PLC Network Instructions It is our suggestion that you carefully follow this document first in at...

Страница 2: ...2 w D2 DSCBL w null modem null modem Windows Driver Configuration PLC Port 2 MODEM 15pin SVGA DB9 Male Male TXD 2 3 TXD RXD 3 2 RXD GND 7 5 GND RTS 5 7 RTS CTS 4 8 CTS PLC Port 2 MODEM RJ 12 DB9 Male...

Страница 3: ...IBM Compatible Remote Modem PLC Installing the Windows Modem Driver Install the standard 28800 baud modem driver in Windows to use with the ADC modem Here is the procedure for installing this driver 1...

Страница 4: ...L Application Note doc Page 4 of 16 Return to top 4 Last reviewed 03 07 2002 Local Modem IBM Compatible Remote Modem PLC 3 Choose 9600 as the Maximum Port Speed 4 Click on the Advanced Tab and then cl...

Страница 5: ...em IBM Compatible Remote Modem PLC 5 Make Port speed 9600 and choose None for Flow control 5 Click on Advanced and choose 8 Data bits None Parity and 1 Stop Bits Click OK until all dialog boxes are cl...

Страница 6: ...m Use the 9 pin serial cable to connect between the serial port of your PC and the ADC modem in order to download the configuration If using an ADC modem on both local and remote CPU s which is the be...

Страница 7: ...Last reviewed 03 07 2002 Local Modem IBM Compatible Remote Modem PLC 3 Set this page up as shown below then click on the Next button 4 Set this page up as shown below Be sure to disable Error Correct...

Страница 8: ...Modem Document MDM TEL Application Note doc Page 8 of 16 Return to top 8 Last reviewed 03 07 2002 Local Modem IBM Compatible Remote Modem PLC 5 Click on Write Configuration to the Modem to download th...

Страница 9: ...onfigured through DirectSOFT You must configure the DIP switches and selector switches for the proper setup on these modules Again follow the same parameters guidelines from this example and refer to...

Страница 10: ...L Application Note doc Page 10 of 16 Return to top 10 Last reviewed 03 07 2002 Local Modem IBM Compatible Remote Modem PLC 3 Set the port up as indicated below and then send the settings to the PLC by...

Страница 11: ...ne line On the PLC side you connect your cables as shown at the beginning of this document You will need to connect your modem to a phone line and establish the number extensions and delays between th...

Страница 12: ...this is required in your facility You may also need to add commas for time delays when appropriate One comma equals about one second 3 Choose the K sequence protocol and setup the time delays as shown...

Страница 13: ...re download the configuration to verify the correct setup The modem driver is not configured properly Consult the steps in this document to verify modem driver setup The wrong modem may be answering T...

Страница 14: ...cation to start transmitting data Here is an example wiring diagram You must make sure that you use the correct I O cards for this The output from the PLC to initiate the modem dialing requires either...

Страница 15: ...modem configuration will be very similar to the settings listed earlier in this document ADC Modem Configuration The remote modem configuration will be the same as before The local modem will differ o...

Страница 16: ...tion you are requesting and the remote PLC with which you are communicating You should write the code and setup the communication port is the same manner that you would for a direct connection between...

Отзывы: