Cooling and Heat Dissipation

Airflow Rate for Cooling

Power Dissipation (Watts)

Model 

Number

Flow Rate 

(cfm)

Flow Rate 

(m

3

/hr)

Loss External

(Heat sink)

Internal

Total

GS21X-20P5

0.0

0.0

16.3

14.5

30.8

GS21X-21P0

29.1

20.1

49.2

GS23X-20P5

16.5

12.6

29.1

GS23X-21P0

29.1

20.1

49.2

GS23X-40P5

17.6

11.1

28.7

GS23X-41P0

30.5

17.8

48.3

GS21X-22P0

46.5

31

77.5

GS23X-22P0

50.1

24.2

74.3

GS23X-42P0

45.9

21.7

67.6

GS23X-43P0

60.6

22.8

83.4

GS21X-23P0

27.3

46.4

70.0

35.0

105.0

GS23X-23P0

76.0

30.7

106.7

GS23X-25P0

108.2

40.1

148.3

GS23X-45P0

93.1

42.0

135.1

GS23X-27P5

33.5

56.6

192.8

53.3

246.1

GS23X-47P5

132.8

39.5

172.3

GS23X-4010

164.7

53.3

246.1

•  External Flow Rate is across the heat sink.

•  Internal Flow Rate is through the chassis.

•  Published flow rates are the result of active 

cooling using fans, factory installed in the 

drive.

•  Unpublished flow rates ( - ) are the result 

of passive cooling in drives without factory 

installed fans.

•  The required airflow shown in the chart 

is for installing a single GS20X drive in a 

confined space.

•  When installing multiple GS20X drives, the 

required air volume would be the required 

air volume for a single GS20X drive 

multiplied by the number of GS20X drives.

•  When calculating power dissipation (Watt 

Loss), use the Total value. Heat dissipation 

shown in the chart is for installing a single 

GS20X drive in a confined space.

•  When installing multiple drives, the volume 

of heat/power dissipation should be the heat/

power dissipated by a single GS20X drive 

multiplied by the number of GS20X drives. 

•  Heat dissipation for each model is calculated 

by rated voltage, current and default carrier 

frequency.

Environment for Operation, Storage, and Transportation

Do not place the GS20X drive in a critical environment, such as direct contact with chemical substance and 

solvent, or exposure to direct sunlight.

Envir

onment

Installation Location

PCB design is compliant with IEC60364-1/IEC60664-1 Pollution degree 2. The outer case 

meets IP66 standard for indoor use. If the drive is for outdoor application, avoid direct 

sunlight.

Surrounding 

Temperature

Operation:  -20°C to +40°C, -20°C to +50°C with derating
Storage:  -40°C to +85°C

Transportation:  -20°C to +70°C

No condensation, non-freezing

Rated Humidity

Operation:  0

100%

Storage/Transportation:  Max. 95%

No condensed water

Air Pressure

Operation:  86 to 106 kPa

Storage/Transportation:  70 to 106 kPa

Pollution Level

IEC60721-3
Operation:  

Class 3C2; Class 3S2

Storage:  

Class 2C2; Class 2S2

Transportation:  

Class 1C2; Class 1S2

No concentrate

Altitude

Operation

If the GS20X drive is installed at altitudes of 0~1000m, follow normal 

operation restriction.  If installed at altitudes of 1000~2000m, decrease 

1% of rated current or lower 0.5°C of temperature for every 100m 

increase in altitude.  Maximum altitude for Corner Grounded is 2000m. 

Contact ADC for more information if you need to use this motor drive at 

an altitude of 2000m or higher.

Package 

Drop

Storage

ISTA procedure 1A (according to weight) IEC60068-2-31

Transportation

Vibration

Operating

1.0mm, peak-to-peak value range from 2Hz to 13.2 Hz; 0.7G~1.0G range from 

13.2Hz to 55Hz; 2.0G range from 55Hz to 512 Hz.  Complies with IEC 60068-2-6.

Non-operating

2.5 G peak, 5Hz~2kHz: 0.015” maximum displacement.

Impact

Operating

IEC/EN60068-2-27: 15G, 11ms

Non-operating

30G

Protection Level

IP66 / NEMA4X

To prevent personal injury, please make sure that the case and wiring are installed 
according to these instructions.  The figures in these instructions are only for reference.  
They may be slightly different from the one you have, but it will not affect your 
customer rights.
These installation instructions may be revised without prior notice.  The most recent 
edition can be downloaded from the AutomationDirect web site at any time: 
http://www.automationdirect.com/static/manuals/index.html.

Minimum Mounting Clearances

When installing your GS20X drive, please keep the following in mind:

•  Prevent fiber particles, scraps of paper, shredded wood, saw dust, metal particles, etc., from adhering to the 

heat sink.

•  Install the AC motor drive in an incombustible (non-flammable) indoor environment to prevent the risk of 

accidental fire.

•  Install the AC motor drive in Pollution Degree 2 environments only: normally only nonconductive pollution 

occurs and temporary conductivity caused by condensation is expected.

 (Blue Arrow) Inflow       

 (Red Arrow) Outflow

Single drive Independent installation.

Installation Method

(mm)

(mm)

Ambient Temperature
Max 

(w/out derating)

Max 

(Derating)

Single drive installation

50

30

40

50

Отзывы: