MODULEX CONTROLLER OPERATION
A-10
A-4.
EXPERT AREA
The EXPERT Menu area includes the same Sub-Menu areas as the USER Menu described in paragraph
3.5. However, in order to change any settings, the valid Code No. (password) must be entered.
Whenever
“CODE NO.” is displayed, it indicates that the valid password must be entered. This is
accomplished by entering code 0000 (4 zeros) by pressing the Program Key 4 times.
As the following Table shows, the EXPERT Menu contains a large number of Functions, particularly in
the INSTALLATION Sub-Menu.
EXPERT MENU TABLE
FUNCTION
DESCRIPTION
ENTRY
RANGE
DEFAULT
INSTALLATION Sub-Menu
CODE-NO
Permits entry of valid Code No.(0000)
0000 - 9999
0000
BUS ID 1
The heating circuits are sequentially
numbered starting with "01", heating circuit
numbers must not be assigned twice
(00), 01 - 15
01
BUS ID 2
The heating circuits are sequentially
numbered starting with "01", heating circuit
numbers must not be assigned twice
(00), 01 - 15
- - - -
AF SUPPLY
Outdoor sensor power supply
00, 01 (OFF/ON)
01 (ON)
BUS TERM
Bus terminating resistor (Must be set to 01)
00, 01 (OFF/ON)
01 (ON)
EBUS SUPPLY
Switches the eBUS supply ON/OFF
00, 01 (OFF/ON)
01 (ON)
TIME MASTER
When set to 00, it indicates there is no time
master. When set to 01 the Controller is the
time master. LEAVE SET TO 00.
00, 01
00
(N/A)
MAX T-COLL
Sets the maximum allowable header set point
temperature.
30.0°C
–
110.0°C
85.0°C
MIN T-COLL
Sets the minimum allowable header set point
temperature.
10.0°C
– 80.0°C
10.0°C
MAX T-HS2
Sets the maximum allowable HS2 (Heat
Source 2) set point temperature
(Not Applicable)
30.0°C
–
110.0°C (N/A)
85.0°C
(N/A)
MIN T-HS2
Sets the minimum allowable HS2 set point
temperature.
10.0°C
– 80.0°C
40.0°C
V-CURVE
0 to 10 Volt input Voltage curves. Choose
from preset curves (see para. 3.5.1) or
customize a curve.
00 - 11
11
CURVE 11-U1
Low voltage setting
0.00V
– 10.00V
0.000
CURVE 11-U2
High voltage setting
0.00V
– 10.00V
10.00
CURVE 11-T1
Low temperature level setting (Min. set point
temperature)
0.0°C
– 120.0°C
15.0°C
CURVE 11-T2
High temperature level setting (Max. set point
temperature)
0.0°C
– 120.0°C
85.0°C
CURVE 11-UO
Stop/Start voltage level. Going below/above
this setting will stop/start the Boiler.
0.00V
– 10.00V
1.00
Содержание Modulex E8
Страница 1: ...Operation User Guide Modulex E8 Controller ...
Страница 30: ...MODULEX CONTROLLER OPERATION 28 Figure 3 7 INSTALLATION Menu Flow Chart ...
Страница 50: ......
Страница 51: ...MODULEX CONTROLLER OPERATION A 1 APPENDIX A CONTROLLER MENU LISTINGS ...
Страница 69: ...A 19 MODULEX CONTROLLER OPERATION NOTES ...