background image

Revised 7/30/02 • S6104

15

© 2002 Automated Logic Corporation

action pane. To retry a failed download, 
click the module in the Failures list, click 
Add, and click the Execute Download 
button again. If you do not want to retry a 
failed download, click the Clear Failures 
button.

NOTE

Since a failed download indicates 

a system problem, you should never clear 
a failure. Locate and resolve the problem, 
then retry the download.

6. Click the Properties button to refresh the 

screen. This removes the items from the 
Download Items list.

Transferring Memory in SuperVision

If you are using SuperVision to transfer 
memory, you must use SuperVision v2.6b or 
later, FB Link v2.7a or later, and the SLM 
module driver. The S6104 module using the 
SLM module driver can store a single FB. 

1. Log in to SuperVision on a workstation 

connected to the CMnet. You can also 
connect directly to the module using the 
Access Port or LogiStat Port; see 
“Communicating with the Workstation 
Using SuperVision” on page 6
.

2. Navigate to the module driver and look at 

the module status report in SuperVision to 
make sure the module type and number 
agree with the module.

• To view the module status report in 

SuperVision v3.0, click Tools - 
Troubleshooting - Module Status.

• To view the module status report in 

SuperVision v2.6b or later, press the 
[ESC} key, type 

MO ,,module address,15 

and press Enter.

3. Transfer memory to the module.

• In SuperVision v3.0, click Tools - 

Troubleshooting - Transfer Memory to 
Module.

• In SuperVision v2.6b, download 

memory for This Module.

4. When the memory transfer is finished, 

check the module status report again. 
Make sure the FB List on this page shows 
the FB you intended to transfer.

Troubleshooting

Formatting the Module

If you are unable to communicate with a 
module after transferring memory, you can, 
as a last resort, manually format the module 
to try to restore communication. Formatting 
the module erases all memory, so you need to 
transfer memory back to the module once it is 
formatted.

NOTE

Since the module is automatically 

formatted when you transfer memory, you 
should only manually format the module if 
communication was not established after the 
memory transfer.

1. Turn the module’s power off. Make sure 

the address switches are not set to ‘0 0’.

2. Press and hold the Format button (see 

Figure 1 on page 2 for location). While 
continuing to hold the Format button, turn 
the module’s power on.

3. Continue to hold the button until the Error 

LED flashes three times in sync with the 
Run LED.

4. Release the Format button.

5. Transfer memory to the module. Refer to 

“Transferring Memory” on page 14.

LEDs

The S6104 module has several LED indicators 
to show the status of certain functions. 
Table 9 on page 16 explains the Run and Error 
LED signals in detail to assist troubleshooting. 
See Figure 17 for location of LED signals.    

Содержание S6104

Страница 1: ...ounting 3 Addressing 3 Power Wiring 4 Network Communications 4 Using the S6104 on an ARC156 Segment 5 Using the S6104 on a Legacy CMnet 5 Connecting the S6104 to the Network 5 Communicating with the W...

Страница 2: ...log outputs A single board provides the power circuitry microprocessor and non volatile memory stores data even during a power failure The Access Port allows communication with WebCTRL or SuperVision...

Страница 3: ...Outputs 6 digital outputs Form A 3A max Analog Outputs 4 analog outputs 0 to 10VDC 20mA source capability Output resolution 8 bit D A Communication For WebCTRL 156 kbps BACnet over ARCNET and 9600 bp...

Страница 4: ...he S6104 has an operating range of 21 6VAC to 26 4VAC If voltage measured at the module s power input terminals is outside this range the module may not work properly 1 Turn the module s power off Thi...

Страница 5: ...lect jumper must also be set to Access NOTE Setting the CMnet jumper to Legacy disables the industry standard BACnet over ARCNET ARC156 protocol for the network segment and enables the proprietary ALC...

Страница 6: ...ommunication speed is fixed at 1200 baud 1 Connect the computer s serial port to the EIA 232 port of the APT using a standard straight through cable 2 Set the APT s Mode Select switch to TTL see Figur...

Страница 7: ...rt when finished to allow the S6104 to receive inputs from the LogiStat Communicating Through the Access Port Using SuperVision When using SuperVision you can connect a workstation or portable compute...

Страница 8: ...ource to power the 4 20mA transducer The B terminal is capable of supplying 18 to 24VDC but the total current of all B terminals must not exceed 200mA If the voltage measured from the B terminal to Gn...

Страница 9: ...e of sensor used Make sure the jumper is positioned correctly and be sure to grip the jumper by the sides only See Figure 10 Figure 8 Input Wiring 15 16 17 18 20 19 14 13 12 11 10 9 8 7 6 5 4 3 2 1 IN...

Страница 10: ...pin 2 Temp of the LogiStat Port The LogiStat Plus also provides the slidepot position and TLO inputs through pin 3 Sw The LogiStat Pro provides temperature setpoint adjust and TLO inputs through seria...

Страница 11: ...mode by setting the HOA switches see Figure 1 on page 2 for the switches location Table 5 on page 12 shows the status of the digital output based on the output s configuration and the HOA switch posit...

Страница 12: ...put s operation lock the output to a known condition using the Function Block s Properties page in WebCTRL or Parameter page in SuperVision Be sure the equipment operates as specified Writing GFBs for...

Страница 13: ...pend on the type of sensor or actuator attached to the I O point You can select the channel number offset and gain using SuperVision s Point Help feature or Configure Points utility Alternatively you...

Страница 14: ...ute Download button If any downloads failed they are listed in the Failures section under the tree in the UI 2 Thermistor 32 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 mA or Volts 32 0 to 20mA 0...

Страница 15: ...SC key type MO module address 15 and press Enter 3 Transfer memory to the module In SuperVision v3 0 click Tools Troubleshooting Transfer Memory to Module In SuperVision v2 6b download memory for This...

Страница 16: ...imal Figure 17 S6104 LED locations Table 9 LED Signals Run LED Error LED Condition 2 flashes per second Off Normal 2 flashes per second 1 flash then pause Normal but module is alone on the CMnet this...

Отзывы: