background image

Revised 7/30/02 • S6104

14

© 2002 Automated Logic Corporation

Transferring Memory

You should download memory whenever you 
make changes to your modules (for example, 
change the module number, upgrade the 
module driver, or change the FB).

The S6104 can store a single Function Block 
in addition to the module driver. If any 
problems occur during this procedure, 
contact Technical Support at (770) 429-3002.

NOTE

A memory download should be 

performed with caution. When the module is 
automatically restarted before and after 
transferring memory, any equipment 
controlled by the module is shut down and 
restarted. Downloading memory also 
overwrites all Function Blocks in the module 
causing the module to lose any stored data.

Transferring Memory in WebCTRL

If you are using WebCTRL to transfer memory, 
you must use the DRV_S6104 module driver. 
You must be logged in to WebCTRL with the 
appropriate privilege to download memory. 
For more information about using WebCTRL, 
refer to the 

WebCTRL Configuration Guide

.

1. Click the CFG button at the bottom of the 

navigation pane.

2. Click Download in the CFG tree control.

3. Click the Memory, Parameters, or 

Schedules boxes, depending on what you 
want to download.

NOTE

A memory download includes a 

parameter and schedule download.

4. Expand the tree in the action pane, click 

the module you want to download to, 
then click Add. Click on and Add any 
other modules you want to download to.

5. Click the Execute Download button. 

If any downloads failed, they are listed in 
the Failures section under the tree in the 

UI 2

Thermistor

32

-17° to 213° F
-27° to 100.6° C

0.00
0.00

15.88
15.69

mA or Volts

32

0 to 20mA
0 to 5V

§

§

Digital

22

UI 3

Thermistor

33

-17° to 213° F
-27° to 100.6° C

0.00
0.00

15.88
15.69

mA or Volts

33

0 to 20mA
0 to 5V

§

§

Digital

23

UI 4

Thermistor

34

-17° to 213° F
-27° to 100.6° C

0.00
0.00

15.88
15.69

mA or Volts

34

0 to 20mA
0 to 5V

§

§

Digital

24

UI 5

Thermistor

35

-17° to 213° F
-27° to 100.6° C

0.00
0.00

15.88
15.69

mA or Volts

35

0 to 20mA
0 to 5V

§

§

Digital

25

UI 6

Thermistor

36

-17° to 213° F
-27° to 100.6° C

0.00
0.00

15.88
15.69

mA or Volts

36

0 to 20mA
0 to 5V

§

§

Digital

26

UI 7

Thermistor

37

-17° to 213° F
-27° to 100.6° C

0.00
0.00

15.88
15.69

mA or Volts

37

0 to 20mA
0 to 5V

§

§

Digital

27

UI 8

Thermistor

38

-17° to 213° F
-27° to 100.6° C

0.00
0.00

15.88
15.69

mA or Volts

38

0 to 20mA
0 to 5V

§

§

Digital

28

UI 9 *

Thermistor 39

-17° to 213° F
-27° to 100.6° C

0.00
0.00

15.88
15.69

mA or Volts

39

0 to 20mA
0 to 5V

§

§

Digital

29

UI 10 *

Thermistor

3A

-17° to 213° F
-27° to 100.6° C

0.00

15.88
15.69

mA or Volts

3A

0 to 20mA
0 to 5V

Digital 2A

* This input is not available when using a LogiStat or LogiStat Plus.
† Celsius values can only be displayed in SuperVision when the Function 
Block is made in Eikon v2.0 or later with the Metric option enabled. Refer to 
the Eikon User’s Guide for more information.
§ For ALC 0-20mA sensors, use the offset and gain printed on the sensor. 
Otherwise use the Point Configuration or Point Help feature in SuperVision 
v2.0 or later.

Table 8. Universal Input Channel Numbers 

Point

Signal Type

Channel
Number

†Range Offset

Gain

Содержание S6104

Страница 1: ...ounting 3 Addressing 3 Power Wiring 4 Network Communications 4 Using the S6104 on an ARC156 Segment 5 Using the S6104 on a Legacy CMnet 5 Connecting the S6104 to the Network 5 Communicating with the W...

Страница 2: ...log outputs A single board provides the power circuitry microprocessor and non volatile memory stores data even during a power failure The Access Port allows communication with WebCTRL or SuperVision...

Страница 3: ...Outputs 6 digital outputs Form A 3A max Analog Outputs 4 analog outputs 0 to 10VDC 20mA source capability Output resolution 8 bit D A Communication For WebCTRL 156 kbps BACnet over ARCNET and 9600 bp...

Страница 4: ...he S6104 has an operating range of 21 6VAC to 26 4VAC If voltage measured at the module s power input terminals is outside this range the module may not work properly 1 Turn the module s power off Thi...

Страница 5: ...lect jumper must also be set to Access NOTE Setting the CMnet jumper to Legacy disables the industry standard BACnet over ARCNET ARC156 protocol for the network segment and enables the proprietary ALC...

Страница 6: ...ommunication speed is fixed at 1200 baud 1 Connect the computer s serial port to the EIA 232 port of the APT using a standard straight through cable 2 Set the APT s Mode Select switch to TTL see Figur...

Страница 7: ...rt when finished to allow the S6104 to receive inputs from the LogiStat Communicating Through the Access Port Using SuperVision When using SuperVision you can connect a workstation or portable compute...

Страница 8: ...ource to power the 4 20mA transducer The B terminal is capable of supplying 18 to 24VDC but the total current of all B terminals must not exceed 200mA If the voltage measured from the B terminal to Gn...

Страница 9: ...e of sensor used Make sure the jumper is positioned correctly and be sure to grip the jumper by the sides only See Figure 10 Figure 8 Input Wiring 15 16 17 18 20 19 14 13 12 11 10 9 8 7 6 5 4 3 2 1 IN...

Страница 10: ...pin 2 Temp of the LogiStat Port The LogiStat Plus also provides the slidepot position and TLO inputs through pin 3 Sw The LogiStat Pro provides temperature setpoint adjust and TLO inputs through seria...

Страница 11: ...mode by setting the HOA switches see Figure 1 on page 2 for the switches location Table 5 on page 12 shows the status of the digital output based on the output s configuration and the HOA switch posit...

Страница 12: ...put s operation lock the output to a known condition using the Function Block s Properties page in WebCTRL or Parameter page in SuperVision Be sure the equipment operates as specified Writing GFBs for...

Страница 13: ...pend on the type of sensor or actuator attached to the I O point You can select the channel number offset and gain using SuperVision s Point Help feature or Configure Points utility Alternatively you...

Страница 14: ...ute Download button If any downloads failed they are listed in the Failures section under the tree in the UI 2 Thermistor 32 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 mA or Volts 32 0 to 20mA 0...

Страница 15: ...SC key type MO module address 15 and press Enter 3 Transfer memory to the module In SuperVision v3 0 click Tools Troubleshooting Transfer Memory to Module In SuperVision v2 6b download memory for This...

Страница 16: ...imal Figure 17 S6104 LED locations Table 9 LED Signals Run LED Error LED Condition 2 flashes per second Off Normal 2 flashes per second 1 flash then pause Normal but module is alone on the CMnet this...

Отзывы: