Automated Logic MX400 Скачать руководство пользователя страница 3

Revised 4/3/00 • MX400

3

© 2000 Automated Logic Corporation

Mounting

Screw the MX400 into an enclosed panel
using the mounting holes provided on the
cover plate. Be sure to leave about 2 inches (5
centimeters) on each side for wiring.

Addressing

Before setting or changing the address, make
sure the MX400’s power is off. The MX400
only reads the address when the module is
turned on.

The MX400 uses a rotary switch to assign the
module’s expander number. If the module’s
expander address is three, set the switch to
three, as shown in Figure 2.

Power Wiring

Whenever possible, make sure the module’s
power and communications connections are
working properly before connecting any input
or output points.

CAUTION

The MX400 module is a Class 2

device (less than 30VAC, 100VA maximum).
Take appropriate isolation measures when
mounting the MX400 module in a control
panel where non-Class 2 devices (for
example, 120VAC) or wiring are present.

You can power several modules from the
same transformer if you maintain the same
polarity.

The MX400’s operating range is 21.6VAC to
26.4VAC. If voltage measured at the module’s

power input terminals is outside this range,
the module may not work properly.

1. Turn the module’s power off. This

prevents the module from being powered
up before the proper voltage is verified.

2. Make sure the 24VAC power source is off.

3. Connect the power wires to the module’s

power terminals labeled Ground and
24VAC (see Figure 1 on page 2 for
location).

4. Apply power to the transformer.

5. Make sure that 24VAC is present at the

module’s power input terminals.

6. Set the module’s address. Refer to

“Addressing” for details about setting the
address.

7. Turn the module’s power switch on.

When the module turns on, the Run and
Power LEDs turn on. The Run LED begins
blinking and the Error LED turns off. See
“LEDs” on page 4 to troubleshoot the
LEDs. If the module does not respond, call
Technical Support at (770) 429-3002.

Digital Outputs

The MX400 module has four digital outputs
that can be connected to a maximum of 24
Volts AC/DC. Each output is a dry contact
(rated at 3A, 24VAC maximum) that can be
configured as normally open or normally
closed, according to the jumper setting.

Be sure the MX400’s power is off before
wiring any inputs or outputs. Connect the
output wiring to the screw terminals on the
module as shown in Figure 3 on page 4.

NOTE

Do not power pilot relays from the

same transformer that powers the MX400.

To verify each output’s operation, lock the
output to a known condition using the

Figure 2. Setting the expander’s address

1's

Содержание MX400

Страница 1: ... and Alert are registered trademarks of Automated Logic Corporation InterOp is a trademark of Automated Logic Corporation BACnet is a registered trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions MX400 Using the MX400 2 Specifications 2 Mounting 3 Addressing 3 Power Wiring 3 Digital Outputs 3 Channel Numbers 4 Troubleshooting ...

Страница 2: ...ea is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Specifications Power 24VAC 10 50 60Hz 24VAC 10 60Hz for UUKL Smoke Control Systems 8VA power consumption single Class 2 source only 100VA or less Digital Outputs four digital outputs relay contacts rated at 3A resistive 24VAC Configurable as normally open or normally cl...

Страница 3: ... properly 1 Turn the module s power off This prevents the module from being powered up before the proper voltage is verified 2 Make sure the 24VAC power source is off 3 Connect the power wires to the module s power terminals labeled Ground and 24VAC see Figure 1 on page 2 for location 4 Apply power to the transformer 5 Make sure that 24VAC is present at the module s power input terminals 6 Set the...

Страница 4: ...ooting LEDs The MX400 module has several LED indicators to show the status of certain functions Power lights when power is being supplied to the module Run flashes to indicate a normal condition Expander Comm flashes to indicate expansion bus communications are valid Digital Output Status lights when the digital output is activated Protection The MX400 module is protected by internal solid state P...

Страница 5: ... in SuperVision Refer to the SuperVision User s Guide for more information about the module status report A sticker on the back of the module also shows the date the module was manufactured The first three characters on the sticker indicate the type of module The next three characters show the year month and week of manufacture The month digit is in hexadecimal ...

Отзывы: