Revised 9/13/00 • MX16160
6
© 2000 Automated Logic Corporation
You can monitor the status of the HOA
switches through SuperVision by assigning
each switch a digital input in the FB using
channel numbers 81 through 96. Channel 81
corresponds to HOA switch number one;
channel 82 corresponds to HOA switch two,
and so on. Switches 10 through 15 use
channel numbers 8A through 8F, and switch
16 uses channel number 80.
An off status on these channels means the
HOA switch is in Auto mode. An on status
means the HOA switch is in Manual mode.
Channel Numbers
The following tables show the valid channel
numbers for each point on the MX16160.
Enter the channel number, offset, and gain for
each point in Eikon before the Function Block
is made, or on the FB’s Parameter page in
SuperVision. If an offset and gain are not
provided here, use SuperVision’s Point
Configuration or Point Help feature to
determine the offset and gain.
Table 3. Digital Output Channel Numbers
Point
Signal Type
Channel
Number
DO 1
Digital
HOA Status†
11
81
DO 2
Digital
HOA Status†
12
82
DO 3
Digital
HOA Status†
13
83
DO 4
Digital
HOA Status†
14
84
DO 5
Digital
HOA Status†
15
85
DO 6
Digital
HOA Status†
16
86
DO 7
Digital
HOA Status†
17
87
DO 8
Digital
HOA Status†
18
88
DO 9
Digital
HOA Status†
19
89
DO 10
Digital
HOA Status†
1A
8A
DO 11
Digital
HOA Status†
1B
8B
DO 12
Digital
HOA Status†
1C
8C
DO 13
Digital
HOA Status†
1D
8D
DO 14
Digital
HOA Status†
1E
8E
DO 15
Digital
HOA Status†
1F
8F
DO 16
Digital
HOA Status†
10
80
† Use digital input microblocks to
monitor the status of HOA Switches.
Table 4. Input Channel Numbers
Point
Signal Type
Channel
Number
†Range Offset
Gain
UI 1
Thermistor
31
-17° to 213° F
-27° to 100.6° C
0.00
0.00
15.88
15.69
mA or Volts
31
0 to 20mA
0 to 5V
§
§
Digital
21
UI 2
Thermistor
32
-17° to 213° F
-27° to 100.6° C
0.00
0.00
15.88
15.69
mA or Volts
32
0 to 20mA
0 to 5V
§
§
Digital
22
UI 3
Thermistor
33
-17° to 213° F
-27° to 100.6° C
0.00
0.00
15.88
15.69
mA or Volts
33
0 to 20mA
0 to 5V
§
§
Digital
23
UI 4
Thermistor
34
-17° to 213° F
-27° to 100.6° C
0.00
0.00
15.88
15.69
mA or Volts
34
0 to 20mA
0 to 5V
§
§
Digital
24
UI 5
Thermistor
35
-17° to 213° F
-27° to 100.6° C
0.00
0.00
15.88
15.69
mA or Volts
35
0 to 20mA
0 to 5V
§
§
Digital
25
UI 6
Thermistor
36
-17° to 213° F
-27° to 100.6° C
0.00
0.00
15.88
15.69
mA or Volts
36
0 to 20mA
0 to 5V
§
§
Digital
26
UI 7
Thermistor
37
-17° to 213° F
-27° to 100.6° C
0.00
0.00
15.88
15.69
mA or Volts
37
0 to 20mA
0 to 5V
§
§
Digital
27
Table 3. Digital Output Channel Numbers
Point
Signal Type
Channel
Number