background image

Revised 11/6/02 • LGRM-E

4

© 2002 Automated Logic Corporation

Before setting or changing the address, make 
sure the LGRM-E’s power is off. The LGRM-E 
only reads the address when the module is 
turned on. After changing the address, you 
must transfer memory to the module. Refer to 
“Transferring Memory” on page 7.

IP Addressing

TCP/IP must be set up on the workstation 
with an active IP address before configuring 
the module’s IP address (refer to the 

TCP/IP 

Setup for SuperVision Workstations Technical 
Instructions

 for a detailed procedure).

You can use a default IP address for the 
LGRM-E that is created by the module, or 
assign an IP address if required by the 
customer. The IP ADD switch (Figure 2 on 
page 3
) determines which IP address is used.

• Default: When the IP ADD switch is set 

to Default, the following IP networking 
parameters are automatically set on the 
LEM Parameter page:

IP Address = 192.168.168.XXX

, where 

XXX is the LGRM-E’s LGnet address (see 
“LGnet addressing” on page 3).

Subnet Mask = 255.255.255.0

Default Gateway Address = 

192.168.168.254

NOTE

The default gateway address is 

an intranet address. This means that the 
data packets from this address are 
dropped by all internet routers and are 
not sent beyond the local network 
segment.

• Assigned: When the IP ADD DIP switch 

is set to Assigned, you must set the 
above parameters on the LEM 
Parameter page.

Default mode

Use the following procedure to set the IP 
address when using the Default mode:

1. Set the IP ADD DIP switch to Default.

2. Turn the LGRM-E’s power on.

3. If using SuperVision v2.6, edit your HOSTS 

file to include the following line for each 
gateway (see the 

TCP/IP Setup for 

SuperVision Workstations Technical 
Instructions

 for a detailed procedure):

192.168.168.x

Where x is the gateway’s address as 
defined in “LGnet addressing” on page 3.

4. If using SuperVision v2.6, run Setup.exe 

on the disk shipped with your LGRM-E.

This setup copies updated Portman files to 
your emsys folder.

5. Configure the connection as Network in 

SuperVision Plus v3.01 and later or 
NetBIOS in SuperVision v2.6.

Assigned mode

Use the following procedure to set the IP 
address when using the Assigned mode:

1. Obtain an IP address from the job site’s 

Network Administrator.

2. Set the IP ADD DIP switch to Assigned.

3. If using SuperVision v2.6, edit your HOSTS 

file to include the following line for each 
gateway (see 

TCP/IP Setup for SuperVision 

Workstations Technical Instructions 

for a 

detailed procedure):

IP Address LGx

Where IP Address is the address assigned 
by the Network Administrator and x is the 
gateway’s LGnet address.

4. If using SuperVision v2.6, run Setup.exe 

on the disk shipped with your LGRM-E.

Содержание LGRM-E

Страница 1: ...rOp is a trademark of Automated Logic Corporation BACnet is a registered trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions LGRM E Using the LGRM E 2 Specifications 3 Mounting 3 Addressing 3 LGnet addressing 3 IP Addressing 4 Wiring 5 Power Wiring 5 Communications Wiring 5 Initializing the LGRM E 6 Transferring Memory 7 Troubl...

Страница 2: ...e Automated Logic website at www automatedlogic com or on the SupportPlus CD NOTE This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can ...

Страница 3: ...s on the faceplate see Figure 1 on page 2 If a rack is not available the LGRM E can be mounted with mounting brackets The LGRM E is designed to be mounted inside the building All warranties are void if mounted outside CAUTION Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user s authority to operate equipment Addressing LGnet add...

Страница 4: ...ocal network segment Assigned When the IP ADD DIP switch is set to Assigned you must set the above parameters on the LEM Parameter page Default mode Use the following procedure to set the IP address when using the Default mode 1 Set the IP ADD DIP switch to Default 2 Turn the LGRM E s power on 3 If using SuperVision v2 6 edit your HOSTS file to include the following line for each gateway see the T...

Страница 5: ...nect power to the LGRM E 1 Turn off the LGRM E s power switch 2 Connect the terminal strip connector see Figure 4 to the power connector on the back of the LGRM E see Figure 5 on page 6 3 Plug the power adaptor into an outlet 4 Turn the module s power switch on When the module turns on the Run and Power LEDs turn on The Run LED begins blinking and the Error LED turns off See Table 3 on page 10 to ...

Страница 6: ...ame polarity as used throughout the rest of the CMnet 3 Make sure the LGRM E is configured for the correct communication speed Connecting to the LGnet Connect a LAN 10base T cable to the Ethernet port Connecting to a Workstation or Modem Connect the DC95 or DC99 cable to console port 1 or 2 See Communicating with the Workstation on page 7 for more details NOTE The EIA 232 connection should not exc...

Страница 7: ...ver and look at the module status report in SuperVision to make sure the module type and number agree with the module To view the module status report in SuperVision v3 0 click Tools Troubleshooting Module Status To view the module status report in SuperVision v2 6b press the Esc key type MO module address 15 and press Enter 3 Transfer memory to the module In SuperVision v3 0 click Tools Troublesh...

Страница 8: ... Port 9 pin 20 DTR 7 GND 8 DCD 3 RX 2 TX Workstation 25 pin DCD 1 DTR 4 TX 3 RX 2 GND 5 Console Port 9 pin DS R 6 RI 9 CTS 8 RTS 7 8 DCD 20 DTR 2 TX 3 RX 7 GND Modem 25 pin 6 DSR 22 RI 5 CTS 4 RTS G ND 5 TX 1 RX 2 Console Port 5 pin 5 GND 2 RX 3 TX W orkstation 9 pin Console Port 2 DTR 3 20 DTR TX 1 2 TX RX 2 3 RX GND 5 7 G ND Console Port 5 pin DCD 4 8 DCD Modem 25 pin W ire connection usually no...

Страница 9: ... on page 2 for location While continuing to hold the Format button turn the module s power on 3 Continue to hold the button until the Error LED flashes three times in sync with the Run LED 4 Release the Format button 5 Transfer memory to the module Refer to Transferring Memory on page 7 LEDs The LGRM E has several LED indicators to show the status of certain functions Table 3 on page 10 explains t...

Страница 10: ...out the module status report A sticker on the back of the module also shows the date the module was manufactured The first three characters on the sticker indicate the type of module The next three characters show the year month and week of manufacture The month digit is in hexadecimal Table 3 LED Signals Run LED Error LED Condition 2 flashes per second Off Normal 2 flashes per second 1 flash per ...

Отзывы: