Revised 12/22/99 • LGE

7

© 1999 Automated Logic Corporation

2. Set the APT’s Mode Select switch.

• On an ARC156 CMnet, use the TTL

setting.

• On a legacy CMnet, use the 485 setting.

3. Connect the APT’s Access Port to the

module’s Access Port.

4. In SuperVision, define the connection type

using Table 2.

Formatting the Module

When you are unable to communicate with a
module, you can, as a last resort, manually
format the module to try to restore
communication. Formatting the module
erases all memory, so you need to transfer
memory back to the module once it is
formatted.

1. Turn the module’s power off. Make sure

the module’s address switches are not set
to ‘0 0’.

2. Press and hold the Format button (see

Figure 1 on page 2 for location). While
continuing to hold the Format button, turn
the module’s power on.

3. Continue to hold the button until the Error

LED flashes three times in sync with the
Run LED.

4. Release the Format button.

5. Transfer memory to the module. Refer to

“Transferring Memory” on page 6.

Figure 5. Wiring Diagrams

Figure 6. Using the Access Port

*DTR 4

GND 5

*DCD 1

RX 2

TX 3

Console Port

(9 pin)

1 DCD*

5 GND

4 DTR*

3 TX

2 RX

Workstation

(9 pin)

*DCD 1

GND 5

*DTR 4

TX 3

RX 2

Console Port

(9 pin)

20 DTR*

7 GND

8 DCD*

3 RX

2 TX

W orkstation

(25 pin)

*DCD 1

*DTR 4

TX 3

RX 2

GND 5

Console Port

(9 pin)

*DSR 6

*RI 9

**CTS 8

**RTS 7

8 DCD*

20 DTR*

2 TX

3 RX

7 GND

Modem
(25 pin)

6 DSR*

22 RI*

5 CTS**

4 RTS**

* Wire connection usually not needed
** Needed only if hardware handshaking is used

9

Rx

6 1

2- Tx o ut
3- R x i n
5- Gnd
1,6,8- +10 V or flo atin g

Tx

+5V

APT

5

Ex ec . 4 relay

Is olate Netwo rk

Mode S elec t

TTL

485

ACCESS

POR T

EIA-232

Port

Mode Select

Switch

Exec. 4 relay

Switch

Access

Port

G ro u n d

2 4 V a c

O p t i o n a l

S h e il d

N et -

N e t +

LGE

Table 2. Connection Types

SuperVision

Version

Type of

CMnet

Use Connection Type

3.0

any

Access Port

2.6

ARC156

Direct Connect

2.6

legacy

Direct Network

Содержание LGE

Страница 1: ...Corporation InterOp is a trademark of Automated Logic Corporation BACnet is a registered trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical I...

Страница 2: ...ion The LGE uses the CEM module driver for more information see the CEM Module Driver document on the Automated Logic website at www automatedlogic com CAUTION Changes or modifications to this unit no...

Страница 3: ...net Console Port 1 and Ethernet communications errors running and power Memory 1 MB flash 1 MB RAM Protection Built in surge and transient protection circuitry Battery 7 year lithium BR2325 battery pr...

Страница 4: ...d the local network segment Assigned When the IP Addr DIP switch is set to Assigned you must set the above parameters on the CEM Parameter page Use the following procedure to set the IP address when u...

Страница 5: ...s the module from being powered up before the proper voltage is verified 2 Make sure the 24VAC power source is off 3 Connect the power wires to the module s power terminals labeled Ground and 24VAC se...

Страница 6: ...erVision v3 0 click Tools Troubleshooting Module Status To view the module status report in SuperVision v2 6b press the Esc key type MO module address 15 and press Enter 3 Transfer memory to the modul...

Страница 7: ...l the Error LED flashes three times in sync with the Run LED 4 Release the Format button 5 Transfer memory to the module Refer to Transferring Memory on page 6 Figure 5 Wiring Diagrams Figure 6 Using...

Страница 8: ...ion Refer to the SuperVision User s Guide for more information about the Module Status report A sticker on the back of the module also shows the date the module was manufactured The first three charac...

Отзывы: