background image

Revised 11/19/99 • BACview

2

Hardware Guide

3

© 1999 Automated Logic Corporation

Specifications

Power

24 VAC ± 10% 50-60 Hz at 350 mA,

8.4 VA supplied by the 14 conductor
ribbon cable (see Figure 2).

Software Requirements

Screen files

must be transferred to the module
connected to the BACview

2

. Refer to the

BACview

2

Programmer's Guide

and the

BACview Programmer’s Tutorial

for further

information.

Module Interface

14-pin proprietary

auxiliary device port.

Hardware Requirements

Use the

BACview

2

with any Exec 6.0 (or later)

control module with a 14-pin auxiliary
device port. For instructions on using the
BACview

2

, refer to the

BACview

2

User's

Guide

.

Operating Temperature Range

32 - 120

°F, or 0 °C to 48.9 °C; 10 to 90% relative
humidity (non-condensing).

Protection

Provides 12KV human

discharge model protection to the
encloser.

Listed By

PAZX (UL 916), cUL C22.2

No.205-M1983.

Mounting

The BACview

2

rear mounting plate (see

Figure 2) has four mounting holes and one
opening for the 14 conductor ribbon cable.
The rear mounting plate can be removed by
releasing the four screws on the sides and is
used as a template for mounting. There are
typically two different types of mounting,
Types I and II.

NOTE

If this equipment is used in a manner

not specified by the manufacturer, the
protection provided by the equipment may be
impaired.

Type I Mounting

The BACview

2

can be mounted onto a panel

directly above the module it will
communicate with (see Figure 3 on page 4).

1. Remove the rear mounting plate screws

(see Figure 2 for location) from the
BACview

2

.

2. Remove the rear mounting plate from the

BACview

2

.

Figure 2. Rear Mounting Plate

Mounting Holes

14 Pin TTL Connector

14 Conductor
Ribbon Cable

Rear Mounting
Plate Screws

Mounting Holes

Rear Mounting
Plate Screws

Содержание BACview2

Страница 1: ...o SuperVision Eikon and Alert are registered trademarks of Automated Logic Corporation InterOp is a trademark of Automated Logic Corporation BACnet is a registered trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions BACview2 Hardware Guide Introduction 2 Specifications 3 Mounting 3 Type I Mounting 3 Type II Mounting 4 BACview2 ...

Страница 2: ...ng you to view and change parameters locally without a separate computer However the BACview2 was not designed to serve as a job start up tool It is meant to help you operate your control system by allowing local access to the most commonly changed parameters Note that any parameter changes issued from the BACview2 exist only in the module until you transfer them to the workstation The BACview2 ca...

Страница 3: ...discharge model protection to the encloser Listed By PAZX UL 916 cUL C22 2 No 205 M1983 Mounting The BACview2 rear mounting plate see Figure 2 has four mounting holes and one opening for the 14 conductor ribbon cable The rear mounting plate can be removed by releasing the four screws on the sides and is used as a template for mounting There are typically two different types of mounting Types I and...

Страница 4: ...2 on page 3 Be sure not to bend or pinch the ribbon cable beneath the rear mounting plate 7 Connect the ribbon cable to the face of the BACview2 8 Reattach the BACview2 to the rear mounting plate 9 Connect the ribbon cable to the module s Auxiliary Device port mounted inside the panel box see Figure 4 on page 5 BACview2 Wiring CAUTION The BACview2 is a Class 2 device less than 30 VAC 100VA max Tak...

Страница 5: ...x p ans ion A B A B A B A B A B A B A B A B IN 1 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 IN 9 IN 10 IN 11 IN 12 IN 13 IN 14 IN 15 IN 16 IN 24 IN 23 IN 22 IN 21 IN 20 IN 19 IN 18 IN 17 B A B A B A B A B A B A B A B A IN 32 IN 31 IN 30 IN 29 IN 28 IN 27 IN 26 IN 25 B A B A B A B A B A B A B A B A 0 2 0 m A 0 5 V d c T h e r m i s to r d r y c o n t a c t O n O f f G n d 2 4 V a c C la s s 2 2 4 V a c 5 0...

Отзывы: