SINGLE OPERATING MANUAL
15
Figure 5
–
The Station foundation
WARNING!
Only qualified personnel should connect the power cable to the AC mains.
It is recommended to select the cross-section of the power cable based on the ChS power
(copper stranded conductor with a cross-
section of 5×16mm
2
to 5×25mm
2
).
Table. Recommended cross-section of power cable
Charging Station power, kW
Power cable cross-section, mm
2
16
5×2.5
32
5×6
40
5×10
80
5×35
When laying the power cable, an AC circuit breaker should be installed between the Station
and the mains. Depending on the Charging Station power and the number of connected phases,
it is recommended to use a 2-pole (for single-phase connection), 4-pole (for three-phase
connection) circuit breaker in the range from 16A to 80A.